Challenges building resources near series capacitors Jonathan Rose ERCOT Planning Engineer RPG 11142017 Purpose of Presentation Recently Renewable Resources are connecting closer to series capacitors even tapping seriescompensated lines themselves ID: 767907

energy series compensated voltage series energy voltage compensated challenges engineering ssr capacitors tapping extra require resources accumulation

Share:

Link:

Embed:

Download Presentation from below link

Download Presentation The PPT/PDF document "Challenges building resources near serie..." is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

Challenges building resources near series capacitorsJonathan RoseERCOT Planning EngineerRPG, 11/14/2017

Purpose of PresentationRecently,Renewable Resources are connecting closer to series capacitors, even tapping series-compensated lines themselvesCausing complex engineering challengesMay require extra time and extra capital to resolve

Tapping a Series Compensated Line Compensation level seen by IRR can be >100% Potential Challenges:More SSR riskVRT / tripping issues“Energy accumulation”Voltage ProfileVoltage Control3

SSR RiskHigher percent compensation seen by generator:Appears more difficult for renewable manufacturers to damp SSRSSR studies take longer4

“Energy Accumulation” and VRT Tripping Issues Energy accumulates in capacitor during faultFault clears, and energy discharges into IRRMay reverse power flow leading to generator trippingERCOT expects generators to ride through (LVRT)May require hardware changes to fixCustom engineering. No “off-the-shelf” fix. 5 Bypassing? The CREZ series capacitors may not automatically bypass depending on fault conditions. Thus energy accumulation is a real possibility.

Voltage Profile on Series-Compensated Line6 AEP Presentation to RPG, 11/11/2011 (Sample, for illustration) Voltage varies widely with flow Most CREZ lines are insulated for normal operation up to 110% voltage Possible to have voltages >105% during contingency and heavy flows Voltage control more challenging (effective impedance varies)

SummaryUnique challenges locating close to series capacitors, especially tapping a series-compensated lineMay complicate studiesMay require custom engineering solutionsTakeaway:GINR-FIS process may need more scrutinyHighly recommended perform SSR study wel l in advance (e.g. 1 year)Expect challenges / difficultiesTemporary taps create extra layer of complexity 7