/
Demand control ventilation: Demand control ventilation:

Demand control ventilation: - PowerPoint Presentation

sherrill-nordquist
sherrill-nordquist . @sherrill-nordquist
Follow
375 views
Uploaded On 2018-02-22

Demand control ventilation: - PPT Presentation

maximize savings with practical approaches Scott Hackel Senior Energy Engineer Minnesota Energy Expo September 26 2016 Minnesota Conservation Applied Research and Development CARD Grant Program ID: 634264

zone dcv design flow dcv zone flow design study field sequence sensor reset control ventilation sensors damper occupancy system

Share:

Link:

Embed:

Download Presentation from below link

Download Presentation The PPT/PDF document "Demand control ventilation:" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

Slide1

Demand control ventilation:

maximize savings with practical approaches

Scott Hackel, Senior Energy Engineer

Minnesota Energy Expo

September 26, 2016Slide2

Minnesota Conservation Applied Research and Development (CARD) Grant Program

AcknowledgementSlide3

Quality DCV design

Field study results

(Re)commissioning

Program recommendations

Today’s topicsSlide4

Background on DCV

FIELD STUDY

Sensor

VAV Boxes

Central and/or Zone Control

AHU

Source: http://i.stack.imgur.com/4WKDC.jpg

SA

OA

RASlide5

Quality DCV designSlide6

Specific sequence

- CO

2

setpoint

- Outside airflow lower limit

CO

2

sensor location

Airflow measurement req.

Choose responsible party

Be complete:

Mechanical engineer

Controls contractor

Other (vendor, …)

Be thorough

DCV DESIGNSlide7

1. Direct OA flow control

Zone CO

2

sensors

b. Return CO

2

sensor

Slight potential for imperfect IAQ…

More potential for imperfect IAQ…

SA

OA

RA

BAS

BAS

Sequence options

DCV DESIGNSlide8

Ventilation reset

Zone outdoor airflow

V

oz

500 600

700

= 1800

Zone primary airflow

V

pz

1500 2000 1500 = 5000

Zone OA fraction

Z

pz

=

V

oz

/

V

pz

0.33 0.30

0.47

Average OA fraction

X

s

=

V

ou

/

V

ps

= 1800/5000

0.36

System vent efficiency

E

v

= 1 +

X

s

– max

Z

pz

= 1 + 0.36 – 0.47

0.89

System OA intake flow

V

ot

=

V

ou

/

E

v

= 1800/0.89

2020

Figure and table used with permission from Trane, a business of Ingersoll Rand.

Sequence options

DCV DESIGNSlide9

Ventilation reset

Zone outdoor airflow

V

oz

500 600

400

= 1500

Zone primary airflow

V

pz

1500 2000 1500 = 5000

Zone OA fraction

Z

pz

=

V

oz

/

V

pz

0.33

0.30 0.27

Average OA fraction

X

s

=

V

ou

/

V

ps

= 1500/5000

0.30

System vent efficiency

E

v

= 1 + X

s

– max

Z

pz

= 1 + 0.30 – 0.33

0.97

System OA intake flow

V

ot

=

V

ou

/

E

v

= 1500/0.97

1550

Figure and table used with permission from Trane, a business of Ingersoll Rand

Sequence options

DCV DESIGNSlide10

2. Ventilation reset

OA flow reset

b. Zone, then OA flow reset

c. Zone, then OA flow reset, with occupancy sensors

BAS

Sequence options

DCV DESIGNSlide11

Upper limit

Freeze protection

Mitigates failures

Lower limit

Save energy

Maintain press.

Elements of sequence

DCV DESIGNSlide12

CO

2

setpoint

Setpoint(s) per:

 

Proportional or single

setpoint

Elements of sequence

DCV DESIGNSlide13

Ideally in zone

At breathing height (3-6 ft.)

Not below a thermostat

Common return

Limited situations

Show on drawings!

CO

2

sensor location

DCV DESIGNSlide14

Use AFMS

(not damper position)

Careful layout

on

dwgs

:

Consider manufacturer requirements

If possible: second intake for economizer

Airflow measurement

DCV DESIGNSlide15

Use occupancy sensors!

Occ. sensor

= VAV savings, aside from

DCV

Consider

OA

diversity in sizing

DCV: not just a ‘Yes / No’ choice

Control portion of zones

Strategically use common return

Use 2-way dampers

Mix approaches

Other considerations

DCV DESIGNSlide16

Field study resultsSlide17

Characterization of approaches

FIELD STUDY

96 systems around Minnesota

:Slide18

Approaches (sequences):

1a. Direct OA flow control, return

sens.

1b.

Direct OA flow control

2a. Ventilation reset

2b. Zone box, then ventilation reset

2c. Zone min. reset, w/ occ. sensors

Characterization of approaches

FIELD STUDYSlide19

Measured savings per design OA rate (cfm)

Occ. + CO

2

sensing

High lower limit

With ERV

Median = $0.50/cfm

Results

FIELD STUDYSlide20

Results

FIELD STUDY

We also scaled the results to a Duluth climateSlide21

Results

FIELD STUDY

Savings are heavily weighted toward heating fuelSlide22

Deficiencies

Recommissioning

FIELD STUDYSlide23

Recommissioning results

FIELD STUDY

Half the systems saved more, an average of 54%Slide24

Economics

FIELD STUDYSlide25

(Re)commissioningSlide26

Conduct when hot, or very cold outside

Review CO

2

and OA flow trends:

CO

2

(ppm)

OA flow (cfm)

Find lower limit

(also look for upper)

CO

2

follows occupancy

OA flow increases per sequence

Virtual performance checks

CxSlide27

OA not directly

ctrld

.

= 480 ppm

Determine control: 1) OA damper position vs. 2) OA flow measurement (if available)

Check for rogue DCV zones

Check CO

2

sensor reading at unoccupied

Determine OA damper schedule

Higher Ed PAC

Office

Virtual performance checks

CxSlide28

Determine control: 1) OA damper position vs. 2) OA flow measurement (if available)

Check for rogue DCV zones

Check CO

2

sensor reading at unoccupied

Determine OA damper schedule

Recognize

that savings is from heating (gas)

- Economizer negates cooling savings

Verify economizer operation

Virtual performance checks

CxSlide29

Meet the operator on-site; discuss system operation

Validate measured points:

Temperatures: SA, MA, RA, OA (brief traverse)

Valve positions (visual, temp)

OA damper position (visual)

Supply fan speed (VFD)

Spot checks

CxSlide30

CO

2

sensors

Calibrate or replace

Auto calibration valid?

Sensors

CxSlide31

Recalculate setpoint per Standard 62.1

Check location

of sensor

Areas not being

sensed?

Leave

CO

2

logger

behind

Sensors

CxSlide32

Test the AHU

Modify CO

2

reading or setpoint

False full occupancy,

AND

False no occupancy

Determine response

Await steady-state if possible

Test individual VAVs; same method

System performance tests

CxSlide33

Test OA damper

Visually verify two positions

Check for leakage

Test occ. sensor impact on VAV box

BAS

System performance tests: other

CxSlide34

Correct deficiencies

found in tests

Optimize:

 OA upper / lower limit, CO

2

setpoint, OA schedule

Sequence Optimization

CxSlide35

Report any changes made

Add any needed

trending

Complete handover

missed at install

Document the

sequence

Plan for future

monitoring

Hand over to operators

CxSlide36

Program recommendationsSlide37

Opportunity #1

: New and retrofit DCV systems

Incentives per OA flow (see report)

Consider more detailed requirements

Dependent on heating fuel

Opportunity #2:

Recommissioning

Highly cost-effective for many programs

- Recommissioning,

retrocommissioning

, HVAC tune-up

Four opportunities

CxSlide38

SOURCE: http://blog.waterdamagedefense.com/wp-content/uploads/2011/01/hiring-a-contractor.jpg

Opportunity #3:

Ventilation re-design

Code changes

Excessive safety factors

Poor estimate of occupancy

Problem AFMS or dampers

OA damper schedule

Opportunity #4:

Trade allies

Awareness

Training

Four opportunities

CxSlide39

Sequences

Basic:

EDR 2007

Ventilation reset:

Trane 2005

With occupancy sensors:

Taylor 2014.

Demand control

ventilation for multiple zone VAV systems – problem solved

(from ASHRAE Annual Meeting, Seattle 2014; seminar available for a fee)

Code requirements

Code Notes 2012 IECC Demand Control Ventilation

AFMS:

Fisk 2009

CO

2

sensor performance:

Shrestha 2009

For more information

CxSlide40

Download the study

Find the full report, and a fact sheet: seventhwave.org/dcvContact me

shackel@seventhwave.org

608.210.7129

Learn about our work

seventhwave.org/buildings

Resources