/
PLC NANO MANAGING SAFETY FUNCTIONS PLC NANO MANAGING SAFETY FUNCTIONS

PLC NANO MANAGING SAFETY FUNCTIONS - PowerPoint Presentation

marina-yarberry
marina-yarberry . @marina-yarberry
Follow
395 views
Uploaded On 2016-05-12

PLC NANO MANAGING SAFETY FUNCTIONS - PPT Presentation

acting on electrical p ower for MEYNA ExperimentsBarracks PLC TYPE AND FUNCTION PLC SCHNEIDER of type TSXNANO TSX07 312422 out of production by SCHNEIDER Installed by EL at the end of the 90s ID: 316970

2012 plc infante behalf plc 2012 behalf infante nano cut plc

Share:

Link:

Embed:

Download Presentation from below link

Download Presentation The PPT/PDF document "PLC NANO MANAGING SAFETY FUNCTIONS" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

Slide1

PLC NANO MANAGING SAFETY FUNCTIONS

acting on electrical

p

ower

for

MEY/NA Experiments/BarracksSlide2

PLC TYPE AND FUNCTION

PLC

SCHNEIDER

of type TSX-NANO (TSX-07 312422), out of production by SCHNEIDERInstalled by EL at the end of the ’90’sIt manages safety inputs, such as FIRE, GAS, TEMPERATURE and AUL to cut the power of the Experiment and/or its barracks and/or its clim, based on the logic below:

08/10/2012

S. Infante on behalf of EN/EL

2

/7Slide3

Some photos

08/10/2012

S. Infante on behalf of EN/EL

3

/7Slide4

POWER CUT OF ALPHA EXP.

After the power cut of ALPHA Experiment (

193 - AD

Complex) on the 28/07/2012, due to failure of a PLC NANO, a MERI was issued (EDMS 1234142) and the incident discussed during a TIOC meeting.The Group EL clarified that, although the PLC’s

had been installed by EL based on Users request at the time, they are are not EN/EL responsibility, nor within EL competences and mandate.

08/10/2012

S. Infante on behalf of EN/EL4/7Slide5

NUMBER OF PLC installed

An

inventory

has been done by EL in the mean time. 21 PLC’s of this type have been found in Meyrin and North Area experimental areas:

3 in AD

2 in West Hall7 in East Hall

1 in nTOF3 in EHN15 in EHN208/10/2012S. Infante on behalf of EN/EL

5

/7Slide6

Current situation

By a visual

inspection

of the installations, it has been noted that the majority of inputs are bridged (Temp, Gas,..) and some are not even cabled.In West Hall 2 PLC’s

still running could be dismantled since all inputs are bridged (no more beam lines).

2 versions of PLC software programs have been found (with a minor variant between the 2 programs).

A general PLC electrical drawing exists, that would need to be crosschecked for each installed PLC (to mark what is really cabled and what it is not).08/10/2012

S. Infante on behalf of EN/EL

6

/7Slide7

Common approach for all PLC

Due to the obsolescence of the

material, the installation and the difficulty to have PLC

NANO spares, all PLC’s will have to be replaced In the mean time the 2 PLC in WH could be removed and kept as spareThe visual inspection in the PLC rack proved that a

risk analysis should be re-evaluated for each installation, to know exactly what information should cut the power of an Experiment and its barracks.

Extreme difficulty we’ve found so far to know who to contact to bring up this issue (Facility M

anager, Infrastructure Responsible, Experiment Responsible, TSO’s, DSO’s, HSE, GS-ASE, EN-MEF,…).Who will have to take care of this upgrade has to be clarified!08/10/2012

S. Infante on behalf of EN/EL

7

/7