800 5824524 salesxpcccom wwwxpcccom E90 Technical Presentation XPC E90 Technical Training Agenda Product Overview Options Design and Operation Installation Front Panel System Operation ID: 790705

press e90 display key e90 press key display enter battery setting scroll amp panel lcd front parallel boa ups

Share:

Link:

Embed:

Download Presentation from below link

Download The PPT/PDF document "230 Yuma Street Denver, CO 80223" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

Slide1

230 Yuma Street

Denver, CO 80223

(800) 582-4524

sales@xpcc.com

www.xpcc.com

E90 Technical Presentation

Slide2

XPC

E90 Technical Training Agenda

Product Overview

Options

Design and Operation

InstallationFront Panel

System OperationTroubleshooting

Slide3

E90 Product Overview

208/120V Three-Phase UPS

Product snapshot

10kVA/10kW, 15/15kW, 20kVA/20kW, 208/120V 3Ph Tower UPS

Unity power factor

Compact footprint

UL,

cUL, RoHS, FCC A

2 year electronics, 2 year battery warranty (USA and Canada)

Slide4

E90 Product Overview

Features

Internal Maintenance bypass—manually transfer critical loads from UPS power to utility power

Communication— USB, RS485, RS232, Dry Contacts + 2 communication slots for Web/SNMP, Relay/Dry Contact, Modbus

Charging current—1A to 20A, adjustable from LCD display

0, I, 2, or 3 Internal Battery Strings

Extended battery packs— optional matching battery cabinets available for extended runtimes

Dual or Single Input. Single input jumpers come pre-installed

Parallel up to 4 modules for capacity or redundancyUp to 80kVA Full Capacity

Up to 60kVA N+1 RedundantField Replaceable Electronics Module

Slide5

E90 Product Overview

Extended Runtimes

Slide6

E90 Options

Internal and External Battery Options

0, 1,2,or 3 Strings Internal

63A

External

Battery Pack (10kVA)

125A External Battery Pack (

15/20kVA)

Connectivity OptionsSNMP-1P3PIN – one port card

SNMP-2P3PIN – 2 port cardRelay-STND – Relay CardService Options

5 x 8 Startup with 1, 2, or 3 Year On-Site Warranty7 x 24 Startup with 1, 2, or

5 Year On-Site WarrantyOne Year Extended Warranty

7 x 24 Preventative Maintenance 

Slide7

E90 Design and Operation

Specifications

Slide8

E90 Design and Operation

E90 One-Line

Slide9

E90 Design and Operation

E90 Internal – Left Side

Electronics Module

String #1 -

String #1 +

External DC Connector

External DC Fuses

DC Center-tap

Slide10

E90 Design and Operation

E90 Internal – Right Side

String #2 -

String #2 +

String #3 -

String #3 +

DC Center-tap

DC + Fuses

DC - Fuses

Slide11

E90 Design and Operation

E90 Rear

2 x Battery Temp RS485 Ports

Option Contact Port

USB Port

2 x Intelligent Slots

Cold Start Power Switch

Serial Port

Output Breaker

Maintenance Bypass Breaker

Mains Input Breaker

Bypass Input Breaker

AC Connection Terminal

Parallel Comm. Ports

Local EPO

REPO

External Battery Connector

Slide12

E90

Installation

Thermo-magnetic circuit-breaker

IEC 60947-2 trip curve D (normal)

Sized for 125% of the current as listed below. 10Kva: 40A Input Circuit Breaker required. *

15Kva: 60A Input Circuit Breaker required. 20Kva: 80A Input Circuit Breaker required. * If the battery charger current is to be programmed to 15A or higher,

increase the 10kVA input circuit breaker to 45A WiringWiring shall be in accordance with local

and national electrical codes. Recommended cabling sizing:

Slide13

E90

Installation

AC Connection Terminal

Slide14

E90

Installation

External Battery Connection

Up to 4 x XPC EBP80 cabinetsCan use 3

rd party battery system

Slide15

E90

Front Panel

Alarm LED

Bypass LED

Battery LEDInverter LED

Scroll ButtonEnter Button

On Button

Buttons and LEDs

Slide16

E90

Front Panel

Time and Date

Working Mode

LCD Display - Main

Bypass Data

Input Data

Battery Data

Events and Faults

UPS Status

Display Items

ID Number

Slide17

E90

Front Panel

LCD Display - Data

Press

the scroll key for approximately 1 sec. to highlight Data.

The

Data page will display all three phases of input and output voltage, current, and frequency and output load

percentage

Slide18

E90

Front Panel

LCD Display - Data

While in the Data page, additional data pages to view will be shown on the right side of the screen.

Input: Press ENTER key for approximately 1 sec. The display will show all three phases of the Main voltage, current, and frequency and the Bypass voltage and

frequency.

Slide19

E90

Front Panel

LCD Display - Data

Output: Press the scroll key for approximately 1 sec. The display will show all three phases of the Output voltage, current, and

frequency.

Slide20

E90

Front Panel

LCD Display - Data

Battery: Press scroll key for approximately 1 sec. The display will show the Battery voltage, current, estimated battery runtime and battery capacity

.

Slide21

E90

Front Panel

LCD Display - Data

Load : Press the scroll key for approximately 1 sec. The display will show all three phases of the Load %, kW, and kVA

.

Slide22

E90

Front Panel

LCD Display - Data

Inside: Press the scroll key for approximately 1 sec. The display will show the internal V-BUS (DC bus voltage), T1/T2 (Temperature 1 and Temperature 2), V-

Inv

(Inverter Voltage), and F-Inv (Inverter Frequency) .

Slide23

E90

Front Panel

LCD Display - Info

Press

the scroll key for approximately 3 sec. to exit Data, and press the scroll key for approximately 1 sec. move to Info.

The display will show LCD, PFC, and INV software versions and power rating .

Slide24

E90

Front Panel

LCD Display – Setting-User

Press

the scroll key for approximately 1 sec. to move to the setting page, then press ENTER key to enter setting-user page.

Press the scroll key to change item, press ENTER key to enter item and press the scroll key to change value, press ENTER key confirm the setting.

Slide25

E90

Front Panel

LCD Display – Setting-Maintenance

Maintenance : Press

Scroll +

ENTER key to enter maintenance and display a password window.Press Scroll to change the number and press ENTER to select the value, the password is “1121”

Slide26

E90

Front Panel

LCD Display – Setting – Maintenance - System

Once the Maintenance password is entered, press the Enter key.

The

UPS goes into the Setting-System window.

Press the Enter key to enter item and confirm value, press the Scroll key to change the value.

Slide27

E90

Front Panel

LCD Display – Setting – Maintenance - System

1) Factory default setting for Working Mode is ECO. To disable ECO, reprogram Working Mode to Normal or Parallel.

2) Must be in static bypass to change

3) If not in static bypass, output will drop load 4) This is the MODBUS device address used for RS232 & RS485 communication ports. a. Press Scroll key to set the address. b. When battery temperature sensor is open, choose ID 1~10 & 13~15

c. If UPS is set for parallel mode and device address <= parallel quantity, device address = parallel ID d. Press “ON” to exit the device address setting and save the device address setting value and parallel ID setting. e. Note: Under single UPS mode, until this device address setting save and exit, single UPS setting is done. 5) OFF turns off the sensor switch, ON turns on the sensor switch and send query command to sensor with address 11 and 12 every second.

.

Slide28

E90

Front Panel

LCD Display – Setting – Maintenance - Bypass

Press the Scroll key to highlight Bypass and press the Enter key to enter the Setting-Bypass

window.

Press the Enter key to enter item and confirm value, press the Scroll key to change the value.

Slide29

E90

Front Panel

LCD Display – Setting – Maintenance - Battery

Press the Scroll key to highlight Battery and press the Enter key to enter the Setting-Battery

window.

Setting-Battery: press the Enter key to enter item and confirm value, press the Scroll key to change the value.

Slide30

E90

Front Panel

LCD Display – Setting – Maintenance - Battery

1. Number is the number of batteries per string

2. Capacity is the Amp-Hour rating of the batteries per string

3. Group is the number of strings of batteries 4. I-Maxcharge is the maximum charger current. Setting this above 15A on the E90-10kVA

increases the input current rating and requires an input circuit for 45A .

Slide31

E90

Front Panel

LCD Display – Setting – Maintenance - Parallel

Press the Scroll key to highlight Parallel and press the Enter key to enter the Setting-Parallel

window.

Press the Enter key to enter item and confirm value, press the Scroll key to change the value.

Slide32

E90

Front Panel

LCD Display – Setting – Maintenance - Parallel

1. ID - Program each UPS in Parallel with a unique ID

2. Number - Program the total number of UPS systems in parallel. Maximum of 4 in parallel.

3. Redu. Num. – Program to the total number of UPS systems in parallel to be used for redundancy

Slide33

E90

Front Panel

LCD Display – Record

Displays

event records and fault records. Displays the Index (number in list), Time of event or fault, State (Mode) of UPS and event or

fault. Press the scroll key for approximately 1 sec. to move to the Record page

, then press ENTER key to enter.

Slide34

E90

Front Panel

LCD Display – Record

Press

the scroll key to select Up or Down or Delete. Press ENTER key to confirm.

If Delete is selected, all event or fault records will be deleted..

Slide35

E90 Troubleshooting

Troubleshooting begins by identifying the alarm

Slide36

E90

Troubleshooting

Slide37

E90

Troubleshooting

Slide38

E90

Troubleshooting

 

L

CD displ

ayfault code

  UPS alarm

  

Buzz  

LEDThe board may be damaged(1 shows the max.Probabilit

y, 2 shows the less probability)

12

31

Rectifier fault

long beep

F

ault ON

P

F

C p

o

w

er boa

r

d

P

F

C induc

t

or boa

r

d

c

o

n

t

r

ol

d

e

t

ec- tion

boa

r

d

2

I

n

v

.

f

ault(include I

n

v

.

Brid

g

e arm )

long beep

F

ault ON

INV p

o

w

er

boa

r

d

INV induc

t

or

boa

r

d

c

o

n

t

r

ol

d

e

t

ec- tion

boa

r

d

3

I

n

v

.

SCR short

long beep

F

ault ON

INV induc

t

or

boa

r

d

c

o

n

t

r

ol

d

e

t

ec- tion

boa

r

d

 

4

I

n

v

.

SCR b

r

eak

long beep

F

ault ON

INV induc

t

or

boa

r

d

c

o

n

t

r

ol

d

e

t

ec- tion

boa

r

d

 

5

B

ypass SCR short

long beep

F

ault ON

P

F

C induc

t

or boa

r

d

c

o

n

t

r

ol

d

e

t

ec- tion

boa

r

d

 

6

B

ypass SCR

b

r

eak

long beep

F

ault ON

P

F

C induc

t

or boa

r

d

c

o

n

t

r

ol

d

e

t

ec- tion

boa

r

d

 

7

Fuse b

r

o

k

en

long beep

F

ault ON

INV induc

t

or

boa

r

d

 

 8Paralle Relayfaultlong beepFault ONcontrol detec- tion board  9Fan faultlong beepFault ONfanINV powerboard 10Reservelong beepFault ON   11Auxiliary powerfaultlong beepFault ONINV powerboardcontrol detec- tion board 

Service Manual contains Table based on fault code and lists most probable cause

Slide39

E90

Troubleshooting

Service Manual contains Appendix A: UPS Fault Judgement

 

No.

 

UPS

Alarm

Software judgment Buzz

 LED

Condition 1Condition 2

Condition 3Condition 4

 

1

 

R

ectifier

f

ault

DC BUS

o

v

e

r

-

v

ol

t

a

g

e

DC

BUS

unde

r

-

v

ol

t

a

g

e

La

r

g

e bus dif

f

e

r

ence

 

long

beep

F

ault

ON

 

 

2

 

I

n

v

.

f

ault(include I

n

v

. Brid

g

e arm )

 

The a

b

solu

t

e

v

alue of the output

v

ol

t

a

g

e >112.5% of

r

at

ed output

v

ol

t

a

g

e, la

s

t 500ms

Brid

g

e arm midpoi

n

t

v

ol

t

a

g

e( I

n

v

.

v

ol

t

a

g

e)

la

s

t 500ms >1.1 time

of

r

a

t

-

ed

peak

v

alue

360

v

f

or230 344

f

or220

376

f

or240

 

long

beep

 

F

ault

ON

 

3

 

I

n

v

. SCR short

 

long

beep

F

ault

ON

 

4

 

I

n

v

. SCR b

r

eak

(in pa

r

allel, X phase load

r

at

e<6.3%) &&(pa

r

allel X phase

t

o

t

al load

r

at

e>50%) &&(la

r

g

e loop cur

r

e

n

t||in

b

ypass mode) la

s

t time

2S

long

beep

F

ault

ON

5

B

ypass SCR

short

(X phase Output

v

ol

t

a

g

e>60% of

r

at

ed) &&(the a

b

solu

t

e

v

alues of other phases

v

ol

t

a

g

e<5% of

r

at

ed voltage) last 2slongbeepFaultON6Bypass SCRbreak((in parallel, X phase load rate <6.3%) &&(parallel X phase total load rate<50%) &&(large loop current|| in Bypass mode) ) ||(X phase cur- rent>10% of rated&&X phase Output voltage>50% of the Bypass voltage) last 2SlongbeepFaultON7Fuse brokenHardware signal low availablelongbeepFaultON8Parallel Relayfault( Inv. status&&Relay open) ||(no Inv. Status && parallel Relay close) last20mslongbeepFaultON9

Fan faultHardware signal low available f

or 5s

 

 

 

long

beep

F

ault

ON

Slide40

The end, questions?

Xtreme Power Conversion

230 Yuma Street

Denver, CO 80223800.582.4524

Sales & Customer Support

1-800-582-4524 ext 1sales@xpcc.comTechnical Support & Service

1-800-582-4524 ext 2support@xpcc.com

service@xpcc.comMarketing

marketing@xpcc.com