 1 RGK600 – RGK700 – RGK800  1 RGK600 – RGK700 – RGK800

1 RGK600 – RGK700 – RGK800 - PowerPoint Presentation

alida-meadow
alida-meadow . @alida-meadow
Follow
355 views
Uploaded On 2020-04-06

1 RGK600 – RGK700 – RGK800 - PPT Presentation

RGK900 GENSET CONTROLLERS M60GB050214 GENSET CONTROLLERS SMALL RGK400SA RGK420SA STAND ALONE AND AMF CONTROLLERS COMPACT RGK600 RGK610 RGK600SA RGK601 RGK601SA STANDARD RGK700 RGK700SA ID: 776172

gen set controllers m60gb05 gen set controllers m60gb05 inputs usb rgk900 rs485 alarms digital rs232 port outputs remote voltage

Share:

Link:

Embed:

Download Presentation from below link

Download Presentation The PPT/PDF document " 1 RGK600 – RGK700 – RGK800" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

Slide1

1

RGK600 – RGK700 – RGK800

RGK900

GEN-SET CONTROLLERS

M60GB05_02_14

GEN-SET CONTROLLERS

Slide2

SMALLRGK400SARGK420SASTAND ALONE AND AMF CONTROLLERSCOMPACTRGK600 – RGK610 – RGK600SARGK601 – RGK601SASTANDARDRGK700 – RGK700SAEXPANDABLERGK800 – RGK800 SASYNCRONYSINGAND LOAD SHARING CONTROLLERSRGK900RGK900SARGK900MCACCESSORIES

GEN-SET CONTROLLERS

2

M60GB05_02_14

Slide3

3

RGK4…SA

Stand alone applicationWithout starting keyRGK400SAWith starting key (OFF, local start, remote start)RGK420SA

GEN-SET CONTROLLERS

M60GB05_02_14

RGK400SA

RGK420SA

Slide4

4

RGK6…

AMFSTAND ALONEPICK-UP/WNo CANbusRGK600RGK600SACANBUSNo Pick-up/WRGK601RGK601SAPICK-UP/WNo CANbusExpandableRGK610RGK610 programmed as stand alone

GEN-SET CONTROLLERS

M60GB05_02_14

Slide5

5

AMFSTAND ALONENOT EXPANDABLERGK700RGK700SAEXPANDABLERGK800RGK800SA

GEN-SET CONTROLLERS

RGK700 – RGK800

RGK700

RGK700SA

RGK800

RGK800SA

M60GB05_02_14

Slide6

GEN-SET CONTROLLERS

6

RGK900 types

RGK900RGK900SARGK900MCSingle genset in parallel to mains ●--Multiple genset paralleling in island◦●-Multiple genset bus in parallel with mains(ATS with closed transition)--●

Default applicationApplicable with specific parameter programmingNot applicable.

M60GB05_02_14

Slide7

7

RGK900

GEN-SET

CONTROLLERS

RGK900

Single gen-set in parallel to mains

P

ower

bus

M60GB05_02_14

Slide8

8

RGK900SA

GEN-SET CONTROLLERS

RGK900SA

RGK900SA

RGK900SA

Multiple gen-set in parallel in island mode

Power bus

CANbus

M60GB05_02_14

Slide9

9

RGK900 or RGK900SA + RGK900MC

GEN-SET CONTROLLERS

RGK900

RGK900SA

RGK900

RGK900SA

RGK900

RGK900SA

RGK900MC

Multiple generators in parallel with mains

P

ower bus

CANbus

M60GB05_02_14

Slide10

10

Auxiliary power supplyRated voltage: 12/24VDC (max consumption 1.1W)Continuous operating range: 7…33VDC for RGK4...SA/RGK6.../RGK700.../RGK800...7…36VDC for RGK900...Minimum value during cranking: 5.5VDC (4.5VDC for RGK4...SA).Voltage inputs4 inputs (L1, L2, L3, N) for mains (only for AMF versions)4 inputs (L1, L2, L3, N) for generatorRated voltage: RGK4...SA-RGK6...: 480VAC (L-L)RGK700...-RGK800...-RGK900...: 600VAC (L-L).Voltage range:RGK4...SA-RGK6...: 50…576VAC (L-L)RGK700...-RGK800...-RGK900...: 50…720VAC (L-L).

GEN-SET CONTROLLERS

M60GB05_02_14

Slide11

11

Current inputs1 input for RGK4...SA3 inputs for RGK6... - RGK700...4 inputs for RGK800... (earth leakage monitoring)5 inputs for RGK900... (earth leakage monitoring and load current)CT secondary rated current: 5A or 1A (programmable)Current range: 10mA…6A (CT/5A); 10mA…1.2A (CT/1A).

Built-in connections3 Resistive analog inputs (1 for RGK4...SA)Engine speed inputs: Hz, pick-up/W (not RGK601...)CANbus J1939 (not RGK4...SA and RGK600...)2° CANbus channel for controllers interlink (RGK900... only)Remote alarms/status signal outputRS232 (RGK700... only)RS485 (RGK800... - RGK900... only).

GEN-SET CONTROLLERS

M60GB05_02_14

Slide12

12

DIFFERENCES BETWEEN RGK4…SA AND RGK6…

RGK4…SARGK600…Digital inputs5 negative + 1 emergency4 negative + 1 emergencyDigital outputs5 static6 staticAnalog inputs1 resistive/digital3 resistive/digitalExpandability1 slot for EXP1040(2 resistive/digital inputs, 2 static outs)RGK610: 1 slot forEXP1010 (USB)EXP1011 (RS232)EXP1012 (RS485)Front panel dimensions110x110mm144x144mmON/OFF commandRGK400SA: push buttonRGK420SA: 3 position keyRGK600SA: push buttonLCD ScreenWith iconsGraphic LCD 128x80 pixels

GEN-SET CONTROLLERS

M60GB05_02_14

Slide13

13

DIFFERENCES BETWEEN RGK600… AND RGK700…

RGK600…RGK700…Digital inputs4 negative + 1 emergency6 negative + 1 emergencyDigital outputs6 static4 static + 3 relayAnalog inputs3 resistive/digital3 resistiveBuilt-in serial port-RS232Front panel dimensions144x144mm240x180mmDegree of protectionIP54IP65 with optional gasketIP65ON/OFF push buttonRGK600SA-LCD Screen50x35mm1750 sqmm72x45mm3240 sqmm

GEN-SET CONTROLLERS

M60GB05_02_14

Slide14

14

DIFFERENCES BETWEEN RGK700… AND RGK800…

RGK700…RGK800…Digital inputs6 negative + 1 emergency8 negative + 1 emergencyDigital outputs4 static + 3 relay6 static + 3 relay + 1 pulseAnalog inputs3 resistive4 resistiveEXP module compatibility-3Current inputs34Earth leakage control-●400Hz capability-●Built-in serial portRS232RS485Real time clock-●

GEN-SET CONTROLLERS

M60GB05_02_14

Slide15

15

DIFFERENCES BETWEENRGK800… AND RGK900…

RGK800…RGK900…LCD screen128x80 pixels (72x45mm)128x112 pixels (71x61mm)Digital inputs812CANbus channels1 - ECU1 - ECU2 - Genset system linksAnalog outputs-V – PWM forAVR and GovernorMains-Gen parallel operation-RGK900Bus-Gen parallel operation-RGK900SABus-Mains parallel operation-RGK900MCExpansion slots34

GEN-SET CONTROLLERS

M60GB05_02_14

Slide16

16

RGK900… REAR

GEN-SET CONTROLLERS

AVR control

Opto-isolated analog output, fully programmable Voltage mode range: -10…+10 VDCPWM mode: 0…5V No need for dip switches, software controlled.GOVERNOR controlIsolated analog output, fully programmable Voltage mode range: -10…+10 VDCPWM mode: 0…5V No need for dip switches, software controlledControl via engine CANbus as well.CANbus for genset interlink / load sharingCAN2: Opto-isolated interface.

M60GB05_02_14

Slide17

17

OPTICAL PORT ON FRONT

PC link through

USB (CX01)Wi-Fi (CX02)

REMOVABLE LABELLabel for name customising or plant indication

GEN-SET CONTROLLERS

CX01

CX02

M60GB05_02_14

Slide18

18

GEN-SET CONTROLLERS

SCREENSHOTS FOR GRAPHIC DISPLAY

User-friendly interface with completedescriptions during programming(5 languages at the same time)

Easy browsing through measurements and full description texts (5 languages). The texts can be modified through the front optical port.

Customised pages with free text description.Free messages for alarms

Graphs (waveform, stem).

M60GB05_02_14

Slide19

19

GEN-SET CONTROLLERS

RGK4…SA DISPLAY

M60GB05_02_14

Backlighted display with icons which shows:symbols for alarms numeric valuestexts for operation messages, alarms and parameters setting.

Slide20

20

GEN-SET CONTROLLERS

PID CONTROLLERS FOR GOVERNOR AND AVR

M60GB05_02_14

Slide21

21

GEN-SET CONTROLLERS

SYNCHRONISATION

M60GB05_02_14

Slide22

22

OPTICAL PORT ON FRONT

AdvantagesNo need to disconnect the panel power supply to connect with the device.Electrical safety (no physical connection).IP65 protection degreeSimple access to the unit on front.

GEN-SET CONTROLLERS

M60GB05_02_14

Slide23

23

Using CX02 (Wi-Fi), the following is possible:Project upload/download Controller cloningConnection to the device with apps.

PC link through USB (CX01) or Wi-Fi (CX02) for:ProgrammingDiagnosticsData downloadingFirmware upgrade.

GEN-SET CONTROLLERS

OPTICAL PORT ON FRONT

CX01

CX02

M60GB05_02_14

Slide24

24

PROFILE

Low profile and reduced depth are useful during the controller installation even in very compact electrical panels.

GEN-SET CONTROLLERS

RGK7…

/ RGK8… / RGK9…

RGK6…

M60GB05_02_14

Slide25

25

INSTALLATION

Metal elements with screws to guarantee adhesion over time

Expandability with EXP series modules

IP65 rubber gasket

Fixing slots for plastic ties provide for orderly cabling

GEN-SET

CONTROLLERS

M60GB05_02_14

Slide26

26

IP65 TEST ACCORDING TO

IEC 60947-1

GEN-SET

CONTROLLERS

M60GB05_02_14

Slide27

27

LIMIT OF TEMPERATURE TEST FOR LCD

GEN-SET

CONTROLLERS

-30°C

+70°C

M60GB05_02_14

Slide28

28

RADIATED EMISSION AND IMMUNITY TEST

GEN-SET

CONTROLLERS

M60GB05_02_14

Slide29

29

VIBRATION TEST ACCORDING TO IEC 60068-2-6

GEN-SET

CONTROLLERS

M60GB05_02_14

Slide30

30

GEN-SET CONTROLLERS

EXP… EXPANSION MODULES

Plug-in connection at the base unit rearPower supplied by the base unitUp to 1 module for RGK4...SA and RGK610Up to 3 modules for RGK800...Up to 4 modules for RGK900...Plastic retainer for applications with strong vibrations for RGK800... and RGK900...

ADVANTAGESConfiguration flexibilityOnly one code for the base unitPossibility to add functions even after the first installation.

M60GB05_02_14

RGK4...SA

Slide31

31

GEN-SET CONTROLLERS

Plug&Play!

Save

Retry

Digital inputs/outputs

EXP1000 - 4 digital inputs

EXP1001 - 4 digital outputs

EXP1002 - 2 digital inputs + 2 static outputsEXP1003 - 2 relay outputs.Analog inputs/outputsEXP1004 - 2 multifunction analog inputsEXP1005 - 2 multifunction analog outputs. EXP1040 – 2 resistive/digital inputs + 2 static outputsCommunication modulesEXP1010 – USBEXP1011 – RS232EXP1012 – RS485EXP1013 – Ethernet (with web server)EXP1015 – GSM/GPRS Modem.

EXP…

EXPANSION MODULES

The controller

automatically recognises the new system configuration.User is asked to confirm or retry.Parameters of expansion modules need to be programmed to take advantage of new features.

M60GB05_02_14

Slide32

32

TRADITIONAL CONFIGURATION (external GSM modem)Requirements:RS232 serial communication port available on the device (built-in or added by installing an expansion module)External GSM modem with RS232 port.Operations:Configuration of the serial ports both for the device and the modemModem programming using AT commands (for experts only!).

CONFIGURATION WITH EXP1015Requirements:Support of EXP1015 module.Operations:Plug&play module installation (no configuration necessary!).

GEN-SET CONTROLLERS

EXP1015 GSM/GPRS MODEM EXPANSION MODULE

M60GB05_02_14

Slide33

33

12-24VDC

dedicated

supply

CABLE51C7

GSM Antenna

EXP1015

CX03

INSTALLATION

without EXP1015

with EXP1015 + CX03

GEN-SET

CONTROLLERS

M60GB05_02_14

Slide34

34

FUNCTIONSSMS sending and receivingEmail sending with data and diagnostic informationFTP client (log file transfer to a remote FTP server)Connection to remote control software.

GEN-SET

CONTROLLERS

M60GB05_02_14

Slide35

35

EXP1015 FTP FUNCTION

PC with FTP server (available for free on the web)

Internet connection

Static IP address.

EXP1015

GEN-SET

CONTROLLERS

M60GB05_02_14

Slide36

36

EXP1015 FTP FUNCTION

GEN-SET

CONTROLLERS

M60GB05_02_14

Name Dimensions Last update

Index / Test bgs2/

Measurement

VT & CT

Web Slices

Favorites

[ main directory]

Slide37

37

GEN-SET CONTROLLERS

FUNCTIONS

Load managementDummy loads:Threshold and delay for activationThreshold and delay for deactivation4 steps.

Load shedding (non-priority loads):Threshold and delay for non-priority load connectionThreshold and delay for disconnectionMaximum configuration: 4 sets of non-priority loads.

M60GB05_02_14

Slide38

38

GEN-SET CONTROLLERS

Digital inputs and outputsProgrammable inputs (functions and properties)Programmable outputs (functions and properties)Pulse output (energy and status remoting).

FUNCTIONS

Pulse output

M60GB05_02_14

Slide39

39

GEN-SET CONTROLLERS

Analog inputs and outputsProgrammable resistive analog inputsAnalog inputs: 0…10VDC, 0/4…20mA, PT100Analog outputs: 0…10VDC, 0/4…20mA.

FUNCTIONS

M60GB05_02_14

Slide40

40

GEN-SET CONTROLLERS

Alarms

More than 50 alarms ready to use8 user alarms:Programmable source (inputs, outputs, limits, remote variables, PLC variables, remote alarms)Free textProgrammable propertiesAcoustic signals:BuzzerSirenBuzzer + siren.

FUNCTIONS

M60GB05_02_14

Slide41

41

GEN-SET CONTROLLERS

Fuel statusLevel:Autonomy monitoring2 thresholds for minimum levelFuel theft detection.Filling pump:Start and stop thresholdsManual command.

Current protection

Thermal protection

Earth fault current (leakage) monitoring.

FUNCTIONS

M60GB05_02_14

Slide42

GEN-SET CONTROLLERS

42

POWER MANAGEMENT (GEN-GEN)

POWER MANAGEMENT (MAINS-GEN)

Total rated power of running gen-sets

Power

demand

of the load

Actual

reserve

Minimum

reserve (start)

Max

power reserve (stop)

Start / stop

reserve thresholds

Load demand vs. total system power

Max

power

reserve (stop)

Active power management configuration

Mains power

Breaker status / power flow

Mains

PF

Load

demand

Generator

power

Breaker

status /

power flow

Generator

PF

Load

PF

M60GB05_02_14

Slide43

43

GEN-SET CONTROLLERS

Engine operationEngine running hours monitoring3 maintenance periods:Independent periodsTotal, engine running, load connected hour count.Rent managementTotal, engine running, load connected hour countProgrammable alarm generation.

FUNCTIONS

M60GB05_02_14

Slide44

44

GEN-SET CONTROLLERS

Event list250 eventsReading of the measurement causing the event.

Information pages

1 completely free page

1 system page with free generator description.

FUNCTIONS

M60GB05_02_14

Slide45

45

GEN-SET CONTROLLERS

Automatic test

4 operative modes:TestAutoManOff

4 user pages

Selection of 3 measurementsFree titleThe page can be set as the main page.

FUNCTIONS

M60GB05_02_14

Slide46

46

GEN-SET CONTROLLERS

Remote variables(virtual inputs).

Password2-level software password1 locking digital input

Limit thresholdsi.e. min ambient temperature to start auxiliary warm-up systems

FUNCTIONS

M60GB05_02_14

Slide47

47

GEN-SET CONTROLLERS

Generic countersSource selectionWeight setupFree title text.

Changeover operationContactors (2 outputs)Motorised changeover switches (3 outputs)Motorised circuit breakers (4 outputs)

Mutual standbyExchange by timeExchange by startsMutual help.

RS485

RS232

Status

alarms

FUNCTIONS

M60GB05_02_14

Slide48

48

GEN-SET CONTROLLERS

COMMISSIONING

Harmonic analysis and waveformsLoad analysisEnable/disable capability.

Configurations

4 alternative preset configurations

Selection through digital inputs.

Inputs/Outputs

Test mode to force outputs to verify the system

Software adjustment of an offset for resistive inputs to compensate cable length.

PID adjustmentDirect access to PID parameters from displaySetting of PID parameters while engine running.

M60GB05_02_14

Slide49

49

BUILT-IN CANBUS J1939

Supported ECUGeneric J1939Volvo (EDC4, EMS, EMS2)Scania (EMS)DeutzPerkinsJohn DeereIveco (Nef, Cursor).

Capability ofMeasurement readingAlarm readingAlarm resetCommands sending.

Status

Alarms

Commands

J1939

GEN-SET CONTROLLERS

M60GB05_02_14

Slide50

50

GEN-SET CONTROLLERS

PLC logic

Combination of internal status (engine running, AUT mode, etc.) with alarms and digital inputs to drive programmable outputs and to generate alarms according to the specific application.

M60GB05_02_14

Slide51

51

GEN-SET CONTROLLERS

M60GB05_02_14

COMPATIBILITY WITH (CONFIGURATION AND REMOTE CONTROL SOFTWARE)

Slide52

52

GEN-SET CONTROLLERS

Synergy is the new software for control and supervision of Lovato Electric products equipped with communication capabilities via serial ports, Ethernet or modem. With this unique software, it is now possible to monitor and control the Lovato Electric devices connected to a heterogeneous network. Device wiring can be done using different types of networks creating communication channels with a simple and intuitive user interface.

M60GB05_02_14

COMPATIBILITY WITH

(SUPERVISION AND ENERGY MANAGEMENT SOFTWARE)

Slide53

53

APPLICATIONS FOR SMARTPHONES AND TABLETS

LOVATO Electric applications let the user:Set up the deviceSend commands to the deviceRead values and alarmsDownload statistics and eventsEmail retrieved data.

Wi-Fi connection between the smartphone/tablet and CX02Application and driver upgrade possible if an Internet connection is availableCompatible with iOS and Android.

GEN-SET CONTROLLERS

M60GB05_02_14

Slide54

54

GEN-SET CONTROLLERS

RGK4…SA: all the technologies for setup

M60GB05_02_14

Setup operation can be performed through:the front optical port with CX01 (USB) and CX02 (Wi-Fi) donglesNFC interface even if no power supply is available

CX01

CX02

Android

Android

-

iOS

Windows

Slide55

55

GEN-SET CONTROLLERS

REMOTE ACCESS DEVICES FOR RGK800

“MIRRORS” of the main controller: the user operates from a remote site as if in front of the device.

RGK 800 RD SA: Remote display for RGK 800 SARGK 800 RD: Remote display for RGK 800Power supply: 12-24VDCBuilt-in RS485 serial port to connect up to 32 devices4 inputs (commands sent to main controller)1 relay output (remote output of the main controller)1 static output (remote output of the main controller).

“Mirror” installed in the control room

Local controller next to the generator

RS485

M60GB05_02_14

Slide56

56

GEN-SET CONTROLLERS

REMOTE ACCESS DEVICES FOR RGK800

RGK RA (Remote Annunciator)It is possible to remote display the active alarms, to reset them and mute on-board buzzers.Power supply: 12/24VDC or 100…240VACBuilt-in RS485 serial port to connect up to 32 devices.

RS485

M60GB05_02_14

Slide57

57

GEN-SET CONTROLLERS

ALARM-STATUS RELAY UNIT

RGK status (alarms, automatic mode, etc.) remote relay unitEach relay (8 N/O + 4 C/O) corresponds to a logic combination of different status or a single statusUp to 2 units connected together (24 relays).

RGK RR

CODED PULSES

Long distances (1000m)

Refresh time 2.5s

CANBUS

(

parallel with ECU)Short distances (40m)Refresh time 10ms

M60GB05_02_14

Slide58

58

GEN-SET CONTROLLERS

INSTALLATIONS

M60GB05_02_14

Slide59

59

GEN-SET CONTROLLERS

INSTALLATIONS

M60GB05_02_14

Slide60

60

GEN-SET CONTROLLERS

INSTALLATIONS

M60GB05_02_14

Slide61

61

COMPETITION

GEN-SET CONTROLLERS

M60GB05_02_14

Characteristics

LOVATO

RGK600

RGK600SA

RGK601

RGK601SA

Deepsea

DSE4410

DSE4420

Deepsea

DSE4510

DSE4520

Deepsea

DSE6010

DSE6020

COMAP

InteliLite

AMF8-9 / MRS3-4

COMAP

InteliNANO

MRS-AMF-PLUS

Configuration from front panel

-

● (thresholds and I/O)

Programming from front

-

-

-

-

-

Digital inputs

/

outputs

Digital inputs

4

4

4

4

4

2

Emergency input

-

-

-

-

-

Digital/Analog inputs

3

-

3

-

-

4

Digital output

6

6

DSE4510: 4

DSE4520: 6

6

MRS3-4: 4

AMF9: 6

6

Engine motion/speed

W input for engine speed

Alt. with CAN Bus

Alt. with CAN Bus

-

Alt. with CAN Bus

-

-

Pick-up input for engine speed

Alt. with CAN Bus

Alt. with CAN Bus

-

Alt. with CAN Bus

-

-

Voltage/current inputs

Generator and mains voltage inputs

3 ph + N

3ph + N

3ph + N

3ph + N

3ph + N

3ph (MRS)

1ph-2ph (PLUS)

Current inputs

3ph

3ph

3ph

3ph

3ph

1ph (PLUS)

Slide62

62

COMPETITION

GEN-SET CONTROLLERS

M60GB05_02_14

Characteristics

LOVATO

RGK600

RGK600SA

RGK601

RGK601SA

Deepsea

DSE4410

DSE4420

Deepsea

DSE4510

DSE4520

Deepsea

DSE6010

DSE6020

COMAP

InteliLite

AMF8-9 / MRS3-4

COMAP

InteliNANO

MRS-AMF-PLUS

Analog

inputs

Fuel level input

Oil pressure input

Water temperature input

Functions

AMF function

RGK600/601

DSE4420

DSE4520

DSE6020

AMF9

AMF - PLUS

Event log

50 events

5 events

15 events

5 events

100 events

10 events

Sleep mode

-

-

Alternative configurations

4

-

1

1

-

-

Communication

Programming port

USB (CX01)

WiFi (CX02)

USB

USB

USB

USB

USB

Can Bus (J1939)

RGK610/610SA

Alt. with pick-up/W

Alt. with pick-up/W

Housing

Dimensions

144x144x44mm

180x116x42mm

140x113x43mm

215x158x42mm

180x120mm

118x108mm

Slide63

63

GEN-SET CONTROLLERS

RGK6… STRONG SELLING POINTS

Commissioning and maintenance helpers: CX01, CX02 I/O forcing, analog sensor adjustmentharmonic analysisDedicated emergency input:the push button directly open the common supply to EV and FUEL outputsalarm condition is generated by RGK6… without auxiliary inputsReal sleep mode (0 mA from battery) for RGK600SA versionGraphic display.

M60GB05_02_14

Slide64

64

COMPETITION

GEN-SET CONTROLLERS

M60GB05_02_14

Characteristics

LOVATO

RGK700SA

RGK700

Deepsea

DSE6010

DSE6020

Deep-Sea

DSE7210

DSE7220

COMAP

InteliLite

NT-MRS16

NT-AMF25

Inputs + Outputs

6 + 7

4+4 (pickup)

4+6 (no p.up)

7 + 8

6 + 6 (MRS16)

7 + 7 (AMF25)

Alarms

Nr. of programmable alarms

(+ user’s alarms)

50 + 4

17

23 + 6

22

Programmable property alarms

Voltage/Current inputs

Generator voltage inputs

3 ph + N

3 ph + N

3 ph + N

3 ph + N

Mains voltage inputs

3 ph + N

3 ph + N

3 ph + N

3 ph + N

Voltage inputs range

(phase-phase)

50...720

VAC

25…576

VAC

25…576

VAC

0…600

VAC

Analog inputs

Fuel level input

-

Oil pressure input

Water temperature input

Auxiliary analog input

-

-

-

Slide65

65

COMPETITION

GEN-SET CONTROLLERS

M60GB05_02_14

Characteristics

LOVATO

RGK700SA

RGK700

Deepsea

DSE6010

DSE6020

Deep-Sea

DSE7210

DSE7220

COMAP

InteliLite

NT-MRS16

NT-AMF25

Functions

Event log

● (250)

● (5)

● (100)

PLC function

-

-

-

Dual mutual standby

-

Communication

Modem support

-

-

Modbus protocol support

-

-

SMS

-

-

CAN bus / J1939

Option

RS232

-

-

Optional board

RS485

-

-

-

Optional board

Programming port

USB/WiFi

USB

USB

Option

Housing

Dimensions

240x180x40

180x116x42

240x181x42

180x120x55

Slide66

66

COMPETITION

GEN-SET CONTROLLERS

M60GB05_02_14

Characteristics

LOVATO

RGK800SA

RGK800

Deep-Sea

DSE7310

DSE7320

COMAP

InteliCompactNT SPtM/MINT

COMAP

InteliGen

NT-NTC

Inputs + Outputs

8 + 10

8 + 8

9 + 8

12 + 12

Alarms

Nr. of programmable alarms

(+ user’s alarms)

50 + 8

n.a.

n.a.

n.a.

Programmable property alarms

Voltage/current inputs

Generator voltage inputs

3 ph + N

3 ph + N

3 ph + N

3 ph + N

Mains voltage inputs

3 ph + N

3 ph + N

3 ph + N

3 ph + N

Voltage inputs range

(phase-phase)

50...720

VAC

25…576

VAC

0…600

VAC

0…600

VAC

Analog inputs

Fuel level input

Oil pressure input

Water temperature input

Auxiliary analog input

-

-

Functions

Event log

● (250)

PLC function

Dual mutual standby

Slide67

67

COMPETITION

GEN-SET CONTROLLERS

M60GB05_02_14

Characteristics

LOVATO

RGK800SA

RGK800

Deep-Sea

DSE7310

DSE7320

COMAP

InteliCompactNT SPtM/MINT

COMAP

InteliGen

NT-NTC

Communication

Modem/SMS support

Modbus protocol support

Ethernet

with EXP

External module

External module

External module

CAN bus / J1939

RS232

-

Optional board

RS485

Optional board

Programming port

USB/WiFi

USB

Option

USB/RS232

Housing

Dimensions

240x180x40

240x181x42

180x120x55

180x120x55

Expandability

Slide68

68

GEN-SET CONTROLLERS

RGK7… & RGK8… STRONG SELLING POINTS

Commissioning and maintenance helpers: CX01, CX02 I/O forcing, analog sensor adjustmentharmonic analysisBuilt-in CANbus J1939Low profile and reduced depth to install the controller in very compact electrical panelsSupport for EXP series expansion modules (only RGK800...)Metallic elements with screws for long-lasting fixingMutual standby functionIntegration in Synergy software.

M60GB05_02_14

Slide69

69

GEN-SET CONTROLLERS

COMPETITION

M60GB05_02_14

LOVATO

Deepsea

Comap

RGK900SA

RGK900

RGK900MC

DSE7510

DSE7520

DSE7560

DSE8610

DSE8620

DSE8660

DSE8810

-

DSE8860

InteliGenNT

-

InteliMains

InteliGenNTC

-

InteliMains

InteliSYSNT

-

InteliMains

Configuration from front panel

Programming from front port

-

-

-

-

-

-

Programming port

Frontal port with

CX01 (USB)

CX02 (WiFi)

Back port with DSE810 interface

RS232

USB

USB

USB

RS232

RS485

USB

RS232

RS485

RS232

RS485

Maximum rated voltage Ue

600VAC L-L

480VAC L-L

480VAC L-L

480VAC L-L

600VAC L-L

600VAC L-L

600VAC L-L

Current inputs

5

5

5

4

4

4

4

Slide70

70

GEN-SET CONTROLLERS

COMPETITION

M60GB05_02_14

LOVATO

Deepsea

Comap

RGK900SA

RGK900

RGK900MC

DSE7510

DSE7520

DSE7560

DSE8610

DSE8620

DSE8660

DSE8810

-

DSE8860

InteliGenNT

-

InteliMains

InteliGenNTC

-

InteliMains

InteliSYSNT

-

InteliMains

Digital

inputs

12 + 1 for emergency pushbutton

9

11

11

12

12

16

Digital outputs

10

7

10

10

12

12

16

Operating temperature

-30 - +70°C

-30 °C to +70 °C

-30 °C to +70 °C

-30 °C to +70 °C

-20 to +70°C

-20 to +70°C

-20 to +70°C

Frontal protection degree

IP65

IP42

(IP65 with optional gasket)

IP42

(IP65 with optional gasket)

IP42

(IP65 with optional gasket)

IP65

IP65

IP65

Dimension

240x180x44mm

240.0 x 181.1 x 41.7 mm

240 x 181.1 x 41.7 mm

245 x 184 x 50 mm

185 x 123 x 123 mm

185 x 123 x 123 mm

185 x 123 x 123 mm

Slide71

71

GEN-SET CONTROLLERS

COMPETITION

M60GB05_02_14

LOVATO

Deepsea

Comap

RGK900SA

RGK900

RGK900MC

DSE7510

DSE7520

DSE7560

DSE8610

DSE8620

DSE8660

DSE8810

-

DSE8860

InteliGenNT

-

InteliMains

InteliGenNTC

-

InteliMains

InteliSYSNT

-

InteliMains

AVR

Direct connection

Direct connection

Direct connection

Direct connection

External insulator

External insulator

External

insulator

Governor

PWM

-

-

-

Multi gen Island

AMF function

RGK900

DSE7520

DSE8620

-

Multi gen AMF

RGK900MC + RGK900SA

DSE7560 + DSE7510

DSE8660 + DSE8610

DSE8810 + DSE8860

InteligenNT + InteliMains

InteligenNTC + InteliMains

InteliSYSNT + InteliMains

Baseload

Peak shaving

R.O.C.O.F & Vector Shift

PID regulation

On front

PC

PC

PC

PC

PC

PC

Slide72

72

GEN-SET CONTROLLERS

COMPETITION

M60GB05_02_14

LOVATO

Deepsea

Comap

RGK900SA

RGK900

RGK900MC

DSE7510

DSE7520

DSE7560

DSE8610

DSE8620

DSE8660

DSE8810

-

DSE8860

InteliGenNT

-

InteliMains

InteliGenNTC

-

InteliMains

InteliSYSNT

-

InteliMains

Communication

USB (EXP)

RS232 (EXP)

RS485 (Built-in)

Ethernet (EXP)

USB

RS232

RS485

USB

RS232

RS485

Ethernet

USB

RS232

RS485

Ethernet

RS232

RS485

USB

RS232

RS485

Ethernet

RS232

RS485

Slide73

73

GEN-SET CONTROLLERS

COMPETITION

M60GB05_02_14

LOVATO

Woodward

RGK900SA

RGK900

RGK900MC

easYgen-2200 P1

-

-

easYgen-2500 P1

-

-

easYgen-3200 P1

-

-

easYgen-3500 P1

-

-

Configuration from front panel

Programming from front port

-

-

-

-

Programming port

Frontal port with

CX01 (USB)

CX02 (WiFi)

DPC cable

DPC cable

DPC cable

DPC cable

Maximum rated voltage Ue

600VAC L-L

600VAC L-L

600VAC L-L

600VAC L-L

600VAC L-L

Current inputs

5

4

4

4

4

Slide74

74

GEN-SET CONTROLLERS

COMPETITION

M60GB05_02_14

LOVATO

Woodward

RGK900SA

RGK900

RGK900MC

easYgen-2200 P1

-

-

easYgen-2500 P1

-

-

easYgen-3200 P1

-

-

easYgen-3500 P1

-

-

Digital

inputs

12 + 1 for emergency pushbutton

8

10

12

12

Digital outputs

10

6

11

12

12

Operating temperature

-30 - +70°C

-20 to +70°C

-20 to +70°C

-20 to +70°C

-20 to +70°C

Frontal protection degree

IP65

IP65

IP65

IP65

IP65

Dimension

240x180x44mm

219 × 171 × 61 mm

219 × 171 × 98 mm

282 × 217 × 99 mm

282 × 217 × 99 mm

Slide75

75

GEN-SET CONTROLLERS

COMPETITION

M60GB05_02_14

LOVATO

Woodward

RGK900SA

RGK900

RGK900MC

easYgen-2200 P1

-

-

easYgen-2500 P1

-

-

easYgen-3200 P1

-

-

easYgen-3500 P1

-

-

AVR

Direct connection

Direct

connection

Direct connection

Direct connection

Direct

connection

Governor

PWM

Multi gen Island

AMF function

RGK900

Multi gen AMF

RGK900MC + RGK900SA

Baseload

Peak shaving

R.O.C.O.F & Vector Shift

PID regulation

On front

PC

PC

PC

PC

Slide76

76

GEN-SET CONTROLLERS

COMPETITION

M60GB05_02_14

LOVATO

Woodward

RGK900SA

RGK900

RGK900MC

easYgen-2200 P1

-

-

easYgen-2500 P1

-

-

easYgen-3200 P1

-

-

easYgen-3500 P1

-

-

Communication

USB (EXP)

RS232 (EXP)

RS485 (Built-in)

Ethernet (EXP)

-

RS485

RS232

RS485

RS232

RS485

Slide77

77

GEN-SET CONTROLLERS

RGK9… STRONG SELLING POINTS

Commissioning and maintenance helpers: CX01, CX02 I/O forcing, analog sensor adjustmentharmonic analysisPID configuration directly on the unitPower management pages with graphic descriptionSyncronisation pages with graphic descriptionNo external devices required for syncronisation and parallel operationIntegration in Synergy software.

M60GB05_02_14

Slide78

78

www.LovatoElectric.com

Thank you

for your attention!

GEN-SET CONTROLLERS

M60GB05_02_14

www.LovatoElectric.com

Thank

you for the attention!

GEN-SET CONTROLLERS