J Botelho Direito ENCVPJ 29112012 FSTS Leak Rate Qualification Procedure Leak Rate Qualification Process 29112012 FSTS Leak Rate Qualification Procedure ID: 487953
Download Presentation The PPT/PDF document "FSTS Leak Rate Qualification Procedure" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.
Slide1
FSTS Leak Rate Qualification Procedure
J. Botelho DireitoEN/CV/PJ
29/11/2012 FSTS - Leak Rate Qualification Procedure Slide2
Leak Rate Qualification Process
29/11/2012 FSTS - Leak Rate Qualification Procedure Slide3
Maximum Leak Rate for the FSTS
He Leak Rate [
mbar.l
/s]
(inlet pressure of 0.1 mbar)
Number of connections
(or locations to be tested)Maximum leak rate per connection Condenser3.47x10-3301.16x10-4Vapour line5.62x10-3301.87x10-4Liquid line3.22x10-42001.61x10-6Brine Circuit1.53x10-41001.53x10-6
29/11/2012 FSTS - Leak Rate Qualification Procedure Slide4
Validation Pressure Test
29/11/2012 FSTS - Leak Rate Qualification Procedure
Thermosyphon Circuit – Return Line
Thermosyphon Circuit – CondenserSlide5
Validation Pressure Test
29/11/2012 FSTS - Leak Rate Qualification Procedure
Thermosyphon Circuit – Liquid Line
Brine Circuit