Remarks & Questions on Remarks & Questions on

Remarks & Questions on - PowerPoint Presentation

hotmountain
hotmountain . @hotmountain
Follow
343 views
Uploaded On 2020-07-03

Remarks & Questions on - PPT Presentation

Lucasz concept Feedback on LHCb cooling review B Verlaat EPDTFS 11 February 2016 Remarks On the current PampID there is no way to pressurize the detector from the LUCASZ plant to do a leak check for example ID: 794150

design lucasz remarks lite lucasz design lite remarks amp questions concept plant safety valves changed point disks service burst

Share:

Link:

Embed:

Download Presentation from below link

Download The PPT/PDF document "Remarks & Questions on" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

Slide1

Remarks & Questions on Lucasz concept

Feedback on LHCb cooling reviewB. Verlaat, EP-DT-FS11 February 2016

Slide2

Remarks:On the current P&ID, there is no way to pressurize the detector from the LUCASZ

plant to do a leak check for example. On this point the design of Lucasz has been changed (LUCASZ lite

)

On the 3D it seems there is pipe above the motor of the pump, think about the maintenanceOn this point the design of Lucasz has been changed (LUCASZ lite)We would not remove the ‘’service components”.The service components need to be discussed, as it is a matter of budget, maybe a manual version is possibleExperience in CMS has shown that the concept of including a cold box in the cooling plant has numerous well appreciated advantages. It would be good if this can also be implemented in the VELO plant design.A foam construction was chosen because of budget.The design of the frame looks very light considering that LEWA pumps generate vibrations. Frames should be rather rigid to avoid resonance. On this point the design of Lucasz has been changed (LUCASZ lite)The design does not look like it is optimised. More compact seems possible.LUCASZ lite has implemented this

Remarks & Questions on LUCASZ concept

2

Slide3

Remarks & Questions on LUCASZ concept

Remarks:A good trade-off study between safety valves and burst disks should be performed. Safety valves often leak, burst disks require higher system pressures.The system already has the absolute minimum of safety valves.

Questions:

Is there compressed air in the assembly area?The new Lucas-lite design has no air3