Duct casings for particulate filters DCA Duct casings for particulate filters DCA

Duct casings for particulate filters DCA - PowerPoint Presentation

marina-yarberry
marina-yarberry . @marina-yarberry
Follow
384 views
Uploaded On 2017-09-27

Duct casings for particulate filters DCA - PPT Presentation

1 Side service door for easy filter change For the fitting of Mini Pleat filters or activated carbon filter cells Clamping ID: 591207

filters duct filter frame duct filters frame filter dca side casing connecting casings particulate system clamping flanges mechanism fitting

Share:

Link:

Embed:

Download Presentation from below link

Download Presentation The PPT/PDF document "Duct casings for particulate filters DCA" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

Slide1

Duct casings for particulate filters DCA

1

Side

service door for easy filter change For the fitting of Mini Pleat filters or activated carbon filter cells• Clamping mechanism for secure sealing and air-tight fitting of the filter element• Quick installation: Casing frame can be used as connecting frame

Upstream

side

Downstream

sideSlide2

Duct casings for particulate filters DCA

2

The duct casing can be installed into

the duct using the casing frame as a connecting frame. Possible connecting flanges up to 40 mm on the upstream side and on the downstream side Common flange sizes on site are 30 mm The screws must be set at 15 mm from the bottom of the casing (mid of 30 mm flanges) The casing must be sealed on the

perimeter connecting flanges

when installed into the

duct system

AirflowSlide3

Duct casings for particulate filters DCA

3

Frame

system inside of the DCA with filtersSlide4

Duct casings for particulate filters DCA

4

The Mini Pleat Filter

of the dimension 610x610x292 mm has to be placed on the support brackets Please consider that the flat section seal of the filter must be pressed against the frame system The clamping mechanism is used for the airtight fitting of the filter

Support

brackets

for filter

element

Frame

system

inside

of

the

DCA

with

filters

Clamping

mechanism