Download Pdf The PPT/PDF document "Eaton9PX PowerPass" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

1 Eaton9PX PowerPass® For use with 9PX 500
Eaton9PX PowerPass® For use with 9PX 5000/6000/8000/11000 VA UPS Models Class A EMC StatementsFCC Part 15part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interferenceEN 62040-2reproduced in any way without the express written approval of Eaton Corporation. Requesting a Declaration of ConformityEU Directives:2006/95/EC, Council Directive on e

2 quipment designed for use within certain
quipment designed for use within certain voltage limits Special Symbols RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and theassociated warning should be observed. CAUTION: REFER TO OPERATOR'S MANUAL This symbol indicates that you should not discard the UPS or the UPS batteriesin the trash. This product contains sealed, leadacid batteries and must bedisposed of

3 properly. For more information, contact
properly. For more information, contact your local recycling/reuse orhazardous waste center. This symbol indicates that you should not discard waste electrical or electronicequipment (WEEE) in the trash. For proper disposal, contact your localrecycling/reuse or hazardous waste center. Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 41Introduction1System Conf

4 iguration Options2Safety3Equipment Insta
iguration Options2Safety3Equipment Installation7Inspecting the Equipment4Electrical Installation159PXPPDM2 Electrical Installation169PXTFMR11 Electrical Installation209PXPPDM1 and 9PXTFMR5 Electrical Installation235Voltage Selection 279PXPPDM1 and 9PXPPDM2 Voltage Selection28 TABLE OF CONTENTSEaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 49PXTFMR11 Voltage

5 Selection326StartupSystem Configuration
Selection326StartupSystem Configuration Connections407Maintenance Bypass45Using Maintenance BypassReturn to Normal UPS Protection468Specifications499Service and Support55 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4The Eaton 9PX PowerPass Distribution Module (9PX PPDM) and 9PX Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200

6 Rev 4Figure 1 illustrates front views of
Rev 4Figure 1 illustrates front views of the 9PX PPDM and 9PX Transformer Front Cover with Center Cover Attached (all models) 208V240V BYPASS 24V Figure 1. Front Cover and Operation Switches Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4System Configuration OptionsNOTE See “System Configuration Connections” on page 40 for illustrations of the system Eato

7 n 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PX
n 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Safety WarningsIMPORTANT SAFETY INSTRUCTIONSThis manual contains important instructions that you should follow during installation andThe UPS contains To reduce the risk of fire or electric shock, install this UPS in a temperature a

8 nd humidity Eaton 9PXTFMR5, 9PXPPDM2, 9P
nd humidity Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Inspecting the EquipmentChecking the AccessoriesNOTE Packaging must be destroyed according to waste management standards. RecyclingVerify that the accessory items listed in Table 1 are included with the Eaton 9PXTFM

9 R5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 Us
R5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Table 1. Accessories Item (1) Manual (2) Rails and mounting screws for rackmount cabinetinstallation in standard 19-inch rack bays, in accessorybox (1) Joining bracket and mounting screws for towerconfiguration, in the accessory box (2) Mounting brackets and mounting screws forrackmount cabinet installation, in the accesso

10 ry box (1) Transformer cable used from U
ry box (1) Transformer cable used from UPS Output to (2) Cable glands used as strain relief for hardwired cables Table 2 lists the tools that are needed to install the 9PX PPDM and 9PXTransformers.Table 2. Installation Tools Item Phillips® cross-head screwdriverFlat-head screwdriver Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Tower SetupDO NOT install

11 the 9PX PPDMs and 9PX Transformers in a
the 9PX PPDMs and 9PX Transformers in a hermetically-closedNOTE The order of a tower installation, from left to right, is the 9PX PPDM or 9PX EBM, and the 9PX UPS.1.Do this only if the UPS is already installed and operating: ShutNOTE Eaton recommends a minimum of 150 mm (5.9”) free space behind the UPS rearNOTE Joining brackets are required to stabilize the upright cabinets in installatio

12 ns withNOTE If you are adding a cabinet
ns withNOTE If you are adding a cabinet to an existing tower configuration, only add a single Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 Joining Brackets Figure 2. Joining Brackets (9PXTFMR11, 9PX 240V EBM, and 9PX 11k UPSRackmount SetupNOTE The order of a rackmount installation, from top to bottom, is the 9PX UPS, 9PX EBM,NOTE Eaton 9PXTFMR5, 9PXP

13 PDM2, 9PXTFMR11, and 9PXPPDM1 User's Gui
PDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Installing the Rails (Right) FRONT Screw PositionsREARRail-mountingScrew Positions Figure 3. Attaching the Rails Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Installing the Cabinet1.Do this only if the UPS is already installed and operating: Shut Figure 4. Installing Mounting Brackets4.Set the

14 rear of the cabinet on the cabinet moun
rear of the cabinet on the cabinet mounting flanges andslide the cabinet into the rack (see Figure 5). Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 240V Figure 5. Installing the Cabinet in the Rack EBM9PXTransformeror 9PX PPDM Two M6x12Rail-mountingTwo M6x12Cabinet-mountingBracket Screws Figure 6. Cabinet installed in Rack (Front view) Eaton 9PXTFMR5, 9

15 PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's
PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Risk of electrical shock. Only qualified service personnel (such as a licensed electrician) shallTo reduce the risk of fire, unit input connect only to a circuit provided with branch circuitNOTE Do not make unauthorized changes to the 9PX UPS,

16 9PX PPDM, or 9PX TransformerTable 3. Rec
9PX PPDM, or 9PX TransformerTable 3. Recommended Input Circuit Breaker Rating for 9PX PPDMs 9PX PPDM Input Circuit Breaker Rating 9PXPPDM1 9PXPPDM2 ELECTRICAL INSTALLATIONEaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 49PXPPDM2 Electrical InstallationFigure 7 shows the 9PXPPDM2 block diagram. The 9PXPPDM2 I/O Voltage Selection Figure 7. 9PXPPDM2 Block Diagra

17 m ELECTRICAL INSTALLATIONEaton 9PXTFMR5,
m ELECTRICAL INSTALLATIONEaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4To wire the I/O terminal block for the 9PXPPDM2: 208V24V Figure 8. Resetting the Switch to UPS (Normal) ELECTRICAL INSTALLATIONEaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 NORMALAC SOURCE Punch OutKnock-outNormal ACSourceOutput NORMAFigure 9. Remov

18 ing the Terminal Block Cover6.Punch out
ing the Terminal Block Cover6.Punch out the pre-cut knock-out holes for the input and outputconduit.7.Pull the input and output wires through separate conduit, leavingapproximately 0.5m (2 ft) of exposed wire. Attach a flexible metalfitting to the end of each conduit.8.On the UPS, insert each conduit through a wiring access entry.Strip 9 mm (0.35”) of insulation from the end of each incoming

19 wire.9.On the 9PXPPDM2 terminal block, w
wire.9.On the 9PXPPDM2 terminal block, wire the UPS connections(terminals 1…3) and attach the cable gland to the panel (seeFigure 10 and Table 4).10.To wire the load connections (terminals 4…6), observe the following:Connect 4 and 6 (line to line) for 240VConnect 5 and 6 (line to neutral) for 120VConnect 4 and 5 (line to neutral) for 120V11.Connect 7 (ground). ELECTRICAL INSTALLATIONEaton

20 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPP
9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4OUTPUTNORMALAC SOURCE N(L-2N L-2)L-1 120V120V240VSource Input Line 1Source Input Line 2Input GroundOutput Line 1Output Line 2Output GroundOutput NeutralUPS ConnectionsLoad Connections(1 to 3)(4 to 7) Figure 10. 9PXPPDM2 I/O Terminal Block TerminalPosition 9PXPPDM2 Wire Function Terminal WireSize Rating* TighteningTo

21 rque 1 Source Input Line 1 10–16 mm2(8–6
rque 1 Source Input Line 1 10–16 mm2(8–6 AWG) 1.8 ±0.22 Nm(16 ± Source Input Line 2 3 Input Ground 6–16 mm2(10–6 AWG) 4 Output Line 1 10–16 mm2(8–6 AWG) 5 Output Neutral 6 Output Line 2 7 Output Ground 6–16 mm2(10–6 AWG) * Use 8 AWG for 9PXPPDM2 (75 Attach the cable gland to the panel. ELECTRICAL INSTALLATIONEaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 49

22 PXTFMR11 Electrical InstallationFigure 1
PXTFMR11 Electrical InstallationFigure 11 shows the 9PXTFMR11 block diagram. The 9PXTFMR11 I/O AC Output Figure 11. 9PXTFMR11 Block Diagram ELECTRICAL INSTALLATIONEaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4screw (see Figure 12). NORMALAC SOURCENORMALAC SOURCE SELECT Remove Screw Figure 12. Removing the Terminal Block Cover ELECTRICAL INSTALLATIONEaton

23 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXP
9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4OUTPUTNORMALAC SOURCE N(L-2N 120V 240VL-1L-1L-2) Source Input Line 1 Figure 13. 9PXTFMR11 I/O Terminal Block ELECTRICAL INSTALLATIONEaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 TerminalPosition Wire Function Terminal WireSize Rating* TighteningTorque 1 Source Input Line 1 6 A

24 WG 1.8 ±0.22 Nm(16 ± Source Input Line 2
WG 1.8 ±0.22 Nm(16 ± Source Input Line 2 6 AWG 3 Input Ground 6 AWG 4 Output Line 1 6 AWG 5 Output Neutral 6 AWG 6 Output Line 2 6 AWG 7 Output Ground 6 AWG * Use 6 AWG for 9PXTFMR11 (90 Attach the cable gland to the panel.9PXPPDM1 and 9PXTFMR5 Electrical InstallationThe 9PXPPDM1 and 9PXTFMR5 models require a 30A circuit with short circuit and ELECTRICAL INSTALLATIONEaton 9PXTFMR5, 9PXPPDM2,

25 9PXTFMR11, and 9PXPPDM1 User's Guide
9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Figure 14 shows the 9PXPPDM1 block diagram. To UPS 20A CB Figure 14. 9PXPPDM1 Block Diagram ELECTRICAL INSTALLATIONEaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Figure 15 shows the 9PXTFMR5 block diagram. 30A CBVoltage Selection(To UPSTransformerL2N1201205-20R(x3)20A CB20A CB20A CBL2GG5-20R(x3)5-20R

26 (x3)5-20R(x3) L6-30P30A 5-20R(x3) Figure
(x3)5-20R(x3) L6-30P30A 5-20R(x3) Figure 15. 9PXTFMR5 Block DiagramFor the 9PXPPDM1 and 9PXTFMR5 plug-receptacle models:2.9PXTFMR5 only3.9PXPPDM1 ELECTRICAL INSTALLATIONEaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Verify that the bypass switch is in the UPS (normal) position. 208V24V Figure 16. Resetting the Switch to UPS (Normal) Eaton 9PXTFMR5, 9PXPPDM2

27 , 9PXTFMR11, and 9PXPPDM1 User's Guide
, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4NOTE In most applications, the voltage setting does NOT need changing.NOTE The 9PXTFMR11 does not have a voltage switch. The voltage must be wired in the Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 49PXPPDM1 and 9PXPPDM2 Voltage SelectionSee Table 6 for 9PXPPDM1 voltage settings. See Table 7 for

28 9PXPPDM2Table 6. 9PXPPDM1 I/O Voltage
9PXPPDM2Table 6. 9PXPPDM1 I/O Voltage Settings Input Voltage(from UPS) 9PXPPDM1 Output Voltage 208V Switch Position Default 240V Switch Position L6-30R 200 231 115 231/115 200 100 200/100 208 240 120 240/120 208 104 208/104 220 254 127 254/127 220 110 220/110 230 265 133 265/133 230 115 230/115 240 277 138 277/138 240 120 240/120 Table 7. 9PXPPDM2 I/O Voltage Settings Input Voltage(from UP

29 S) 9PXPPDM2 Output Voltage 208V Switch P
S) 9PXPPDM2 Output Voltage 208V Switch Position HV 200 231 115 200 100 208 240 120 208 104 220 254 127 220 110 230 265 133 230 115 240 277 138 240 120 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4To change the 9PXPPDM1 or 9PXPPDM2 voltage switch position:Remove Screws 240V BYPASS Figure 17. Remove the Front Cover Screws 208V240V BYASS Figure 18. Open the

30 Front Cover Eaton 9PXTFMR5, 9PXPPDM2, 9P
Front Cover Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 49PXTFMR5 Voltage SelectionSee Table 8 for 9PXTFMR5 voltage settings.Table 8. 9PXTFMR5 I/O Voltage Settings Input Voltage(from UPS) 9PXTFMR5 Output Voltage 208V Switch Position 5-20R 200 115 100 208 120 104 220 127 110 230 133 115 240 138 120 250 144 125 Remove Screws 240V Figure 19. Remove the Front

31 Cover Screws Eaton 9PXTFMR5, 9PXPPDM2,
Cover Screws Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 208V240V BYAS Figure 20. Open the Front Cover Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 49PXTFMR11 Voltage SelectionSee Table 10 for 9PXTFMR11 plug-receptacle voltages.Table 9. 9PXTFMR11 I/O Voltage Settings for Voltage Selection Terminal Block Input Volta

32 ge(from UPS) 9PXTFMR11 Output Voltage 20
ge(from UPS) 9PXTFMR11 Output Voltage 208V Setting HV 200 231 115 200 100 208 240 120 208 104 220 254 127 220 110 230 265 133 230 115 240 277 138 240 120 250 288 144 250 125 Table 10. 9PXTFMR11 I/O Voltage Settings for Plug Receptacles Input Voltage(from UPS) 9PXTFMR11 Output Voltage 208V Setting 5-20R 200 116 231/115 100 200/100 208 121 240/120 104 208/104 220 128 254/127 110 220/110 230 134

33 265/133 115 230/115 240 139 277/138 120
265/133 115 230/115 240 139 277/138 120 240/120 250 144 288/144 125 250/125 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 LAC SOURCENORMALAC SOURCE SELECT Normal AC Figure 21. Remove the Voltage Selection Terminal Block Cover 208V /240V SELECTIONConnect Terminals 2 208V Connect Terminals 2240V 240VFigure 22. Wire Selected Voltage3.Replace the voltage se

34 lection terminal block cover and secure
lection terminal block cover and secure itwith the Phillips-head screw.4.For startup with the UPS, go to Chapter 4 StartupŽ on page 35. Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4This chapter provides instructions for starting up Eaton 9PX PowerPassTo start up a 9PX PPD

35 M or 9PX Transformer with the UPS:NOTE
M or 9PX Transformer with the UPS:NOTE NOTE Refer to the 9PX UPS user's guide for recommended upstream protection. ForNOTE Before startup, refer to the 9PX UPS/EBM/MBP user's guides for additionalNOTE To change the UPS default settings, refer to “Display Functions” in the UPS user'sRefer to the UPS user's guide for UPS operation.4.For 8k or 11k Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PX

36 PPDM1 User's Guide P-164000200 Rev 4N
PPDM1 User's Guide P-164000200 Rev 4NOTE button until you hear the UPS beep(approximately three seconds).After the UPS is turned on, it conducts a self-test and entersNormal mode. The Failure to match the UPS output voltage may result in a hazardous condition, including Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Plug-Receptacle ConnectionsDO NOT p

37 rotect laser printers with the UPS becau
rotect laser printers with the UPS because of the exceptionally high power9PXTFMR5, 9PXTFMR11 (plug-receptacle/terminal-block wired option),Observe the appropriate load output limits when connecting for your model. T BREAKER 120V~ 20 T BREAKER 120V~ 20 T BREAKER 120V~ 20T 120V~ 20T 120V~ 20T 120V~ 20T 120V~ 20T 120V~ 20T 120V~ 20T BREAKER (9)5-20R 9PXTFMR5 L1 Receptacle Group Figure 23. 9PXTF

38 MR5 L1 Load Output Limits Eaton 9PXTFMR5
MR5 L1 Load Output Limits Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 T BREAKER 120V~ 20 T BREAKER 120V~ 20 T BREAKER 120V~ 20T 120V~ 20T 120V~ 20T 120V~ 20T 120V~ 20T 120V~ 20T 120V~ 20T BREAKER (9)5-20R 9PXTFMR5 L2 Receptacle Group Figure 24. 9PXTFMR5 L2 Load Output Limits (4)5-20R(1)L14-30R TBREAKER240V~ 30A 50A T 120V~ 20 T 120V~ 20 T 120/240V~ 30

39 T 120/240V~ 30 T BREAKERLAC SOURCE L1N
T 120/240V~ 30 T BREAKERLAC SOURCE L1N(L2)L1L-2N (1)L14-30R When the input voltage is 208V, the total output current maximum is 41.7A for either the L1receptacle group or the L-1 terminal.240V: When the input voltage is 240V, the total output current maximum is 45.8A for either the L1receptacle group or the L-1 terminal.(1) Output Line 1(L-1) Terminal 9PXTFMR11 L-1 Terminal 9PXTFMR11 L1 Rec

40 eptacle Group Figure 25. 9PXTFMR11 L1/L-
eptacle Group Figure 25. 9PXTFMR11 L1/L-1 Load Output Limits Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 TBREAKER240V~ 30A 50A T 120V~ 20 T 120V~ 20 T 120/240V~ 30 T 120/240V~ 30 T BREAKERLAC SOURCE L1N(L2)L1L-2N (1) Output Line 2(L-2) Terminal208V: When the input voltage is 208V, the total output current maximum is 41.7A for either the L2receptacle

41 group or the L-2 terminal.240V: When the
group or the L-2 terminal.240V: When the input voltage is 240V, the total output current maximum is 45.8A for either the L2receptacle group or the L-2 terminal. 9PXTFMR11 L-2 Terminal (4)5-20R(1)L14-30R(1)L14-30R Figure 26. 9PXTFMR11 L2/L-2 Output Limits (1)L14-30R(3)5-20R(1)L6-30R 9PXPPDM1 L1 Receptacle Group CIRCUIT 120V~ 20AOUTPUT 120V~ 20AOUTPUT 120V~ 20ACIRCUIT 120V~ 20AOUTPUT 120/240

42 V~ 30AOUTPUT 240V~ 30ACIRCUIT 240V~ 30A
V~ 30AOUTPUT 240V~ 30ACIRCUIT 240V~ 30A TO UPS INPUTNORMALAC FROM UPS OUTPUT Figure 27. 9PXPPDM1 L1 Load Output Limits Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 9PXPPDM1 L2 Receptacle Group CIRCUIT 120V~ 20AOUTPUT 120V~ 20AOUTPUT 120V~ 20ACIRCUIT 120V~ 20AOUTPUT 120/240V~ 30AOUTPUT 240V~ 30ACIRCUIT 240V~ 30A TO UPS INPUTNORMALAC FROM UPS OUTPUT L

43 14-30R(3)5-20R(1)L6-30R Figure 28. 9PXPP
14-30R(3)5-20R(1)L6-30R Figure 28. 9PXPPDM1 L2 Load Output LimitsSystem Configuration ConnectionsThis section provides illustrations of 9PX PPDM and 9PX TransformerNOTE The installation diagrams in this section depict rack configurations. Although theNOTE Refer to the UPS user's guide for additional installation and system configurationNOTE Note the following:For configurations with an MBP

44 or EBM, refer to the appropriate MBP o
or EBM, refer to the appropriate MBP or EBM Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 UPS Connected toInput Power Input from 9PX TransformerConnected to UPS Output Connector UPS9PXTFMR5 Figure 29. 9PXTFMR5 with 9PX5000 or 9PX6000 UPS (Kits 9PX5KTF5 and 9PX6KTF5) 9PX PPDM Input from 9PX PPDMConnected to UPS OutputConnector Input from UPSConnected to

45 9PX PPDMOutput ConnectorUPS9PXPPDM1 Figu
9PX PPDMOutput ConnectorUPS9PXPPDM1 Figure 30. 9PXPPDM1 with 9PX5000 or 9PX6000 UPS (Kits 9PX5KP1 and 9PX6KP1) Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 9PX PPDMConnected to ACSource Input Power Load Output(Terminal-block Figure 31. 9PXPPDM2 with 9PX5000 or 9PX6000 UPS (Kits 9PX5KP2 and 9PX6KP2) Connected to From MBP UPSInput Connection toUPS Normal A

46 CSource Connection Input from 9PXTransfo
CSource Connection Input from 9PXTransformer Connectedto MBP OutputConnector UPS9PXTFMR5EBM andMBPMBP Outputto UPS Output CommunicationConnection forDetecting the MBP Figure 32. 9PXTFMR5, 11k 240V EBM, and 11k MBP with 9PX8000 or 9PX11000 UPS (Kits 9PX8KTF5 and Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 Load Output (IfTerminal-BlockLoad Output (If Plug

47 gedinto Receptacles) Output from UPSConn
gedinto Receptacles) Output from UPSConnected to 9PXTransformer Normal ACSource Input Connector EBM9PXTFMR11UPS Figure 33. 9PXTFMR11 and 11k 240V EBM with 9PX11000 UPS (Kit 9PX11KTF11) Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4NOTE Refer to the 9PX UPS/EBM user's guide

48 for operation information.NOTE You can
for operation information.NOTE You can assemble a system configuration that provides maintenance bypass byadding a 9PX Maintenance Bypass (MBP). See Figure 32 on page 42 for an illustration of thatUsing Maintenance Bypass indicator displays, indicating the UPS is inbypass mode.2.On the 9PX PPDM front cover, unsnap and remove the squarecenter cover.3.Turn the bypass switch on the 9PX PPDM

49 to the BYPASS position(see Figure 34). T
to the BYPASS position(see Figure 34). The 9PX PPDM is now powering your equipmentfrom utility power. Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 240V NORMALBYPASS Figure 34. Setting the Bypass Switch to BypassReplace the 9PX PPDM square center cover. Return to Normal UPS Protection button on the UPS until you hear the UPSbeep (approximately three secon

50 ds). The indicator remains On. Eaton 9
ds). The indicator remains On. Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 indicator displays, indicating theUPS is in bypass mode.5.If the 9PX PPDM voltage switch is set to 208V, confirm the UPSoutput voltage through the front panel (refer to the UPS user'sguide).6.On the 9PX PPDM front cover, unsnap and remove the squarecenter cover.7.Turn the bypa

51 ss switch on the 9PX PPDM to the UPS (no
ss switch on the 9PX PPDM to the UPS (normal)position (see Figure 35). 208V240V Figure 35. Setting the Bypass Switch to UPS (Normal) indicator remains on,indicating that your equipment is now protected by the UPS.9.Reinstall the 9PX PPDM square center cover. Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 U

52 ser's Guide P-164000200 Rev 4Specific
ser's Guide P-164000200 Rev 4Specification Tables 9PXTFMR5 9PXPPDM1 9PXPPDM2 9PXTFMR11 Operating Temperature 0°C to 40°C (32°F to 104°F) Storage Temperature -22°C to 55°C (-7°F to 131°F) Relative Humidity 0–95% noncondensing Altitude 10% derating over 1000m(The altitude shall not exceed 3000m.) Dimensions (WxDxH) 440645130 mm17.3”25.4”5.1” 440645130 mm17.3”25.4”5.1” 440685130 mm

53 17.3” 27.0”5.1” 440 43.5 kg (96 lb) 4
17.3” 27.0”5.1” 440 43.5 kg (96 lb) 44.5 kg (98 lb) 44.5 kg (98 lb) 85 kg (187 lb) Table 12. Input Specifications ModelNumber Input (Sine Wave Waveform) InputVoltage Input Current Input VoltageRange (UPS onBypass AC Mode) FrequencyRange Input Protection 9PXTFMR5 60 Hz(± 3 Hz) none 46-65 Hz none 46-65 Hz Upstream UL 489 type,30A double-pole CB (not supplied) Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFM

54 R11, and 9PXPPDM1 User's Guide P-1640
R11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 Input Protection FrequencyRange Input VoltageRange (UPS onBypass AC Mode) Input Current InputVoltage Number 46-65 Hz Upstream UL 489 type,80A double-pole CB (not supplied) 240V 46-65 Hz Upstream UL 489 type,80A double-pole CB (not supplied) Table 13. Output Specifications ModelNumber Nominal Power Output (Sine Wave Waveform) OutputVoltage A

55 djustable Range Output Protection 9PXTFM
djustable Range Output Protection 9PXTFMR5 5000 VA, 5000W 120V (2)isolated LinearLoad 60 Hz(± 3 Hz) (1) UL 489 type, 30Adouble-pole CB(4) UL 489 type, 20A CB 9PXPPDM1 6000 VA, 6000W 120V (2)isolated240V (1)isolated LinearLoad 46-65 Hz (1) UL 489 type, 30Adouble-pole CB(2) UL 489 type, 20A CB 9PXPPDM2 6000 VA, 6000W 120V (2)isolated240V (1)isolated LinearLoad 46-65 Hz (1) UL 489 type, 30A

56 double-pole CBDownstream UL 489 type(not
double-pole CBDownstream UL 489 type(not supplied) 9PXTFMR11 10000 VA, 10000W 120V (2)isolated240V (1)isolated LinearLoad 46-65 Hz (1) UL 1077 type, 50Adouble-pole CB(2) UL 489 type, 30Adouble-pole CB(2) UL 489 type, 20A CBDownstream UL 489 type(not supplied) Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 Safety Conformance IEC 62040-1:2008, UL 1778 4th

57 ; CSA C22.2 Agency Markings cULus, CE, N
; CSA C22.2 Agency Markings cULus, CE, NOM EMC (Class A) IEC 62040-2:2006 categories C2, CISPR22 Class A, FCC Part 15, Class A Table 15. Power Connections Model Input Connection Output Outlets 9PXTFMR5 (1) L6-30P, power cord 0.9m (2.3 ft) (18) 5-20R 9PXPPDM1 (1) L6-30P, power cord 0.9m (2.3 ft) (1) L14-30R; (1) L6-30R; (6) 5-20 R 9PXPPDM2  3) Hardwired Terminal Block  3) Hardwired Terminal

58 Blockand plug receptacles(2) L14-30R;
Blockand plug receptacles(2) L14-30R; (8) 5-20 R Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Rear Panels CIRCUIT BREAKER 120V~ 20CIRCUIT CIRCUIT BREAKER 120V~ 20 CIRCUIT BREAKER 120V~ 20OUTPUT 120V~ 20OUTPUT 120V~ 20OUTPUT 120V~ 20OUTPUT 120V~ 20OUTPUT 120V~ 20OUTPUT 120V~ 20CIRCUIT BREAKER Output (to UPS)(1) Main CircuitBreaker (One240V-30A) (2) Outp

59 ut CircuitBreakers (Two120V-20A)(2) Outp
ut CircuitBreakers (Two120V-20A)(2) Output CircuitBreakers (Two120V-20A) (18) 5-20R OutputReceptacles Figure 36. 9PXTFMR5 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 TO UPS INPU MAINCIRCUITBREAKER NORMALAC SOURCE (1) Main CircuitBreaker (One240V-30A)Hardwired LoadOutput(Terminal Block)Hardwired UPSConnections(Terminal Block) Input (to UPS) Output (to

60 UPS) NORMALAC SOURCE Figure 37. 9PXPPDM
UPS) NORMALAC SOURCE Figure 37. 9PXPPDM2 CIRCUIT AC SOURCE CIRCUIT50ASELECT OUTPUT 120V~ 20 OUTPUT 120V~ 20CIRCUITCIRCUIT OUTPUT 120/240V~ 30 OUTPUT 120/240V~ 30 CIRCUIT BREAKER(2) L14-30R Output Receptacles (8) 5-20R OutputReceptacles(2) Output CircuitBreakers (Two120V-20A) (1) OutputCircuit Breaker(One 240V-50A) Output (toUPS)Optional Load OutputConnections (wired terminalblock)Load Vol

61 tage Selection(wired terminal block) (2)
tage Selection(wired terminal block) (2) Output CircuitBreakers (Two240V-30A) OUTPUT Figure 38. 9PXTFMR11 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4 (1) Main CircuitBreaker (One240V-30A) (2) Output CircuitBreakers (Two120V-20A) AC Source CIRCUIT 120V~ 20AOUTPUT 120V~ 20AOUTPUT 120V~ 20ACIRCUIT 120V~ 20AOUTPUT 120/240V~ 30AOUTPUT 240V~ 30ACIRCUIT 24

62 0V~ 30A TO UPS INPUTNORMALAC FROM UPS OU
0V~ 30A TO UPS INPUTNORMALAC FROM UPS OUTPUT Figure 39. 9PXPPDM1 Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164000200 Rev 4Help Desk1-800-461-9166 ext 260NOTE For critical applications, immediate replacement may be available. Call the for the dealer or distributor nearest you. SERVICE AND SUPPORTEaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide P-164