Applications Guide Applications Guide

Applications Guide - PDF document

valerie
valerie . @valerie
Follow
342 views
Uploaded On 2020-11-24

Applications Guide - PPT Presentation

1 2 Acti 9Protection for specialised applicationsActi 9 is Schneider Electric146s new core modular system that makes your power distribution installation safer simpler and more efficientWhatever ID: 823350

breaker circuit protection vigi circuit breaker vigi protection current iec ic60 60947 class 25a terminal temperature 63a ic60n breaking

Share:

Link:

Embed:

Download Presentation from below link

Download Pdf The PPT/PDF document "Applications Guide" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

1Applications Guide2Acti 9Protection
1Applications Guide2Acti 9Protection for specialised applicationsActi 9 is Schneider Electric’s new core modular system that makes your power distribution installation safer, simpler and more efficient.Whatever your specific application needs, we offer a range of dedicated Acti 9 units developed for specialised applications.All units are fully tested, approved and certified by international standards. With Acti 9, you and your customers can rest assured that the installation is 100 % safe and in full compliance with regulations and industry standards.Our range of dedicated Acti 9 protection units covers:UL-certified applications for the North American marketMarine and offshore applicationsDC applicationsFuse

disconnectorsIn addition, we offer bac
disconnectorsIn addition, we offer back-up tables providing quick, at-a-glance overview of everything you need to know when building your panel. The back-up tables include data on Compact NSX circuit breakers with 100 % cascading, making it easy for you to include Acti 9 in larger installations and distribution panels.To learn more about Acti 9 for specialised applications, please contact our customer service on 4473 7880, mail to kundecenter@schneider-electric.com or visit our www.schneider-electric.dk32 & 4 pole RCBo (combine products)iDPNN/HDCPNUL circuit breakerUL489UL1077Marine circuit breakerC60N/H/L17DC circuit breakerC60H-DCC60PV-DCC60NA-DCSW60-DCD0 fuse-disconnectorDO fuse-disconnectorBack-up and cascad

ing tabelsGuideline TabelCross reference
ing tabelsGuideline TabelCross reference tabelFrom Multi 9 to Acti 9NotesNotesIndex42 & 4 pole RCBo (combine products)5Residual current devices• ThcVieipcsidsalasppclt■pmtidc■pmtcatiml circuits (against overcurrents and insulation faults):- ■pmtcatimldipcatprotection for users against electric shocks by indirect contacts (300 mA),- ■pmtcatiml�pcextreme atmospheric conditions,harmonic generating loads,transient operating currents. IEC/EN 61009Protection Earth leakage protection iDPNN VigiiDPN H VigiiDPN H Vigi TypeSI Width in 9 mm Curve B30 mA300 mA30 mA300 mACurve CVoltage rating (Ue)Operating frequencyiDPN N Vigi TypeSI Wid

th in 9 mm modulesCurve B10 mA30 mA100 m
th in 9 mm modulesCurve B10 mA30 mA100 mA300 mA30 mA100 mA300 mACurve C10 mA30 mA100 mA300 mA30 mA100 mA300 mAResidual current devices iDPN Vigi (cont.)6PB110002-40Dimensions (mm)DB124454 8536445.20557345Weight (g)Residual current deviceTypeiDPN VigiDB123314IP20IP40Technical dataTypeiDPN N VigiiDPN H VigiPollution degree Setting temperature for ratingsRated breaking capacity (Icn)Rated residual breaking and making capacity Type ACType AType Additional characteristics Earth leakage protection with instantaneous Degree of protectionenclosureOvervoltage category (IEC 60364)Operating temperature Type ACType A, Storage temperature Tropicalization

(IEC 60068-1)Treatment 2 (relative humi
(IEC 60068-1)Treatment 2 (relative humidity 95 % to 55°C) Connection DB123947Tightening 4 to 40 Agreen strip on the toggle guarantees opening possible) for work to be carried out on live partsFast contact closureInsulated terminals IP20Test buttonVisi-trip double window Fault tripping circuit breaker is indicated by a red mechanical indicator on the front face.Earth fault is indicated by a red mechanical indicator on the front faceResidual current devicesiDPN Vigi (cont.)Protection Earth leakage protection Indifferent position of installation.7Compact residual current circuitbreaker DCP Vigi Protection Earth leakage protectionThe compact residual current circuit breaker provides a complete protecti

on mdaipasits(mtcpasppcltsprotection of
on mdaipasits(mtcpasppcltsprotection of people against electric shocks by direct contacts (30 mA),protection of people against electric shocks by indirect contacts (300 mA),- ■pmtcatimldpmm�pchazapdsDisplay of earth fault on the front panel by position of toggle.International standard: IEC 61009-1 and IEC 60947-2European standard: EN 61009-1 and EN 60947-2* Information to be provided by the country. DCP N Vigi 6000 ATypeWidth in 9-mm Se■sitivity (IΔ■)30 mA30 mASe■sitivity (IΔ■)30 mA30 mAVoltage rating (Ue)Operating frequencyDCP H Vigi 10000 ATypeWidth in 9-mm Se■sitivity (IΔ■)30 mA30 mAVoltage rating (Ue)Operating frequency8Compact residual current circuitbreaker DCP Vigi (suit

e) Protection Earth leakage protection
e) Protection Earth leakage protectionDB123633Tightening torque6 to 32 ATechnical dataMain characteristicsDCP N VigiDCP H VigiRated residual operating current (IEarth leakage protection typeSetting temperature for ratingsasppcltAccording to IEC 61009-1, EN 61009-1Rated breaking capacity (Icn) Service breaking capacity (Ics)Rated residual breaking and making According to IEC 60947-2, EN 60947-2Ultimate breaking Service breaking capacity (Ics)Additional characteristics Degree of protectionenclosureOperating temperature TropicalizationTreatment 2 (relative humidity 95 % to 55°C) DB123314IP20IP40Indifferent position of installation.Weight (g) Residual current deviceTypeDCP Vigi&

#27;
#27;9CM902004E ManglerUL circuit breaker10C60 UL 489 circuit breakers(C and D curves)ProtectionCircuit protectionUL 489 / CSA C22.2 No. 5-02 IEC 60947-2 / GB 14048-2Tunnel terminal240 V 480Y / 277 V 240 V 480Y / 277 V They provide:circuit overcurrent protection■pmtcatimlwipcsshmptaipasitsmanual control and isolationremote tripping, indications by the addition of auxiliaries.Breaking capacity:25 °C / 77°FNumber of 18 mm (0.71 in.) VoltageBreaking capacity (kA rms)UL 489/CSA10102P/3P480Y/277 V 10100.5 to 351P120 V 10-240 V 5102P/3P240 V 1020415 V -10440 V -61P60 V 10(1)10(1)2P125 V Available only in C cu

rve.IEC11C60 UL 489 circuit breakers(
rve.IEC11C60 UL 489 circuit breakers(C and D curves)ProtectionCircuit protectionTunnel terminal connection120 to 240 V 480 Y / 277 V Type60 V 125 V 3P1P2P3PCurveCurve Curve Curve Curve Curve Rating (In)CDCDCDCDCDCD0.560100601176013460151--MGN61300MGN61333MGN61311MGN61344--1601016011860135601526016860184MGN61301MGN61334MGN61312MGN61345MGN61323MGN613561.5601026011960136601536016960185------2601036012060137601546017060186MGN61302MGN61335MGN61313MGN61346MGN61324MGN613573601046012160138601556017160187MGN61303MGN61336MGN61314MGN61347MGN61325MGN613584601056012260139

601566017260188MGN61304MGN61337MGN61315M
601566017260188MGN61304MGN61337MGN61315MGN61348MGN61326MGN613595601066012360140601576017360189MGN61305MGN61338MGN61316MGN61349MGN61327MGN613606601076012460141601586017460190MGN61306MGN61339MGN61317MGN61350MGN61328MGN613617601086012560142601596017560191------8601096012660143601606017660192MGN61307MGN61340MGN61318MGN61351MGN61329MGN6136210601106012760144601616017760193MGN61308MGN61341MGN61319MGN61352MGN61330MGN6136313601116012860145601626017860194------15601126012960146601636017960195MGN61309MGN61342MGN61320MGN61353MGN61331MGN6136420601136013060147601646018060196MGN61310MGN61343MGN61321MGN61354MGN61332MGN6136525601146013160148601656018160197------30601156013260149601666018260198------35601166013360150601676018360199--

----Width in 9 mm modules246246120 to 2
----Width in 9 mm modules246246120 to 240 V 480 Y / 277 V Type60 V 125 V 3P1P2P3PCurve Curve Curve Curve Curve Alternating current and direct current operation. Alternating current operation only.12C60 UL 489 circuit breakers(C and D curves)ProtectionCircuit protectionDB122831Technical dataMain characteristicsVoltage rating, 480 Y / 277 V ,60 V and 125 V Pollution degreeThermal trippingReference temperaturein alternating currentin direct currentUtilization categoryRated breaking and making capacity on a single pole Additional characteristicsDeg

ree of protection Front panelTunnel term
ree of protection Front panelTunnel terminal connectionRing terminal connectionOperating temperatureStorage temperature TropicalizationTreatment 2 (relative humidity of 95 % at 55 °C)TypeTightening (1)Tunnel terminal (#14 #4 AWG)(#14 #2 AWG)Tunnel terminal 1 or 2 wires, 1 to 1.5 mm(#18 #16 AWG)1 or 2 wires, 2.5 to 6 mm(#14 #10 AWG)Ring terminal Silelc ilsslatcd pile tcpmilal, SL mp CSA acpti�cd.PB101000A_SEPB102091A_SETunnel terminal 240 V Tunnel terminalPB100999A_SEPB102090A_SERing terminal 240 V Ring terminal 13C60 UL 489 circuit breakers(C and D curves)ProtectionCircuit protectionWeight (g/)TypeC60 ULDB112931DB112932Tunnel terminal 240 V Tunnel terminal 480Y / 277 V Ring termina

l 480Y / 277 V DB112934Ring terminal 2
l 480Y / 277 V DB112934Ring terminal 240 V 14UL1077 / CSA C22.2, IEC 60947-2 / GB 14048-2C60 UL circuit breakers are multi-standard circuit breakers which combine the following functions:circuit protection against short-circuit currentscircuit protection against overload currentstripping and fault indication by the addition of auxiliaries.25 °C/77 °FNumber of18 mmVoltageBreaking capacity (kA rms)(0.71 in.) polesUL 1077/CSA 10102P/3P/4P240 V 10201P277 V 5-415 V -32P/3P/4P415 V -10440 V -6480Y/277 V 5-0.5 to 63B and C curves1P60 V -101P65 V 10-2P125 V C60 UL 1077 circuit breakers(B, C and D curves)ProtectionCircuit protectionDB105730DB105729IECDB405227PB101029_2-3518360PB100980_2-3518376C60 UL

circuit breakerType
circuit breakerTypeRemote indication and tripping, Remote indication and tripping, Connection kit for ring terminal cat. no. 17400 (option) see CA907012 moduleAlternating current and direct current operation. Alternating current operation only.15C60 UL circuit breakerTypeRemote indication and tripping, Remote indication and tripping, Connection kit for ring terminal cat. no. 17400 (option) see CA907012 moduleC60 UL 1077 circuit breakers(B, C and D curves)ProtectionCircuit protectionUL 1077 additional protective devices, document #E90509.CSA C22.2 no. 235-04 additional protective devices, document #E179014.16

C60 UL 1077 circuit breakers(B, C and D
C60 UL 1077 circuit breakers(B, C and D curves)ProtectionCircuit protectionDB110257Kit for ring terminalsDB122831DB122932IP20Clips onto 35 mm DIN rail.Any installation position.Technical dataMain characteristicsVoltage rating, 60 V and 125 V Pollution degreeThermal trippingReference temperatureRated breaking and making capacity on a single pole Additional characteristicsDegree of protection Front panelTunnel terminal connectionRing terminal connectionOperating temperatureStorage temperature TropicalizationTreatment 2 (relative humidity 95 % at 55 °C)Weight (g/TypeUL 486A connections for copper wires,Without accessoryWith accessoryTightening DB1187890.5 to 25 A30 to 63 A(#14 #4 AWG)(#14 #2 AWG)2 set-scr

ew connectors + 2 separators for termina
ew connectors + 2 separators for terminals (upstream / downstream) cat. no. 17400.058967Nterminal cat. no. 17400 17Marine circuitbreaker18Marine C60N circuit breakers (curve C, D)Marine C60N circuit breaker TypeProtection Circuit protection C60N circuit breakers are circuit breakers which combine the following functions: circuit protection against short-circuit currents,circuit protection against overload currents,breaking and industrial disconnection as per standards IEC/EN 60947-2.The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in com

plete safety.Increased product service l
plete safety.Increased product service life thanks: overvoltage resistance,high performance limitation,Upstream or downstream connection.Suitability for isolation in accordance with the IEC/EN 60947-2 standard.IEC/EN 60947-2 Schneider Electric is committing to have all products Marine type approved by IACS(IltcplatimlalABS, BV, DNV, GL, KRS, LRS, RINA, RMRoS and meet international standards requirements that are compulsory for the worldwide merchant marine market,PB100224_SE-30Alternating current (AC) 50/60 HzUltimate breaking capacity (Icu) as per IEC/EN 60947-2 Voltage (Ue)Ph/Ph (2P, 3P, 4P)C60N 1PC60N 2PABSLRSBVRINAGLDNVKRSRMRoSDB12310219Dimensions (mm)DB122577 Weight (g)TypeTechnical data

Pollution degree Thermal trippingNominal
Pollution degree Thermal trippingNominal temperature According to ambiant temperatureAccording to current frequencyUtilization category IACS part E10Other characteristicsDegree of protection enclosureService temperature Storage temperature Upstream or downstreamDB118772Indifferent position of installation.Marine C60N circuit breakers (curve C, D) (cont.)Protection Circuit protection DB123103Tightening 14 mm20Marine C60H circuit breakers(curve C, D)Marine C60H circuit breaker TypeProtection Circuit protection Alternating current (AC) 50/60 HzUltimate breaking capacity (Icu) as per IEC/EN 60947-2 capacity (Ics)Voltage (Ue)Ph/Ph (

2P, 3P, 4P)240 V415 V440 V240 V415 VIEC
2P, 3P, 4P)240 V415 V440 V240 V415 VIEC/EN 60947-2 Schneider Electric is committing to have all products Marine type approved by IACS(IltcplatimlalABS, BV, DNV, GL, KRS, LRS, RINA, RMRoS and meet international standards requirements that are compulsory for the worldwide merchant marine market,C60H circuit breakers are circuit breakers which combine the following functions: circuit protection against short-circuit currents,circuit protection against overload currents,breaking and industrial disconnection as per standards IEC/EN 60947-2.The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety.Increased produc

t service life thanks: overvoltage resi
t service life thanks: overvoltage resistance,high performance limitation,Upstream or downstream connection.Suitability for isolation in accordance with the IEC/EN 60947-2 standard.ABSLRSBVRINAGLDNVKRSRMRoSDB12310221Dimensions (mm)DB122577 Weight (g)TypeTechnical dataPollution degree Thermal trippingNominal temperature According to current frequencyUtilization category IACS part E10Other characteristicsDegree of protection enclosureService temperature Storage temperature Upstream or downstreamDB118772Indifferent position of installation.Marine C60H circuit breakers(curve C, D) (cont.)Protection Circuit protection DB123103Tightening 1 to 25 A2 N.m1 to 25 mm21 to 25 mm232 to 40 A3.5 N.m1.5 to 35 m

m21.5 to 35 mm2ConnectionDB122945DB12294
m21.5 to 35 mm2ConnectionDB122945DB1229465.5 mm14 mmPZ222Marine C60L circuit breakers(curve C)Marine C60L circuit breaker TypeCurve CCurve CCurve CCurve CProtection Circuit protection Alternating current (AC) 50/60 HzUltimate breaking capacity (Icu) as per IEC/EN 60947-2 Voltage (Ue)Ph/Ph (2P, 3P, 4P)240 V415 V440 V240 V415 VIEC/EN 60947-2 Schneider Electric is committing to have all products Marine type approved by IACS(IltcplatimlalABS, BV, DNV, GL, KRS, LRS, RINA, RMRoS and meet international standards requirements that are compulsory for the worldwide merchant marine market,C60L circuit breakers are circuit breakers which

combine the following functions: circu
combine the following functions: circuit protection against short-circuit currents,circuit protection against overload currents,breaking and industrial disconnection as per standards IEC/EN 60947-2.The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety.Increased product service life thanks: overvoltage resistance,high performance limitation,to fast closing independent of the speed of actuation of the toggle. Suitability for isolation in accordance with the IEC/EN 60947-2 standard.ABSLRSBVRINAGLDNVKRSRMRoSDB12310223Dimensions (mm)DB122577 Weight (g)TypeTechnical dataInsulation voltage (Ui)500 V

ACPollution degree Rated impulse withsta
ACPollution degree Rated impulse withstand voltage (Uimp)Thermal trippingNominal temperature 50 °CAccording to ambiant See module 92515Magnetic tripping (Ii)8.5 In ± 20 %According to current 50/60 HzUtilization category Compliance withOther characteristicsDegree of protection Device in modular Endurance (O-F)10,000 cycles20,000 cyclesService temperature -30°C to +70°CStorage temperature -40°C to +80°CPower loss See module 92517Upstream or downstreamDB118772Indifferent position of installation.Marine C60L circuit breakers (curve C) (cont.)Protection Circuit protection DB123103Tightening 0.5 to 25 A2 N.m1 to 25 mm21 to 25 mm2ConnectionDB122945DB1229465.5 mm14 mmPZ224DC circuit breaker25DC circuit supple

mentary protectors for feeders / distrib
mentary protectors for feeders / distribution systemsC curveRated voltage (Un)Number of polesNumber of Supply from above or below, Supply from Supply fromBreaking capacityUL 1077, IEC 60947-2, EN 60947-2, GB 14048.2IEC 60947-2, EN 60947-2, GB 14048.2* At 25°C / 77°F see temperature derating module 92515.DB105730Country approval pictogramsThe C60H-DC supplementary protectors are used in direct current circuits(Industrial control and automations, transport, renewable energy...).They combine the following functions of circuit protection against short-circuit and overload currents, control and isolation.(Supplementary Protector TC 3)26DC circuit supplementary protectors for feeders / distribution systemsC60

H-DC (cont.)C curveTripping curves: C c
H-DC (cont.)C curveTripping curves: C curve - Overcurrent protection for any type of application.Positive break indication - the green strip indicates that all the poles are open and allows work to be carried out on the downstream circuit in complete safety. Increase in the service life of the product: thanks to fast closure independent of the Current limitation in the event of a fault: fast opening of the contacts prevents the loads from being destroyed in the event of a short-circuit.Main characteristicsRated service breaking capacity (Ics)75 % of the ultimate breaking capacity (Icu)3,000 cycles (where L/R=2 ms)6,000 cycles where the circuit is resistive Additional characteristics Pollution degree Utilization cat

egoryA (no delay in accordance with IEC/
egoryA (no delay in accordance with IEC/EN 60947-2 standards)Tropicalization Operating temperature Storage temperature Technical data Weight (g)TypeDB123310DB123312DB123314IP20IP40Dimensions (mm/in)DB116740DB116741Kit for ring terminalsIndifferent position of installation.Details of minimum distance between circuit-breaker and earthed metal parts for circuit-breaker intended for use without enclosure.Failure to match polarity during connection may lead to a fire hazard and/or serious injury.The connection polarity must be observed (marked on the front panel). Use only with direct cu

rrent. If two poles are used in series
rrent. If two poles are used in series for the American network, use at least a 12 inch / 30 cm cable.27DB118759DC circuit supplementary protectors for feeders / distribution systemsC60H-DC (cont.)C curveTripping 1Insulated connector2Comb busbarTerminal 50 mmRing tongue terminal screw connectionRing tongue terminal connections kitØ 5 mm, (upstream/downstream)Insulated distribution terminalSealable terminal shieldInter-pole barrierRotary handleScrew shieldPadlocking accessory12Spacer2706213Dividable mounting plate2699614Marker strip Indication15SD fault indicating switchTripping MN undervoltage releaseMX + OF shunt releaseMounting accessories The electrical auxiliaries must be installed to t

he left of the circuit breaker and wit
he left of the circuit breaker and within a width of 54 mm.If the auxiliary SD contacts are associated with the tripping auxiliaries (MN, MX, etc.), they must be installed to the left of these auxiliaries.Without accessoryWith accessoriesO-OFFO-OFFTightening 50 mm²#18 - #4 AWG#18 - #6 AWG1 AWG3 x 6 AWG3 x 8 AWG#18 - #2 AWG#18 - #4 AWG28Poles connected in series Network selectionTypeEarthed polarity + or –Earthed central pointProtected polaritiesDiagrams (and type of faults) earthDB118852DB118853Selection of supplementary protector and pole connection24 V Un 250 VTwo-poleTwo-poleUpstream connectionOnly if L+ polarity is earthedDB116735Downstream connectionDB116738DB116738250 V 500 VTwo-p

oleTwo-poleTwo-poleUpstream connectionD
oleTwo-poleTwo-poleUpstream connectionDB116735DB116735Downstream connectionDB116738DB116738Fault analysis (low earth connection resistance) Only protected polarity concerned All the poles of the protected polarity must have a breaking Only positive polarity concernedhave a breaking capacity Not relevantpermanent insulation monitor (PIM) and cleared (IEC/EN 60364)positive) is protected: all the poles of this polarity must have a breaking If two polarities are protected, to ensure isolation: all the protections breaking capacity The 2 polarities are concernedmust have a breaking capacity The 2 polarities are concernedhave a breaking capacity have a breaking capacity requirements DC circuit supplemen

tary protectors for feeders / distributi
tary protectors for feeders / distribution systemsC60H-DC (cont.)C curve29DC circuit supplementary protectors for feeders / distribution systemsC60H-DC (cont.)C curveTripping curvesC curve as in standard IEC 60947.2The operating range of the magnetic release is as follows between 7 In and 10 In.The curves show the cold thermal tripping limits when poles are charged and the electromagnetic The curves are used without any derating.0.010,111010010000.5110t (s)I / InShort circuit current limiting220 V with 1P, 440 V with 2P250 V with 1P, 500 V with 2P10000100000100000010010001001010.10.010.5 -2346101620 -2532 -4050 -6310 msDB12359010000100000100000010010001001010.10.010.5 -12346101620 -2532 -4050 -6310 msPr

ospective current (kA rms)Prospective cu
ospective current (kA rms)Prospective current (kA rms)30DC circuit supplementary protectors for feeders / distribution systemsC60H-DC (cont.)C curveTemperature derating (according to UL 1077/ CSA22.2/ UL489A/ UL489/ IEC 60947-2 standards)The maximum permissable current in a device depends on the ambient temperature in which it is placed.Ambient temperature is the temperature inside the enclosure or switchboard in which the devices have been The reference temperature is in the coloured column.When several simultaneously operating devices are mounted side by side in a small enclosure, the temperature clalmsspcpcdsatimlasppcltpcdsatimlaœd�aicltmpdcptherefore be allocated to the rating (already derated i

f it depends on the ambient temperature)
f it depends on the ambient temperature).Temperature37.3536.7436.1235.5034.8634.2133.5432.8632.1731.4630.743029.2428.4627.6626.8325.9825.1024.1923.2422.253238.4537.9137.3636.8036.2435.6635.0834.4833.8833.2732.643231.3530.6830.0029.3128.5927.8627.1126.3425.543544.1543.4042.6341.8641.0640.2539.4238.5837.7236.8335.933534.0533.0632.0531.0129.9328.8127.6426.4225.144048.9248.1747.4246.6545.8745.0844.2843.4542.6241.7640.894039.0938.1637.2036.2235.2134.1733.1031.9930.845059.9359.0958.2557.3956.5255.6354.7453.8252.8951.9550.985049.0047.9746.9345.8644.7743.6442.4941.3140.096076.1674.8373.4872.1170.7169.2867.8266.3364.8163.2561.646058.3156.5754.7752.9250.9948.9946.9044.7242.436378.1676.9175.6374.3373.0171.6770.3068.9067.4766

.0264.536361.4459.8358.1856.4954.7452.93
.0264.536361.4459.8358.1856.4954.7452.9351.0649.1247.10Curves (cont.)Thermal stress limitation curve220 V with 1P, 440 V with 2P250 V with 1P, 500 V with 2P0.11101001001010.10.01 12346101620 -2532 -4050 -63DB1235890.11101001001010.10.01 12346101620 -2532 -4050 -63Peak current (kA)Peak current (kA)Prospective current (kA rms) Prospective current (kA rms) 31DC circuit supplementary protectors for feeders / distribution systemsC60H-DC (cont.)C curveWithout accessoryO-OFFO-OFFTightening 3 Multi-cables / Different wires2 x 18 AWG - 2 x 8 AWG3 x 18 AWG2 x 13 AWG + 1 x 15 AWG2 x 18 AWG - 2 x 6 AWG3 x 6 AWG2 x 8 AWG + 1 x 9 AWG32DB122506PB108403-50PB108405-50DB404840DB122703A9N61661DC circuit s

upplementary protectors for photovoltaic
upplementary protectors for photovoltaic installationsC60PV-DCThe C60PV-DC is a DC circuit breaker dedicated to multi string photovoltaic This circuit breaker is designed to protect the cables located between each string of photovoltaic modules and the photovoltaic inverter against overloads and short circuits (see application diagram).Combined with a switch (of the C60NA-DC type, for example), the C60PV-DC will be installed in a string PV protection enclosure at the end of each string of photovoltaic It can be locked (by a padlocking device) in OFF position as a safety measure for removal of the PV inverter.asppcltpctcpscdipcatimlasppclt,C60PV-DC can detect and protect against any bidirectional current.To ensure th

e safety of the installation, it is nece
e safety of the installation, it is necessary, depending on the various types of application, to combine the C60PV-DC with:a residual current device at the AC end,an earth protection circuit breaker at the DC end (see Practical Advice CA908035).In all cases, fast action on site will be required to clear the fault (protection not ensured in the event of a double fault).C60PV-DC is not polarity sensitive: (+) and (-) wires can inversed without any risk.The C60PV-DC is: delivered with three inter-pole barrier to provide increased isolation Rated insulation voltage (Ui)Breaking capacity (Icu)Number of polesNumber of modules of 9 mm&#

29;1243INOUTStandardsIEC 60947-2EN
29;1243INOUTStandardsIEC 60947-2EN 60947-2Rating (A)Catalogue numbers1A9N616532A9N616543A9N616555A9N616568A9N6165710A9N6165013A9N6165815A9N6165916A9N6165120A9N6165225A9N61660AuxiliariesSee modules CA907008 and CA90701333DC circuit supplementary protectors for photovoltaic installationsC60PV-DC (cont.)String PV protection enclosureMN, MX, MNx, MNs, MX+OF, OF, SD, OF+SD/OFPV InverterPV InverterPV Inverter protection enclosurePV Inverter protection

enclosure20 A/1000 V DC or32 A/800 V DC
enclosure20 A/1000 V DC or32 A/800 V DC or50 A/700 V DC34DC circuit supplementary protectors for photovoltaic installationsC60PV-DC (cont.)Technical data Position contact indication - suitability for isolation according to IEC/EN 60947-2 standard.The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety.Increased product service life thanks to fast closing independent of the speed of actuation of the toggle.Pre-wired product: Input / Output on the same side.Main characteristicsRated service breaking capacity (Ics)1,500 cycles (where L/R=2 ms)Degree of pollutionCategory A (no delay in accordance with IEC / EN 6

0947-2 standards)TropicalisationRelative
0947-2 standards)TropicalisationRelative humidity: 95 % at 55°C in accordance with IEC 60068-2 and GB 14048.2 standardsTemperatureAdditional characteristicsVoltage drop (mV)Impeda■ce (mΩ)C60PV-DCAmbient temperature (°C)359 mm mini9 mm miniRequired to have a 9 mm space isolation Without accessoryWith accessoriesTightening Copper cables UL 486A �le ■o. #E216919 50 mmCu/Al Terminalscrew connectionDC circuit supplementary protectors for photovoltaic installationsC60PV-DC (cont.)DB118756DB11875514 mmDB112804Dimensions (mm)Weight (g)TypeC60PV-DCTechnical data (cont.)Moreover it is recommended to use: a terminal Screw Shield snaps onto the front of the C60PV-DC protective devices to provide g

reater insulation of the terminal screws
reater insulation of the terminal screwsa spacer clips 9 mm in each side to provide isolation.36DC main switch for photovoltaic installationsC60NA-DCThe C60NA-DC is a direct current switch-disconnector dedicated to disconnection of the string of photovoltaic modules and the PV inverter.It is designed to isolate the string of photovoltaic modules and the inverter from the rest of the photovoltaic installation for maintenance operations in complete safety.Combined with a circuit breaker (of the C60PV-DC type, for example), the C60NA-DC will be installed in a string PV protection enclosure close to the strings of photovoltaic modules. It can also be installed near the PV inverter.It can be locked (by a padlocking dev

ice) in OFF position to ensure safety du
ice) in OFF position to ensure safety during asppcltpctcpscdipcatimllmpmalasppclt,the C60NA-DC can switch a multi-directional current.C60NA-DC is not polarity sensitive: (+) and (-) wires can inversed without any risk.The C60NA-DC is delivered with three inter-pole barrier to provide increased Rated insulation voltage (Ui)Rated operational current (Ie)Permissible rated short-time withstand current (Icw)Rated short-circuit closing current (Icm)Number of polesNumber of modules of 9 mm1243INOUTStandardsIEC 60947-3Catalogue numberA9N61690AuxiliariesSee modules CA907008 and CA907013DB122704DB122506PB1084044-50DB40484137DC

main switch for photovoltaic installatio
main switch for photovoltaic installationsC60NA-DC (cont.)String PV protection enclosurePV InverterPV InverterPV Inverter protection enclosurePV Inverter protection enclosureDiagram with C60NA-DC for 20 ADiagram with SW60-DC for current between 20 and 50 A20 A/1000 V DC or32 A/800 V DC or50 A/700 V DC, MX+OF, OF, SD, OF+SD/OF, OF+SD2438DC main switch for photov

oltaic installationsC60NA-DC (cont.)Tec
oltaic installationsC60NA-DC (cont.)Technical data Position contact indication - suitability for isolation according to IEC/EN 60947-3 standard. The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety. Increased product service life thanks to fast closing independent of the speed of actuation of the toggle. Pre-wired product: Input / Output on the same side.Main characteristicsDegree of pollutionCategory TropicalisationRelative humidity: 95 % at 55°C in accordance with IEC 60068-2 and GB 14048.2 standardsTemperatureRequired to have a 9 mm space isolation DB1227149 mm mini9 mm miniMoreover it is recommended t

o use:a terminal Screw Shield snaps onto
o use:a terminal Screw Shield snaps onto the front of the C60NA-DC protective devices to provide greater insulation of the terminal screwsa Spacer clips 9 mm in each side to provide isolation.Ambient temperature (°C)39DC main switch for photovoltaic installationsC60NA-DC (cont.)Without accessoryWith accessoriesTightening Copper cables UL 486A �le ■o. #E21691950 mmTerminalScrew on 50 A3.5 N.m1 to 35 mm21 to 25 mm250 mm2Ø 5 mm3 x 16 mm23 x 10 mm2DB118756DB11875714 mmPZ26.5 mmDB112805DB118755Dimensions (mm)Weight (g)TypeTechnical data (cont.)40DB122699DB123698DB122700DB123699DC main switch for photovoltaic installationsSwitch SW60-DCcontrol in photovoltaic installation with Voc until 1000 V

DC.Associated with string protections d
DC.Associated with string protections devices (eg: C60PV-DC) and junction box switch iltcptcpiltcptcp.It can be padlocked in off position to garantee safety in case of inverter removal SW60-DC is polarity sensitive: (+) and (-) has to be respected for connection.The SW60-DC is a trip-free switch that can be remotely controlled by adding an MN or MX auxiliary:it is also compatible with the OF (open/closed) auxiliary from the C60 range,it is delivered with three inter-pole barrier to provide increased isolation distance Rated insulation voltage (Ui)Rated operational current (Ie)Number of polesNumber of modules of 9 mm1243

IN++OUTOUTINStandardsIEC 60947-3EN 60
IN++OUTOUTINStandardsIEC 60947-3EN 60947-3Catalogue numberMGN61699Additional characteristicsVoltage drop (mV)Impeda■ce (mΩ)41DC main switch for photovoltaic installationsSwitch SW60-DC (cont.)ApplicationsInverterInverter protection arresters should be the PV array, and the other arresters should be the PV array, and the other MX+OF, OF, SD, OF+SD/OF42DB123702Technical data Position contact indication - suitability for isolation according to IEC/EN 60947-3 standard.The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety.Increased product service life thanks to fast closing independent of the speed of

actuation of the toggle.Pre-wired produc
actuation of the toggle.Pre-wired product: Input / Output on the same side.Complementary technical dataDegree of pollutionCategory WeightTropicalisationRelative humidity: 95 % at 55°C / 131°F in accordance with IEC 60068-2 and GB 14048.2 standardsTemperatureTemperature*(*) the temperature level must be calculated using a heat balance of the enclosure in which the device is to be installed.Moreover it is recommended to use:a terminal Screw Shield snaps onto the front of the SW60-DC protective devices to provide greater insulation of the terminal screws.a Spacer clips 9 mm in each side to provide isolation.Dimensions (mm)DB123700DB122722DB122723DB1237019 mm mini9 mm mini Failure to match polarity during co

nnection may lead to a fire hazard and/o
nnection may lead to a fire hazard and/or serious injury.The connection polarity must be observed (marked on the front panel). Use only with direct current. used on both sides of the device to create a local ventilation space around the product.DC main switch for photovoltaic installationsSwitch SW60-DC (cont.)SW60-DC43DB123704DC main switch for photovoltaic installationsSwitch SW60-DC (cont.)TrippingWithout accessoryWith accessoriesTightening Copper cables UL 486A �le ■o. #E21691950 mmTerminalscrew on 50 A3.5 N.m1 to 35 mm21 to 25 mm250 mm2Ø 5 mm3 x 16 mm23 x 10 mm2DB112804DB118756DB11875714 mmPZ26.5 mmTerminal 50 mmRing tongue terminal screw connectionInsulated distribution terminalInter-

pole barrierScrew shieldPadlocking acc
pole barrierScrew shieldPadlocking accessoryC60 auxiliaries 8SD fault indicating switchTrippingMN undervoltage releaseMX, MX+OF shunt releaseThe electrical auxiliaries must be installed to the left of the circuit breaker and within a width of 54 mm.The SD auxiliary contact must be associated with an auxiliary (MN, MX, MX+OF); it indicates that the switch has been tripped open.44D0 fuse-disconnector45Circuit protectionTertiary sector, IndustryD0 fuse disconnectors switchesfuse D02 provide protection against overloads and short circuits.They are used for service sector and industrial applications.Depending on the versions, they should be provided with D01 or D02 type cartridges.used, from 20 A to 50 A.IEC

/EN 60947-1, IEC/EN 60947-3, IEC 60269-1
/EN 60947-1, IEC/EN 60947-3, IEC 60269-1, IEC 60269-3, VDE 0660-100, VDE 0660-107DB116619Country approval pictogramsUpstream/downstream by tunnel terminals Accessories for D02 switches disconnectors fuseTypeYellowBlown-fuse TypeD01 fuse switches disconnectors D02 switches disconnectors fuseD02 : Gaugesdpmm46Connection DB405245TypeTightening 5.5 mmD01 fu

se switches disconnectors DB405247
se switches disconnectors DB405247Circuit protectionTertiary sector, IndustryD0 fuse disconnectors switches (cont.)Technical dataMain characteristicsOperating frequency (Hz)Service breaking capacity (Isc)Utilization category (IEC 60947-3) Additional characteristicsDegree of protection Device in modular enclosure Operating temperatureStorage temperatureIndifferent position of installation.IP20IP4047Back-up table48Un: 230-240V/380-415V TT and TN earthing systemsMCCB’sTrip unitsValid combinationsTM/MicrologicTM/MicrologicTM/MicrologicRCBO

’sNumber of polesValid combinations
’sNumber of polesValid combinationsIDPNN VigiIDPNN Vigi(i)C60N/H/L VigiRCCB’sNumber of polesValid combinationsNumber of polesValid combinationsThe following components can be used:Connections between level 2 (residual current protection devices) and level 3 (miniature circuit breakers) must be installed so that the short circuit and earth fault can be ruled out. For combination C miniature circuit breaker can be and 2 do not have to be performed the same way as Selection guide for equipment with residual current protection - 10 kA49Back-up tableCombination A:MCCB’s NG125NNG125LNG160ENG160N/HNS(X) 100B/F/NNS(

X) 160B/F/NNS(X) 250B/F/NRCBO IDPNN Vig
X) 160B/F/NNS(X) 250B/F/NRCBO IDPNN VigiIDPNN VigiIDPNN VigiIDPNN Vigi(i)C60N Vigi(i)C60N Vigi(i)C60N Vigi(i)C60N Vigi(i)C60N VigiCombination B & C:Upstream MCCB Downstream MCB Valid for RCCB’s with In between 25 and100 A, Please note that the RCCB’s have to be protected against overload situation.50Un: 230-240V/380-415V TT and TN earthing systemerMCCB’sTrip unitsValid combinationsTM/MicrologicTM/MicrologicTM/MicrologicRCBO’sNumber of polesValid combinationsIDPNN VigiIDPNN Vigi(i)C60N/H/L VigiRCCB’sNumber of polesValid combinationsNumber of polesValid combinationsSelection guide for equipment with residual current protection - 16 kAConnections between level 2 (residual current protect

ion devices) and level 3 (miniature circ
ion devices) and level 3 (miniature circuit breakers) must be installed so that the short circuit and earth fault can be ruled out. For combination C miniature circuit breaker can be placed in either level 1 or 3. Is it placed in level 1, the connections between level 1 and 2 do not have to be performed the same way as between level 2 and 3.The following components can be used:51Back-up tableCombination A:MCCB’s NG125NNG125LNG160ENG160N/HNS(X) 100B/F/NNS(X) 160B/F/NNS(X) 250B/F/NRCBO IDPNN VigiIDPNN VigiIDPNN VigiIDPNN Vigi(i)C60N Vigi(i)C60H Vigi(i)C60L Vigi(i)C60L Vigi(i)C60L VigiCombination B & C:Upstream MCCB D

ownstream MCB Valid for RCCB’s wit
ownstream MCB Valid for RCCB’s with In between 25 and100 A, Please note that the RCCB’s have to be protected against overload situation.52Un: 230-240V/380-415V TT and TN earthing systemerMCCB’sTrip unitsValid combinationsTM/MicrologicTM/MicrologicTM/MicrologicRCBO’sNumber of polesValid combinationsIDPNN VigiIDPNN VigiIDPNN VigiIDPNN Vigi(i)C60N/H/L VigiRCCB’sNumber of polesValid combinationsNumber of polesValid combinationsSelection guide for equipment with residual current protection - 20 kAConnections between level 2 (residual current protection devices) and level 3 (miniature circuit breakers) must be installed so that the short circuit and earth fault can be ruled out. For combinatio

n C miniature circuit breaker can be pla
n C miniature circuit breaker can be placed in either level 1 or 3.Is it placed in level 1, the connections between level 1 and 2 do not have to be performed the same way as between level 2 and 3.The following components can be used:53Back-up tableCombination A:MCCB’s NG125NNG125LNG160ENG160N/HNS(X) 100B/F/NNS(X) 160B/F/NNS(X) 250B/F/NRCBO IDPNN VigiIDPNN VigiIDPNN VigiIDPNN Vigi(i)C60N Vigi(i)C60H Vigi(i)C60L Vigi(i)C60L Vigi(i)C60L VigiCombination B & C:Upstream MCCB Downstream MCB Valid for RCCB’s with In between 25 and100 A, Please note that the RCCB’s have to be protected against overload situation

.54Un: 230-240V/380-415V TT and TN ear
.54Un: 230-240V/380-415V TT and TN earthing systemerTrip unitsTrip unitsValid combinationsTM/MicrologicTM/MicrologicTM/MicrologicRCBO’sNumber of polesValid combinationsIDPNN VigiIDPNN Vigi(i)C60N Vigi(i)C60H/L VigiRCCB’sNumber of polesValid combinationsNumber of polesValid combinationsSelection guide for equipment with residual current protection - 25 kAConnections between level 2 (residual current protection devices) and level 3 (miniature circuit breakers) must be installed so that the short circuit and earth fault can be ruled out. For combination C miniature circuit breaker can be placed in either level 1 or 3. Is it placed in level 1, the connections between level 1 and 2 do not have to be performed

the same way as between level 2 and 3.*
the same way as between level 2 and 3.** Not for NSX100/160/250B and NG160N.The following components can be used:55Back-up tableCombination A:MCCB’s NG125NNG125LNG160ENG160N/HNS(X) 100B/F/NNS(X) 160B/F/NNS(X) 250B/F/NRCBO IDPNN VigiIDPNN VigiIDPNN Vigi(i)C60N Vigi(i)C60H Vigi(i)C60L Vigi(i)C60L Vigi(i)C60L VigiCombination B & C:Upstream MCCB Downstream MCB Valid for RCCB’s with In between 25 and100 A, Please note that the RCCB’s have to be protected against overload situation.56 Cross reference tabel57Cross reference tabelFrom Multi 9 to Acti 9Cross reference tabelType referenceG-numberEAN13-numb

erType referenceTextG-numberEAN13-number
erType referenceTextG-numberEAN13-number1500633191500623303430150060A9S60220Switch iSW 2P 20A 415V33187006623606480088681Auxiliaries iSW changeover 250/415VACImpuls relay iTL 16A 4NO 230VAC/110VDCImpuls relay iTL 16A 4NO 24VAC/12VDCContactor iCT 25A 2NO 220VACContactor iCT 16A 1NO+1NC 230VACInterfacerelay iRBN 230/5mA 5V Auxiliaries iATLc 24-240VACAuxiliaries iATLs 24-240VACAuxiliaries iATLc+s 24-240VACAuxiliaries iATLs+s 24-240VACAuxiliaries iATL4 230VACAuxiliaries iATLs med lys 130-240VACAuxiliaries iATLs 12-240VAC 6-110VDCInterfacerelay iRTBT 12-24/5mA 5VTimemodul iATET 1s-10h 24-240VACImpuls relay iTL 16A 1NO 230VAC/110VDC Impuls relay iTL 16A 2NO 230VAC/110VDCImpuls relay iTLI 16A 1NO+1NC 230/240VACImpuls relay

iTLI 16A 1NO+1NC 48VAC/24VDCImpuls rela
iTLI 16A 1NO+1NC 48VAC/24VDCImpuls relay iTLI 16A 1NO+1NC 24VAC/12VDCImpuls relay iETL 32A 1NO 230/240VAC Impuls relay iTL 16A 1NO 230VAC/110VDC Impuls relay iTL 16A 1NO 130VAC/48VDC58Cross reference tabelFrom Multi 9 to Acti 9Cross reference tabelType referenceG-numberEAN13-numberType referenceTextG-numberEAN13-numberContactor iCT 40A 4NC 230VACContactor iCT 63A 2NO 230VACContactor iCT 63A 3NO 230VACContactor iCT 63A 4NO 230VACContactor iCT 63A 4NC 230VACContactor iCT 63A 2NO+2NC 230VACContactor iCT 100A 2NO 230VACContactor iCT 100A 4NO 230VACContactor iCT 25A 2NO 230VAC on/offContactor iCT 25A 3NO 230VAC on/offContactor iCT 25A 4NO 230VAC on/offContactor iCT 40A 2NO 230VAC on/offContactor iCT 40A 4NO 230VAC on

/offContactor iCT 63A 2NC 230VAC on/offC
/offContactor iCT 63A 2NC 230VAC on/offContactor iCT 63A 4NO 230VAC on/offContactor iCT 25A 2NO 24VACContactor iCT 25A 4NO 24VACContactor iCT 25A 4NC 24VACContactor iCT 63A 2NO 24VACContactor iCT 63A 4NO 24VACContactor iCT 63A 4NC 24VACContactor iCT 16A 1NO+1NC 24VACContactor iCT 25A 2NO 240VAC/60HzContactor iCT 25A 3NO 240VAC/60HzPushbotton iPB 20A 1NC Grey 250VACPushbotton iPB 20A 1NC Red 250VACPushbotton iPB 20A 1NO Grey 250VACPushbotton iPB 20A 1NO+1NC Grey 250VACPushbotton iPB 20A 2P 1NO+1NC Grey 250VACPushbotton iPB 20A 2P 2NO Grey 250VACPushbotton iPB 20A 1NC LED 250VACPushbotton iPB 20A 1NO LED 250VAC12/48VACDC12/48VACDCAuxiliaries iACTc 230VACAuxiliaries iACTc 24-48VACAuxiliaries RCA iC60 1P/2P 230VAC Auxil

iaries RCA iC60 3P/4P 230VACIndicator li
iaries RCA iC60 3P/4P 230VACIndicator light iIL Red LED 110-230VACIndicator light iIL Green LED 110-230VACIndicator light iIL White LED 110-230VACIndicator light iIL Blue LED 110-230VAC59Cross reference tabelFrom Multi 9 to Acti 9Cross reference tabelType referenceG-numberEAN13-numberType referenceTextG-numberEAN13-numberIndicator light iIL Yellow LED 110-230VACIndicator light iIL Red+Green LED 110-230VAC110-230VACIndicator light iIL Red LED 12-48VACDCIndicator light iIL Green LED12-48VACDCIndicator light iIL White LED 12-48VACDCIndicator light iIL Blue LED 12-48VACDCIndicator light iIL Yellow LED 12-48VACDCIndicator light iIL Red+Green LED 12-48VACDCCircuit breaker iDPNN 1PN 1A C Circuit breaker iDPNN 1PN 2A

C Circuit breaker iDPNN 1PN 3A C C
C Circuit breaker iDPNN 1PN 3A C Circuit breaker iDPNN 1PN 6A CCircuit breaker iDPNN 1PN 10A C Circuit breaker iDPNN 1PN 16A C Circuit breaker iDPNN 1PN 20A C Circuit breaker iDPNN 1PN 25A C Circuit breaker iDPNN 1PN 32A C Circuit breaker iDPNN 1PN 40A C 60Cross reference tabelFrom Multi 9 to Acti 9Cross reference tabelType referenceG-numberEAN13-numberType referenceTextG-numberEAN13-numberCircuit breaker iDPNN 3PN 6A CCircuit breaker iDPNN 3PN 10A C Circuit breaker iDPNN 3PN 16A C Circuit breaker iDPNN 3PN 20A C Circuit breaker iDPNN 3PN 25A C Circuit breaker iDPNN 3PN 32A C Circuit breaker iDPNN 3PN 40A C Circuit breaker iDPNN 1PN 13A C Circuit breaker iDPNN 3P 13A C Circuit breaker iDPNN 3P

N 13A C 61Cross reference tabelFrom M
N 13A C 61Cross reference tabelFrom Multi 9 to Acti 9Cross reference tabelType referenceG-numberEAN13-numberType referenceTextG-numberEAN13-numberCircuit breaker iC60N 1PN 1A C Circuit breaker iC60N 1PN 2A C Circuit breaker iC60N 1PN 3A C Circuit breaker iC60N 1PN 4A C Circuit breaker iC60N 1PN 6A C Circuit breaker iC60N 1PN 10A C Circuit breaker iC60N 1PN 13A C Circuit breaker iC60N 1PN 16A C Circuit breaker iC60N 1PN 20A C Circuit breaker iC60N 1PN 25A C Circuit breaker iC60N 1PN 32A C Circuit breaker iC60N 1PN 40A C Circuit breaker iC60N 1PN 50A C Circuit breaker iC60N 1PN 63A C Circuit breaker iC60N 3PN 0,5A CCircuit breaker iC60N 3PN 1A C Circuit breaker iC60N 3PN 2A C Circuit breaker iC60N 3PN 3A C Circuit

breaker iC60N 3PN 4A C Circuit breaker
breaker iC60N 3PN 4A C Circuit breaker iC60N 3PN 10A C Circuit breaker iC60N 3PN 13A C Circuit breaker iC60N 3PN 16A C Circuit breaker iC60N 3PN 20A C Circuit breaker iC60N 3PN 25A C Circuit breaker iC60N 3PN 32A C Circuit breaker iC60N 3PN 40A C Circuit breaker iC60N 3PN 50A C 62Cross reference tabelFrom Multi 9 to Acti 9Cross reference tabelType referenceG-numberEAN13-numberType referenceTextG-numberEAN13-numberCircuit breaker iC60N 3PN 63A C Shunttrip iMX 12-24VAC 12-24VDCRCD Vigi iC60 2P 63A 300mA-s class A RCD Vigi iC60 2P 25A 30mA class ARCD Vigi iC60 2P 25A 30mA class ARCD Vigi iC60 2P 25A 300mA class A RCD Vigi iC60 2P 25A 30mA class ARCD Vigi iC60 2P 25A 100mA class A RCD Vigi iC60 2P 25A 300mA c

lass A RCD Vigi iC60 2P 63A 300mA class
lass A RCD Vigi iC60 2P 63A 300mA class A RCD Vigi iC60 3P 25A 30mA class A RCD Vigi iC60 2P 25A 300mA class A RCD Vigi iC60 4P 25A 30mA class A RCD Vigi iC60 4P 25A 100mA class A RCD Vigi iC60 2P 63A 30mA class Asi RCD Vigi iC60 4P 25A 30mA class AsiRCD Vigi iC60 4P 63A 30mA class AsiRCD Vigi iC60 2P 63A 300mA-s class AsiRCD Vigi iC60 4P 63A 300mA-s class AsiRCD Vigi iC60 2P 63A 30mA class A RCD Vigi iC60 2P 63A 300mA class A RCD Vigi iC60 2P 63A 300mA-s class AsiRCD Vigi iC60 3P 63A 30mA class A RCD Vigi iC60 3P 25A 30mA class AsiRCD Vigi iC60 3P 63A 300mA-s class A RCD Vigi iC60 2P 25A 30mA class Asi RCD Vigi iC60 3P 25A 30mA class AsiRCD Vigi iC60 4P 25A 30mA class AsiRCD Vigi iC60 3P 63A 30m

A class AsiRCD Vigi iC60 2P 25A 500mA c
A class AsiRCD Vigi iC60 2P 25A 500mA class A RCD Vigi iC60 3P 25A 30mA class AsiRCD Vigi iC60 3P 25A 300mA class A RCD Vigi iC60 4P 25A 30mA class AsiRCD Vigi iC60 2P 63A 30mA class Asi RCD Vigi iC60 2P 63A 300mA-s class A RCD Vigi iC60 3P 63A 30mA class AsiRCD Vigi iC60 3P 63A 30mA class A RCD Vigi iC60 3P 63A 500mA class A Auxiliaries OF.S 1CO for iIDAuxiliaries iOF 230-415VAC 24-130VDCAuxiliaries iSD 230-415VAC 24-130VDCAuxiliaries iOF/SD+OF 230-415VAC 24-63Cross reference tabelFrom Multi 9 to Acti 9Cross reference tabelType referenceG-numberEAN13-numberType referenceTextG-numberEAN13-numberShunttrip iMX 100-415VAC 110-130VDCShunttrip iMX/OF 48VAC 48VDCShunttrip iMX/OF 12-24VAC 12-24VDCShunttrip iMN

115VACShunttrip iMN 230VACShunttrip iMNs
115VACShunttrip iMN 230VACShunttrip iMNs 48VACShunttrip iMNs 230VACTerninal/cable shild 1P/2 pcsTerninal/cable shild 2P/2 pcsTerninal/cable shild 2P/2 pcsTerminal shild 4P/20 pcsTerminal shild Vigi 4P/20 pcsTerminal barrier/10 pcsCircuit breaker iK60N 2P 1A C monoCircuit breaker iK60N 2P 2A C monoCircuit breaker iK60N 2P 3A C monoCircuit breaker iK60N 2P 4A C monoCircuit breaker iK60N 2P 6A C monoCircuit breaker iK60N 2P 10A C monoCircuit breaker iK60N 2P 13A C monoCircuit breaker iK60N 2P 16A C monoCircuit breaker iK60N 2P 20A C monoCircuit breaker iK60N 2P 25A C monoCircuit breaker iK60N 2P 32A C monoCircuit breaker iK60N 2P 40A C monoCircuit breaker iK60N 2P 50A C monoCircuit breaker iK60N 2P 63A C mono64Cros

s reference tabelFrom Multi 9 to Acti 9
s reference tabelFrom Multi 9 to Acti 9Cross reference tabelType referenceG-numberEAN13-numberType referenceTextG-numberEAN13-numberCircuit breaker iK60N 4P 6A C monoCircuit breaker iK60N 4P 10A C monoCircuit breaker iK60N 4P 13A C monoCircuit breaker iK60N 4P 16A C monoCircuit breaker iK60N 4P 20A C monoCircuit breaker iK60N 4P 25A C monoCircuit breaker iK60N 4P 32A C monoCircuit breaker iK60N 4P 40A C monoCircuit breaker iK60N 4P 50A C monoCircuit breaker iK60N 4P 63A C monoContactor iCT 40A 4NO 230VACAuxiliaries iACTc 230VAC65Notes66Notes67NotesSchneider Electric Danmark A/Swww.schneider-electric.dkwww.lk.dkSE1042DK_v1 @ Schneider Electric Danmark A/S - All rights reservedstaldapds,dpmmaml�p