8. Troubleshooting 8. Troubleshooting

8. Troubleshooting - PowerPoint Presentation

olivia-moreira
olivia-moreira . @olivia-moreira
Follow
350 views
Uploaded On 2020-01-16

8. Troubleshooting - PPT Presentation

8 Troubleshooting Daikin Altherma Monoblock CA 8 Troubleshoot Error code based troubleshoot Service tools Dchecker Updater Configurator Inverter analyzer Common mistakes Contact information ID: 772989

pcb check water error check pcb error water internal unit troubleshooting hydro inverter a1p service outdoor replace based faulty

Share:

Link:

Embed:

Download Presentation from below link

Download Presentation The PPT/PDF document "8. Troubleshooting" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

8. Troubleshooting Daikin Altherma Monoblock CA

8. Troubleshoot Error code based troubleshoot Service tools D-checker Updater Configurator Inverter analyzer Common mistakes Contact information

Title - Internal use only 3 Error code based troubleshoot 1.

Title - Internal use only 4 1. Error code based troubleshooting Overvieuw of all error codes Full description of most common error codes Referal to Service Manual

Title - Internal use only 5 1.1 Error code based troubleshooting – Overvieuw of all error codes

8. Troubleshooting- Internal use only 6 1.2 Error code based troubleshoot – Most common error codes – 7H Water Flow Trigger Effect Reset System detects flow abnormality during operation. Flow < 12 l/min for 15 seconds. Unit will stop operating, after some time will automatically try to start operation again. Auto-reset. Possible causes Check Corrective action Closed valve in water circuit. Check if all valves are open. Adjust / open valve. Water pressure is too low. Check the water pressure on the pressure gauge. Check for possible water leak. Fix water leak. Purge air out of unit and field supplied water system and backup heater.

8. Troubleshooting- Internal use only 7 1.2 Error code based troubleshoot – Most common error codes – 7H Water Flow Possible causes Check Corrective action Air in water circuit / unit. Check if all air purge valves are open. Check if all air purge valves are open. Check if air purge valves are installed on all highest points of the field installed water circuit. Purge air out of unit and field supplied water system and backup heater. Static pressure of water circuit is too high. Check the system design and determine static pressure of the water circuit (for each loop). Correct hydraulic field circuit (e.g. use of balancing bottle). Water filter is blocked. Check water filter. Clean water filter . Check water quality and possible source of dirt.

Title - Internal use only 8 1.2 Error code based troubleshoot – Most common error codes – 7H Water Flow Possible causes Check Corrective action Faulty 3-way valve for DHW/SPH Check 3-way valve for DHW/SPH Replace 3-way valve Faulty flow sensor / hydro PCB A1P Check flow sensor Replace flow sensor or replace hydro PCB A1P. If flow sensor failed due to contamination, check for source of contamination and consider to install an additional water filter. Faulty water pump / hydro PCB A1P. Check water pump Replace water pump or replace hydro PCB A1P No by-pass installed. Check by-pass settings Install by-pass. Settings of by-pass are wrong. Check by-pass settings Change settings.

Title - Internal use only 9 1.2 Error code based troubleshoot – Most common error codes – AA BUH safety error Trigger Effect Reset Thermal protector Q1L is activated (temp > 90°C). Unit will stop operating. Power reset + reset via user interface + pressing the button on the Q1L (if activated). Possible causes Check Corrective action Air in water circuit / backup heater. Check if all air purge valves are open. Check if air purge valves are installed on all highest points of the field installed water circuit. Purge air out of unit and field supplied water system and backup heater.

8. Troubleshooting- Internal use only 10 1.2 Error code based troubleshoot – Most common error codes – AA BUH safety error Possible cause Check Corrective action Increased water temperature by external heat source. Check if another heat source is installed on the same water circuit. Correct hydraulic field circuit. Faulty thermal protector Q1L/hydro PCB A1P. Check thermal protector backup heater Q1L Replace thermal protector backup heater Q1L or hydro PCB A1P . Faulty thermistor R2T (after backup heater) / hydro PCB A1P. Check thermistor R2T Replace thermistor R2T or hydro PCB A1P. Faulty thermistor R1T (leaving water) / hydro PCB A1P. Check thermistor R1T Replace thermistor R1T or hydro PCB A1P

8. Troubleshooting- Internal use only 11 1.2 Error code based troubleshoot – Most common error codes – AA BUH safety error Possible cause Check Corrective action Faulty backup heater assy / hydro PCB A1P. Check backup heater Replace the faulty components (backup heater or hydro PCB A1P . Water pressure is too low. Check the water pressure on the pressure gauge. Increase water pressure till ~2 bar. Water flow is too low. Check the mimimum water flow required for the system. Adjust system to meet the water flow requirements. (12 l/min)

8. Troubleshooting- Internal use only 12 1.2 Error code based troubleshoot – Most common error codes – AH Disinfection operation warning/error Trigger Effect Reset Disinfection setpoint is not reached or not kept for requested time. Unit will continue operating. Auto-reset when next disinfection is completed. Possible cause Check Corrective action Large hot water quantity has been tapped during / before disinfection. Check when the disinfection is scheduled (schedule it when there is little chance that water will be tapped so that the disinfection can finish in time). Adjust schedule timer and/or related settings. Backup heater is restricted during disinfection. Check the backup heater settings [2-00] till [2-04]. Adjust related settings. Faulty water tank thermistor R5T / hydro PCB A1P. Check thermistor R5T Replace thermistor R5T or hydro PCB A1P

8. Troubleshooting- Internal use only 13 1.2 Error code based troubleshoot – Most common error codes – AH Disinfection operation warning/error Possible cause Check Corrective action Tank setting not OK. Check settings regarding tank (e.g. [E-06]; [E-07]). Change settings. Backup heater not allowed. Check setting backup heater (e.g. [4-00]). Change settings.

8. Troubleshooting- Internal use only 14 1.2 Error code based troubleshoot – Most common error codes – AC-21 Indoor PCB combination malfunction Trigger Effect Reset System detects combination mismatch between Hydro PCB A1P and the extension PCB Unit will stop operating. Manual reset via user interface. Possible causes Check Corrective action Wrong unit combination. Check combination database. Correct installation. Wrong field setting for compressor type. Check setting [E-01]. Check setting [E-01] to correct value. Faulty outdoor inverter PCB. Check if the correct spare part PCB was installed. Replace outdoor inverter PCB when Required Faulty outdoor main PCB. Check if the correct spare part PCB was installed. Replace outdoor main PCB when required Faulty hydro PCB A1P. Check if the correct spare part PCB was installed. Replace hydro PCB A1P when required

8. Troubleshooting- Internal use only 15 1.2 Error code based troubleshoot – Most common error codes – UA PCB communication Trigger Effect Reset System detects combination mismatch between outdoor main PCB and hydro PCB A1P or outdoor inverter PCB. Unit will stop operating. Auto-reset. Possible causes Check Corrective action Wrong unit combination. Check combination database. Correct installation. Wrong field setting for compressor type. Check setting [E-01]. Check setting [E-01] to correct value. Faulty outdoor inverter PCB. Check if the correct spare part PCB was installed. Replace outdoor inverter PCB when Required Faulty outdoor main PCB. Check if the correct spare part PCB was installed. Replace outdoor main PCB when required Faulty hydro PCB A1P. Check if the correct spare part PCB was installed. Replace hydro PCB A1P when required

8. Troubleshooting- Internal use only 16 1.2 Error code based troubleshoot – Most common error codes – U4 Defective transmission between indoor and outdoor unit. Trigger Effect Reset Hydro PCB A1P detects abnormal transmission to outdoor main PCB for a certain time. Unit will stop operation. Auto-reset. Possible causes Check Corrective action Power supply is not OK -> imbalance > 10%. Check power supply for voltage fluctuations (> 10%). Voltage fluctuations should be less than 10%. Wiring between outdoor main PCB and hydro PCB A1P is not OK. Check the wiring (refer to the wiring diagram). Correct the wiring. Faulty outdoor main PCB. Replace outdoor main PCB Faulty hydro PCB A1P. Replace hydro PCB A1Pa External factor (e.g. electrical noise) (cause when error is reset after power reset, and error happens again after awhile). Check for source which could cause electrical interference.

8. Troubleshooting- Internal use only 17 1.3 Error code based troubleshoot – Referal to service manual Service manual available on extranet ! Full error code based troubleshoot Symptom based troubleshoot Component checklistComponent repair = full replacement procedure for all parts.

Title - Internal use only 18 Service tools 2.

8. Troubleshooting- Internal use only 19 2. Service tools D-checker Updater Configurator Inverter analyzer

8. Troubleshooting- Internal use only 20 2.1 Service tools – D-checker D-Checker is a service tool to read out & record operating parameters from below units Split Sky -air ZEAS Convenipack : AC17 model R410A Daikin Altherma LT units (GSHP, Hybrid, LT-BB , LT-CA, LT-CB, MB-CA, …)

8. Troubleshooting- Internal use only 21 2.1 Service tools – D-checker What ? Where ? Extranet + complete work instruction Partnumber 999495P 7-pin connector to connect to split outdoor unit 5-pin connector to connect to outdoor unit ( multi-split, sky -air) or indoor ( Daikin Altherma LT-C*) USB-A/B to provide power

8. Troubleshooting- Internal use only 22 2.1 Service tools – D-checker 5-pin connector Daikin Altherma D - Checker Communication + power USB Daikin Altherma unit connector X10A on Hydro PCB A1P

8. Troubleshooting- Internal use only 23 2.2 Service tools – Updater Service tool used to update software for Daikin Altherma units. User interface for monobloc : V.1.16 or higher Indoor unit for monobloc CA: ID4583 or higher depending on model!!! Partnumber = EKPCCAB3 D-checker cable 999495P Software write cable 5010992 Extention cable for user interface 5006207 Download software: extranet /software downloads/ service software/ heating product + work instruction !

8. Troubleshooting- Internal use only 24 2.3 Service tools – Configurator Marketing tool Possible to make settings on PC Download setting from PC to unit Upload settings from unit to PCChange language on unitPartnumber = EKPCCAB* Download software : http://www.daikineurope.com/support-and-manuals/software-downloads/heating /

8. Troubleshooting- Internal use only 25 2.4 Service tools – Inverter analyzer If abnormal stop occurs due to compressor startup failure or overcurrent output when using an inverter unit, it is difficult to judge whether it is caused by the compressor failure or other failure ( control pcb, power module, ..)  Inverter checker makes it possible to judge the cause of trouble . It checks whether the inverter signal is being sent from the inverter pcb to the compressor. partn °: 1368521 (RSUK0917A)

8. Troubleshooting- Internal use only 26 2.4 Service tools – Inverter analyzer Instructions – connection to the unit Turn the power off before connecting the inverter checker Make sure the charged voltage of the built-in smoothing electronic capacitor drops to 10 VDC or below before carrying out the service work. (1) Remove the faston terminals from the terminal block of the compressor. (2) Connect the faston terminals to the terminals of the Inverter Analyzer. Be careful that the terminals (U,V,W) don’t touch each other , high voltage is applied !

8. Troubleshooting- Internal use only 27 2.4 Service tools – Inverter analyzer Instructions – Small outdoor unit – start inverter check Unit needs to be started in TEST mode! Check IRGIf not , during initialisation , the compressor will not be detected, hence the unit will give an error.In TEST mode, this ‘missing’ signal will be ignored for about 20 minutes.Turn power back on and activate inverter test on service monitor pcb by pushing dipswitch SW1 for 5 seconds ( selector SW2 can be set to either heat or cool)

8. Troubleshooting- Internal use only 28 2.4 Service tools – Inverter analyzer Instructions – Big outdoor unit – start inverter check

8. Troubleshooting- Internal use only 29 2.4 Service tools – Inverter analyzer Instruction – Evaluation If all 6 leds light up  problem is compressor related If not all 6 leds light up  problem is inverter pcb related Instruction – Disconnection To disconnect the Inverter Analyzer, power off the unit and wait a couple of minutes untill all the leds are off ( unloading of the capacitors , 500VDC). Then disconnect the Inverter Analyzer and reconnect the compressor (correct connection of UVW !). Power ON the unit again .