IEC 61850 enabled UniGear May 2013 Tenders 0 1 0 0 1 1 0 0 1 0 0 1 1 0 1 0 1 0 1 0 0 1 0 1 0 1 1 1 1 0 0 0 1 0 1 0 1 0 1 0 0 1 1 0 0 0 1 1 1 0 0 1 0 1 0 1 0 1 0 1 1 0 1 0 1 0 1 1 1 1 0 0 0 1 1 0 1 0 1 0 ID: 774145
Download Presentation The PPT/PDF document "IEC 61850 enabled UniGear" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.
IEC 61850 enabled UniGear May 2013 Tenders 0 1 0 0 1 1 0 0 1 0 0 1 1 0 1 0 1 0 1 0 0 1 0 1 0 1 1 1 1 0 0 0 1 0 1 0 1 0 1 0 0 1 1 0 0 0 1 1 1 0 0 1 0 1 0 1 0 1 0 1 1 0 1 0 1 0 1 1 1 1 0 0 0 1 1 0 1 0 1 0 0 1 0 1 0 1 0 1 0 1 0 0 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 1 1 1 1 0 1 0 1 0 1 0
IEC 61850 enabled MV Primary switchgear Main Accessories ABB’s Relion ® IEDs with IEC 61850 native support Managed Ethernet Switch/ esCommunication Links H01 H02 H03 H04 H05
IEC 61850 enabled MV Primary switchgear Main Accessories / IED with IEC 61850-8-1 interface Converter is needed (communication gateway, card …) Supported communication Vertical
IEC 61850 enabled MV Primary switchgear Main Accessories / IED with IEC 61850-8-1 interface Relion ® protection and control True, native support for IEC 61850 Supported communications Vertical Horizontal GOOSE Dedicated web page www.abb.com/relion
IEC 61850 enabled MV Primary switchgear Main Accessories / Ethernet Switch Managed Ethernet Switch “Substation hardened” to the same level as IEDs Recommended to use all switches from the same vendor, especially when building ring architecture ABB AFS family
IEC 61850 enabled MV Primary switchgear Main Accessories / Ethernet Switch Managed Ethernet Switch Type of switch Compact – Fixed number of ports (connections) Modular – Variable number of ports and their types Type of Port Copper / Fiber
IEC 61850 enabled MV Primary switchgear Main Accessories / Communication Links Optical: Duplex Patch cord with LC-LC connectors Patch cord (cable) Electrical or optical cable used to connect one device to another for data routing It is terminated by connectors on both ends Electrical cable is susceptible to EMI, therefore should be only used inside cabinets Electrical : STP cable Cat.6 or better with RJ45-RJ45 connectors LC RJ45
IEC 61850 enabled MV Primary switchgear Single Network Architecture Typical architecture IEDs are connected directly to Managed E thernet switch Supported by all IEDs Backbone Ring network … …
IEC 61850 enabled MV Primary switchgear Ring (Self-healing) Data is sent into both directions on the ring Essential part is Managed Ethernet switchSupported by 611, 615 (except RED), 620 Series IEDs max. 30 IEDs
IEC 61850 enabled MV Primary switchgear Ring (HSR) - Redundant Network Architecture High-availability Seamless Redundancy ( HSR) Same data is sent into both directions on the ring Eliminating communication downtimeSupported by 615 Series IEC (except RED) and 620 Series IEC max. 30 IEDs
IEC 61850 enabled MV Primary switchgear Double (PRP) - Redundant Network Architecture Parallel R edundancy Protocol (PRP) Same data is sent to both networks with identical topologyEliminating communication downtimeSupported by 615 Series IEC (except RED) and 620 S eries IEC LAN B LAN A
IEC 61850 enabled MV Primary switchgear Ethernet Network Topology Ring Built-in redundancy Centralized /Decentralized Interconnection Fiber optic Ring Network Topology Decentralized ring Architecture
IEC 61850 enabled MV Primary switchgear Accessories L ayout Ethernet switch RSG2100 assembled in LVC of UniGear Location Inside Low Voltage Compartment of the switchgear panels Typically in Bus riser, Metering panel Main benefits Cubicles are ready for connection Saving space in substation building Shorter communication links Cheaper solution
IEC 61850 enabled MV Primary switchgear UniGear Pro Global Tendering Tool fo r Air-insulated UniGear panels
IEC 61850 enabled MV Primary switchgear IED Communication Protocol and Media 3. Select IED Communication protocol IEC61850 Single + GOOSE IEC61850 Ring (Self-healing) + GOOSE IEC61850 Ring (HSR) + GOOSE IEC61850 Double (PRP) + GOOSE IEC61850 Single IEC61850 Ring (Self-healing) IEC61850 Ring (HSR) IEC61850 Double (PRP) 4 . Select Communication media Galvanic (RJ45) Optic Glass Fiber 1. Open Switchgear data window 2. Select tab Control
3. Select sub-tab Relays 2. Select tab Functional unit 1. Open Panel data window 4. Press Add button IEC 61850 enabled MV Primary switchgear Intelligent Electronic Device (Relay) 5. Select Relay Applied filters Communication protocol Communication medium 6. Press OK button
IEC 61850 enabled MV Primary switchgear Ethernet Switches 1. Open Switchgear data or Panel data window 2. Select tab Additional articles 3. Select Type Communications 4. Select Make ABB … 5. Select Variant Ethernet Switches 6. Select Type of Ethernet Switch 7. Press Add button
IEC 61850 enabled MV Primary switchgear Communication cables (Patchcords) 1. Open Switchgear data or Panel data window 3. Select sub-tab Additional articles 4. Select Type Communications 5. Select Make Miscellaneous 6. Select Variant Patchcords 7. Select Type of Patchcord 8. Press Add button 2. Select tab Functional unit