Download The PPT/PDF document "E. Da Riva/M. Gomez Marzoa" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.
Slide1
E. Da Riva/M. Gomez Marzoa
1
WG4 Meeting - 6th March 2013
ITS Ultra-Low-Mass Cooling System
Enrico DA RIVAManuel GOMEZ MARZOAWG4 Meeting - 6th March 2013
Pipe constructive considerations
Plate/squeezed pipe: water test results
Slide2Updates on piping
Received sample tubes from MicroLumen (~1mm ID)
WG4 Meeting - 6th March 20132
E. Da Riva/M. Gomez Marzoa
Single tubes
No.
Substrate
Outside
Reinforcement
Comments
1
Polyimide
Polyimide
SS Coil (100 WPI)Kinks easily2PolyimidePolyimideSS Braid (100 PIC)Suitable for bending, but quite rigid3Polyimide55D Blue Pebax®SS Braid (75 PIC)Very small bending radius4PolyimidePolyimideNoShaped
Sample tube no. 3, bent: kinking begins.
Slide3Updates on piping
Received sample tubes from MicroLumen (~1mm ID)
WG4 Meeting - 6th March 20133
E. Da Riva/M. Gomez Marzoa
Assemblies: for brainstorming
No.
Substrate
Outside
Reinforcement
Comments
5
Polyimide
55D Natural
Pebax®Coil-reinforced PTFE/Pebax (70 WPI)Transition made with Pebax® at OD (reflowed with straight tubes)6PolyimidePolyimideSame transition as 5Includes shaped polyimide sector.Sample tube no. 6.Straight PI tubeShaped PI tubeReinforced transition
Slide4Updates on piping
Main issue: pipe section affected when bending it?Test: water flow and pressure drop check.
In a straight sample.Same sample bent.
Straighten sample again.Sample no. 3: best candidate.Problem: connections
WG4 Meeting - 6th March 20134E. Da Riva/M. Gomez Marzoa
Compare 1 vs. 3
Cross-check with empirical correlations
No.
Substrate
Outside
Reinforcement
Comments
3
Polyimide55D Blue Pebax®SS Braid (75 PIC)Very small bending radius
Slide5Pipe diameter considerations
WG4 6th February 2013: minimum ID estimation.BUT only considered prototype (
Lpipe=0.58m=2x0.29m).Piping coming from outside detector area:
L>3mPractical solutions:Connection out with bigger pipe: AVOIDTransition to bigger pipe: Leak-tight?
Possible only at pipe extremityConnecting small/big tube: adhesive.Continuous tube, same ID as stave: PossiblePressure drop to be checked.WG4 Meeting - 6th March 20135E. Da Riva/M. Gomez Marzoa
Slide6ITS assembly constraints
WG4 Meeting - 6th March 2013
6E. Da Riva/M. Gomez Marzoa
800mm
200mm
2100 mm
Piping coming from
outside
sensitive area: L > 3m
IN
OUT
ITS Inner Barrel
Slide7Continuous piping: water
WG4 Meeting - 6th March 2013
7E. Da Riva/M. Gomez Marzoa
v [m s-1]
Lpipe [m]
OD/ID [mm]
Δ
p [bar]
(x/X
0
)
Stave
%
% water-pipe of (x/X0)Stave0.581.00/0.931.680.16418.30.581.51/1.450.690.21931.10.582.00/1.930.390.29040.70.582.50/2.430.250.38448.0Pressure drop analysis:LPipe=2*LOut_ITS+2*Lstave = 2*3.5+2*0.29=7.58m~8m
Slide8Accessible area
Continuous piping: C
4F10Cooling system can be divided into three sections:
WG4 Meeting - 6th March 20138
E. Da Riva/M. Gomez Marzoa
Stave
In-detector area
L
1
=3.5m
L
2
=0.6m
L3=3.5mp [bar]h [kJ kg-1]ABDQstave [W]x = constT = constC123
A
B
C
D
The small diameter pipe could be used as capillary.
Work with bigger pipe?
Slide9C4F10
vs. R236faWG4 Meeting - 6th March 2013
9
E. Da Riva/M. Gomez Marzoafluid
C4F10
r236fa
T
15.000
15.000
°C
p
1.920
1.922
barρL1533.6161392.752kg m-3ρG20.85513.136kg m-3cpL1062.5811240.483J kg-1 K-1cpG825.533854.634J kg-1 K-1kL0.046
0.077
W m-1 K-1
kG
0.013
0.012
W m-1 K-1
PrL
5.702
5.247
-
PrG
0.764
0.750
-
hL
17892.024
218378.764
J kg-1
hG
108931.647
369985.205
J kg-1
Slide10Experimental facility
WG4 Meeting - 6th March 2013
10E. Da Riva/M. Gomez Marzoa
Tested prototype with squeezed pipes in water
Slide11Pressure drop analysis
WG4 Meeting - 6th March 2013
11E. Da Riva/M. Gomez Marzoa
Laminar flow rate:
pressure drop linear with water flow rate.Leak-less: pipe section expected not to have changed.
Slide12Thermographic pictures
WG4 Meeting - 6th March 2013
12E. Da Riva/M. Gomez Marzoa
Water, 0.3 W cm
-2Q [L h
-1]
Δ
p
St
[bar]
T
H20
[
°C]ΔTH20 [K]3.00.1421.91.606.00.2722.50.739.00.54314.00.71Data post-processing: still to be finishedInclude the information of the NTCs.Quantify the heat pickup from the environment.