1 WG4 Meeting 6th March 2013 ITS UltraLowMass Cooling System Enrico DA RIVA Manuel GOMEZ MARZOA WG4 Meeting 6 th March 2013 Pipe constructive considerations Platesqueezed pipe water test results ID: 816653

gomez 6th march meeting 6th gomez meeting march wg4 riva pipe marzoa 2013 sample water piping drop tube polyimide

Share:

Link:

Embed:

Download Presentation from below link

Download The PPT/PDF document "E. Da Riva/M. Gomez Marzoa" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

Slide1

E. Da Riva/M. Gomez Marzoa

1

WG4 Meeting - 6th March 2013

ITS Ultra-Low-Mass Cooling System

Enrico DA RIVAManuel GOMEZ MARZOAWG4 Meeting - 6th March 2013

Pipe constructive considerations

Plate/squeezed pipe: water test results

Slide2

Updates on piping

Received sample tubes from MicroLumen (~1mm ID)

WG4 Meeting - 6th March 20132

E. Da Riva/M. Gomez Marzoa

Single tubes

No.

Substrate

Outside

Reinforcement

Comments

1

Polyimide

Polyimide

SS Coil (100 WPI)Kinks easily2PolyimidePolyimideSS Braid (100 PIC)Suitable for bending, but quite rigid3Polyimide55D Blue Pebax®SS Braid (75 PIC)Very small bending radius4PolyimidePolyimideNoShaped

Sample tube no. 3, bent: kinking begins.

Slide3

Updates on piping

Received sample tubes from MicroLumen (~1mm ID)

WG4 Meeting - 6th March 20133

E. Da Riva/M. Gomez Marzoa

Assemblies: for brainstorming

No.

Substrate

Outside

Reinforcement

Comments

5

Polyimide

55D Natural

Pebax®Coil-reinforced PTFE/Pebax (70 WPI)Transition made with Pebax® at OD (reflowed with straight tubes)6PolyimidePolyimideSame transition as 5Includes shaped polyimide sector.Sample tube no. 6.Straight PI tubeShaped PI tubeReinforced transition

Slide4

Updates on piping

Main issue: pipe section affected when bending it?Test: water flow and pressure drop check.

In a straight sample.Same sample bent.

Straighten sample again.Sample no. 3: best candidate.Problem: connections

WG4 Meeting - 6th March 20134E. Da Riva/M. Gomez Marzoa

Compare 1 vs. 3

Cross-check with empirical correlations

No.

Substrate

Outside

Reinforcement

Comments

3

Polyimide55D Blue Pebax®SS Braid (75 PIC)Very small bending radius

Slide5

Pipe diameter considerations

WG4 6th February 2013: minimum ID estimation.BUT only considered prototype (

Lpipe=0.58m=2x0.29m).Piping coming from outside detector area:

L>3mPractical solutions:Connection out with bigger pipe: AVOIDTransition to bigger pipe: Leak-tight?

Possible only at pipe extremityConnecting small/big tube: adhesive.Continuous tube, same ID as stave: PossiblePressure drop to be checked.WG4 Meeting - 6th March 20135E. Da Riva/M. Gomez Marzoa

Slide6

ITS assembly constraints

WG4 Meeting - 6th March 2013

6E. Da Riva/M. Gomez Marzoa

800mm

200mm

2100 mm

Piping coming from

outside

sensitive area: L > 3m

IN

OUT

ITS Inner Barrel

Slide7

Continuous piping: water

WG4 Meeting - 6th March 2013

7E. Da Riva/M. Gomez Marzoa

v [m s-1]

Lpipe [m]

OD/ID [mm]

Δ

p [bar]

(x/X

0

)

Stave

%

% water-pipe of (x/X0)Stave0.581.00/0.931.680.16418.30.581.51/1.450.690.21931.10.582.00/1.930.390.29040.70.582.50/2.430.250.38448.0Pressure drop analysis:LPipe=2*LOut_ITS+2*Lstave = 2*3.5+2*0.29=7.58m~8m

Slide8

Accessible area

Continuous piping: C

4F10Cooling system can be divided into three sections:

WG4 Meeting - 6th March 20138

E. Da Riva/M. Gomez Marzoa

Stave

In-detector area

L

1

=3.5m

L

2

=0.6m

L3=3.5mp [bar]h [kJ kg-1]ABDQstave [W]x = constT = constC123

A

B

C

D

The small diameter pipe could be used as capillary.

Work with bigger pipe?

Slide9

C4F10

vs. R236faWG4 Meeting - 6th March 2013

9

E. Da Riva/M. Gomez Marzoafluid

C4F10

r236fa

T

15.000

15.000

°C

p

1.920

1.922

barρL1533.6161392.752kg m-3ρG20.85513.136kg m-3cpL1062.5811240.483J kg-1 K-1cpG825.533854.634J kg-1 K-1kL0.046

0.077

W m-1 K-1

kG

0.013

0.012

W m-1 K-1

PrL

5.702

5.247

-

PrG

0.764

0.750

-

hL

17892.024

218378.764

J kg-1

hG

108931.647

369985.205

J kg-1

Slide10

Experimental facility

WG4 Meeting - 6th March 2013

10E. Da Riva/M. Gomez Marzoa

Tested prototype with squeezed pipes in water

Slide11

Pressure drop analysis

WG4 Meeting - 6th March 2013

11E. Da Riva/M. Gomez Marzoa

Laminar flow rate:

pressure drop linear with water flow rate.Leak-less: pipe section expected not to have changed.

Slide12

Thermographic pictures

WG4 Meeting - 6th March 2013

12E. Da Riva/M. Gomez Marzoa

Water, 0.3 W cm

-2Q [L h

-1]

Δ

p

St

[bar]

T

H20

[

°C]ΔTH20 [K]3.00.1421.91.606.00.2722.50.739.00.54314.00.71Data post-processing: still to be finishedInclude the information of the NTCs.Quantify the heat pickup from the environment.

Slide13

E. Da Riva/M. Gomez Marzoa

13

WG4 Meeting - 6th March 2013

ITS Ultra-Low-Mass Cooling System

Enrico DA RIVAManuel GOMEZ MARZOAWG4 Meeting - 6th March 2013

Pipe constructive considerations

Plate/squeezed pipe: water test results