Download The PPT/PDF document "L4 RF system Status and interlock logi..." is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.
Slide1
L4 RF systemStatus and interlock logic
RF CIBUs connections
PLC Implementation
PLC LOGIC
Actual status
Future
Slide2RF CIBU connections
RFQ CIBU
ALL RF CIBU
PLC INTERFACE
AND
ACCESS RELAY MATRIX
RFQ INTERLOCKS
DTL 1..3 INTERLOCKS
CCDTL 1..7
INTERLOCKS
PIMS 1..12 INTERLOCKS
BUNCHER 1..3
INTERLOCKS
1
3
7
6
3
In AYSRV1 rack
In each Klystron rack
PASS
Considered as EIS machine
Slide3PLC Implementation
Any INTERLOCKS
Module 0 out
Module 1 out
BIC 1
out relay
BIC 2
out relay
Any
CIBU
Software inhibit
From all other systems
From all other systems
PLC Logic
Digital
OUT
Digital
IN
Digital
OUT
Digital
IN
Slide4OR
function for each system up to 19
AND
function for each CIBU channel
PLC LOGIC
Slide5Actual status
Both CIBU links have been tested and electrically validated by BIC Expert (Ch. Martin)
RFQ CIBU is connected and activated
ALL RF CIBU is connected and activated for
DTL1,2,3 only on request of D.NISBET
The PLC has no interface to any control applications it is only modified by RF experts on demand
Slide6FutureA local and / or remote control/monitoring application will be available
Not yet decided but could include:
Possibility to set / reset the CIBU Software inhibit (
Local only by RF experts
)Status of the CIBU connections (available for operation)Status of the PASS connections (available for operation)