Download Presentation The PPT/PDF document "PEC Three Deck Multizone" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.
1. PEC Three Deck Multizone
2. Walking Up to the Unit
3. Looking Left
4. HOT DECKCOLD DECKBYPAS DECKReturn AirTypical Zone SupplySupply FanFiltersCooling CoilHeating CoilZone damper linkage system arranged so that as the actuator strokes, the damper blades modulate from:Full hot deck, no bypass, no cold deck* to;Full bypass deck no cold deck, not hot deck to;Full cold deck, no bypass, no hot deck* This means as the hot deck damper starts to close, the bypass damper starts to open. This continues until the dampers are positioned with the hot deck fully closed and the bypass fully open. Meanwhile, nothing happens with the cold deck damperZone Damper
5. Of Course, Linkage is Not an Issue with Modern Actuators and DDC Control3/8/20115HmmmmmCenterline Drive applies torque directly to the shaft
6. Of Course, Linkage is Not an Issue with Modern Actuators and DDC ControlMinimal complexity; Only 3-4 crank arms, three shafts, 2 - 4 ball joints and a spring per zone3/8/20116Module Title Here
7. 3/8/20117Cold DeckNeutral DeckHot Deck