Analysis of System Analysis of System

Analysis of System - PDF document

helene
helene . @helene
Follow
348 views
Uploaded On 2021-09-26

Analysis of System - PPT Presentation

Protection MisoperationsDecember 2015NERC Analysis of System Protection MisoperationsDecember 2015iTable of ContentsPrefaceiiExecutive Summary1Introduction2Chapter 1 Misoperation Data Analysis4Misope ID: 886207

misoperation misoperations analysis system misoperations misoperation system analysis relay protection nerc failures rate 2014 design 2013 logic setting errors

Share:

Link:

Embed:

Download Presentation from below link

Download Pdf The PPT/PDF document "Analysis of System" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

1 Analysis of System Protection Misopera
Analysis of System Protection Misoperations December 2015 NERC | Analysis of System Protection Misoperations | December 2015 i Table of Contents Preface ................................ ................................ ................................ ................................ ................................ ........ ii Executive Summary ................................ ................................ ................................ ................................ .................... 1 Introduction ................................ ................................ ................................ ................................ ................................ 2 Chapter 1 – Misoperation Data Analysis ................................ ................................ ................................ .................... 4 Misoperation Data Reported ................................ ................................ ................................ ................................ .. 4 Misoperation Data Reported by Relay Technology ................................ ................................ ................................ 6 Chapter 2 – Misoperations Data by Regional Entity ................................ ................................ ................................ .. 8 FRCC Misoperation Analysis ................................ ................................ ................................ ................................ 9 MRO Misoperation Analysis ................................ ................................ ................................ ................................ 9 NPCC Misoperation Analysis ................................ ................................ ................................ ............................ 10 RF Misoperation Analysis ................................ ................................ .

2 ............................... ........
............................... ................................ . 11 SERC Misoperation Analysis ................................ ................................ ................................ ............................. 11 SPP RE Misoperation Analysis ................................ ................................ ................................ .......................... 12 T exas RE Misoperation Analysis ................................ ................................ ................................ ....................... 13 WECC Misoperation Analysis ................................ ................................ ................................ ........................... 13 Chapter 3 – Recommended Actions ................................ ................................ ................................ ........................ 14 Incorrect setting/logic/design errors ................................ ................................ ................................ ............... 14 Communication failures ................................ ................................ ................................ ................................ ... 14 Relay failures/malfunctions ................................ ................................ ................................ ............................. 14 Overall activities ................................ ................................ ................................ ................................ ............... 15 NERC | Analysis of System Protection Misoperations | December 2015 ii Preface The North American Electric Reliability Corporation (NERC) is a no t - fo r - profit international regulatory authority whose mission is to ensure the reliability of the bulk p ower s ystem (BPS) in North America. NERC develops and enforces R eliability S t

3 andards; annually assesses seasonal and
andards; annually assesses seasonal and long‐term reliability; monitors the BPS through system awareness; and educates, trains , and certifies industry personnel. NERC’s area of responsibility spans the continental United States, Canada , and the northern portion of Baja California, Mexico. NERC is the ele ctric reliability organization (ERO) for North America, subject to oversight by the Federal Energy Regulatory Commission (FERC) and governmental authorities in Canada. NERC’s jurisdiction includes u sers, owners , and operators of the BPS , which serves more than 334 million people . The North American BPS is divided into several assessment areas within the eight Regional Entity (RE) boundaries, as shown in the map and corresponding table below. FRCC Florida Reliability Coordinating Council MRO Midwest Reliability Organization NPCC Northeast Power Coordinating Council RF Reliability First SERC SERC Reliability Corporation SPP RE Southwest Power Pool Regional Entity T exas RE Texas Reliability Entity WECC Western Electric ity Coordinating Council NERC | Analysis of System Protection Misoperations | December 2015 1 Executive Summary The State of Reliability 201 5 report found that p rotection system misoperations continued to be a significant contributor to automatic transmission outage severity . 1 In general , transmission system events with protection system misoperations were more impactful than other transmission events . They were also a significant contributor to transmission outage severity, indicating that a reduction in protection system misoperations would lead to an improv ement in system reliability. This report focuses on analysis of the top three protection system misoperation cause codes reported to the Regions and NERC in accordance with Reliabili

4 ty Standard PRC - 004 - 2.1a to identify
ty Standard PRC - 004 - 2.1a to identify regional trends and provide guidance to protection system owners that experience a high number of misoperations. Across NERC , i ncorrect sett ing/logic/design errors accounted for 31% of all misoperations, followed by relay failures/malfunctions at 19%, and then communication failures at 13% . Microprocessor relays with incorrect setting/logic/design errors accounted for more than 20% of all misoperations in 2013 and 2014. This further supports the idea that setting/logic/design controls for microprocessor relays should be focused on . Regional analysis indicate s that from 2013 to 2014 , SPP RE showed a statistically significant decrease in the misoperation rate (misoperations as a percentage of total operations) from 14.2% to 10.9% as did NPCC from 8.2% to 6.8%. RF showed a statistically significant increase in the misoperation rate from 11.4% to 13.5%. The misoperation rate could not be calculated for WECC since that Region did not report total operations for those years. Specific NERC, RE, and industry actions are identified in this re port to help achieve NERC’s goal to reduce the rate of misopera tions due to these causes by 25% by the end of 2017. 1 http://www.nerc.com/pa/RAPA/PA/Performance%20Analysis%20DL/2015%20State%20of%20Reliability.pdf . NERC | Analysis of System Protection Misoperations | December 2015 2 Introduction T he State of Reliability 201 5 2 report noted a linkage between reported misoperations and transmission - related events and that a misoperation outage cause code is positively correlated with transmission severity 3 when outages do occur. The following are additional findings from analyses of misoperations :  The top three cause codes assigned to mi soperations since the first ful

5 l year of data collection in 2012 are 1
l year of data collection in 2012 are 1) incorrect setting/logic/design error s ; 2) relay failures/malfunctions; and 3) communication failure s .  The total rate of misoperations across all R egions (excluding WECC), as a percentage of total operations during 2013 and 2014 , was approximately 10% .  The three most common causes of misoperations remain the same as last year . Over 60% of misoperations are caused by incorrect setting/logic/design errors, communicati on failures, and relay failures/malfunctions . T hree datasets are available to better understand the impact of misoperations on reliability. One dataset is comprised of the event reports that are submitted to the Regions and NERC through the e vent a nalysis program document 4 that was established by the Events Analysis Subcommittee (EAS). When misoperations are associated with reported system disturbances, NERC can then assess their actual impact on the BES and identify whether they were causal or contributor y to the event through cause coding. In 2014, there were 54 transmission - related system disturbances that resulted in a qualified event . Of those 54 events, 47 ( about 87 % ) had associated misoperations. Of the 47 events, 37 of them (79 % ) experienced misoperations that were contributory to or exacerbated the severity of the event. In several cases, multiple misoperations occurred during a single disturbance. In 2013, there were 71 transmission - related system disturbances that resulted in a qualified event reported via the NERC e vent a nalysis process . Of those 71 events, 47 (about 66 % ) had associated misoperations. Of these 47 events, 38 (about 81 % ) exper ienced misoperations that were contributory to or exacerbated the severity of the event. In several cases, multiple misoperations occurred during a single disturbance. A second source of misop

6 erations r eporting occurs through TADS
erations r eporting occurs through TADS data collection. Misoper ations that were identified as being caused by human error or rela y failure are identified in TADS reporting. This occurs for transmission facilities operated at 200 kV and above. A third source of misoperations r eporting is via a database of all misoperations that occur on the BES (100 kV and above) that is collected on a quarterly basis by the Regions and NERC through compliance with Reliability Standard PRC - 004 - 2.1a . This database provides a comprehensive set of data for all tra nsmission and generation misoperations. It is submitted by the system protection owners and includes detailed information about the misoperation, including a description of the misoperation, its category, its causes, and the proposed corrective action and completion date. This report focuses on analysis of the database of all protection system misoperations that occur on the BES (100 kV and above) that is collected on a quarterly basis by the Regions and NERC through compliance with Reliability 2 http://www.nerc.com/pa/RAPA/PA/Performance Analysis DL/2014_SOR_ Final.pdf . 3 The severity of a transmission outage is calculated based on its assumed contribution of power flow through transmission circ uits. A description of the calculation is provided in Appendix A of the State of Reliability 201 5 report. 4 http://www.nerc.com/pa/rrm/ea/EA Program Document Library/Final_ERO_EA_Process_V2.pdf . I ntroduction NERC | Analysis of System Protection Misoperations | November 2015 3 Standard PRC - 004 - 2.1a . Specifically, analysis was performed on the top three cause codes to identify regional trends and provide guidance to protection system owners that experience a high number of misoperations with the desired outcome o

7 f lowering the overall rat e of misopera
f lowering the overall rat e of misoperations throughout North America. This report documents the analysis that NERC staff performed on protection s ystem m isoperations and provides recommended action s that NERC and industry can take to reduce protection system misoperations and the ir impact on reliability. NERC | Analysis of System Protection Misoperations | December 2015 4 Chapter 1 – Misoperation Data Analysis Misoperation Data Reported Figure 1 shows the misoperation rate by Region as reported in compliance with Reliability Standard PRC - 004 - 2.1a . The misoperation rate reflects the ratio of misoperations to total operations for the entire BES , 100 kV and above. This ratio provides a stable way to tre nd the rate of misoperations, as opposed to a count of misoperations that can be influenced by weat her and other factors. T otal protection system operations was first requested with the fourth quarter 2012 misoperation data. Having the total number of operations for the reporting periods in 2013 allow s for a consistent way to normalize and trend protect ion system misoperations over time. Information for WECC is not provided because WECC does not report the total number of operations. Testing the hypotheses on the population proportion revealed three statistically significant changes in the misoperation rate between 2013 and 2014: an increase for the RF misoperation rate and a decrease for the SPP RE and NCPP misoperation rate s . The decrease of misoperations in SPP RE may be partially due to SPP RE ’s outreach efforts to increase the reporting of successful protection system operations. SPP RE established a goal of a 92% successful operations rate and has made this goal part of the SPP RE staff’s performance matrix. SPP RE has presented its misoperation analysis, findings, and conclusions i

8 n workshops, SPP RE Trustee meeting
n workshops, SPP RE Trustee meetings, and the monthly newsletter. SPP RE participates in the System Protection and Control Working Group (SPCWG), which completed a white paper on its analysis of RE relay misoperations caused by communication failures , the p rimary root cause of misoperations in SPP RE . The SPCWG is working on an additional white paper on misoperations 5 caused by incorrect setting/logic/design errors , which is the second - highest root cause of SPP RE misoperations. Figure 1 : Year - o ver - year changes in misoperation rate by Region and NERC (2013 versus 2014) 5 http://www.spp.org/section.asp?group=129&pageID=27 14.2% 12.9% 11.4% 11.4% 9.2% 8.2% 7.7% 10.9% 10.9% 13.5% 11.5% 8.4% 6.8% 8.9% 10.1% 9.8% 0.0% 2.0% 4.0% 6.0% 8.0% 10.0% 12.0% 14.0% 16.0% SPP FRCC RF MRO SERC NPCC TRE 2013 2014 NERC 2013 NERC 2014 Chapter 1 – Misoperation Data Analysis NERC | Analysis of System Protection Misoperations | November 2015 5 Figure 2 shows misoperations by month from January 1 , 201 2 , to March 31 , 201 5 . Overall, the trend is periodic, with peaks in the spring and summer months of all three years . Figure 2: Misoperations by month ( 2012 - 2014 ) Figure 3 illustrates the top - three misoperations cause codes assigned by the Transmission Owners (TOs) : incorrect setting / logic / design error s ; relay failures/malfunctions; and communication failure s . These three causes h ave consistently accounted for over 60 % of all misoperations from 2012 to 2014 . Figure 3 : Misoperations by cause code from 2013 - 2014 Table 1 : Misoperation Cause(s) by Year Cause Codes 2012 2013 2014 Grand Total Incorrect setting/logic/design errors 32% 31% 32% 31% Relay failures/malfunctions 20% 18% 19% 19% Communication fa

9 ilures 13% 14% 12% 13% Unknown
ilures 13% 14% 12% 13% Unknown/unexplainable 11% 13% 10% 11% AC System 9% 7% 10% 9% As - left personnel error 8% 8% 8% 8% DC system 6% 5% 5% 5% Other/explainable 2% 5% 4% 4% 0 50 100 150 200 250 300 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec 2012 2013 2014 0 50 100 150 200 250 300 Jan-12 Apr-12 Jul-12 Oct-12 Jan-13 Apr-13 Jul-13 Oct-13 Jan-14 Apr-14 Jul-14 Oct-14 31% 18% 13% 11% 9% 8% 5% 5% Incorrect setting/logic/design errors Relay failures/malfunctions Communication failures Unknown/unexplainable AC System As-left personnel error DC system Other/explainable Chapter 1 – Misoperation Data Analysis NERC | Analysis of System Protection Misoperations | November 2015 6 Miso peration Data Reported by Relay Technology The misoperation data for 2013 and 2014 was analyzed by the type of protection system relay technology used: e le ctromechanical, microprocessor, and solid state. Figure 4 shows that microprocessor relays with incorrect setting/logic/design errors accounted for over 20% of all misoperations in 2013 and 2014 combined . Figure 4 : Total misoperations by relay technology 2013 - 2014 Statistical analysis was performed on the changes from 2013 to 2014 for the three largest cause codes of communication failures, relay failure s /malfunction s , and incorrect setting/logic/design errors. While there were slight ch anges in all three , only the change in communication failures from 1.6% to 1.3% proved statistically significant . This is noted by the green arrow. F or the seven R egions combined, NERC had a statistically significant decrease in the misoperation rate for misoperations caused by c ommunication failures and nonsignificant increases in the misoperation rate for the other two causes in the top three as shown in Figure 5 . For the t op three causes combined, the misope

10 ration rate was unchanged (5.9% in
ration rate was unchanged (5.9% in 2013 and 20 14). Figure 5 : Misoperations rate by top three causes 2013 - 2014 2.6% 20.8% 1.1% 7.6% 7.9% 3.2% 0.0% 5.0% 10.0% 15.0% 20.0% 25.0% Electromechanical Micro Processor Solid State Incorrect setting/logic/design errors Relay failures/malfunctions 1.6% 1.8% 2.5% 5.9% 1.3% 2.0% 2.6% 5.9% 0.0% 1.0% 2.0% 3.0% 4.0% 5.0% 6.0% 7.0% Communication failures Relay failures/malfunctions Incorrect setting/logic/design errors Top 3 combined 2013 2014 Chapter 1 – Misoperation Data Analysis NERC | Analysis of System Protection Misoperations | November 2015 7 Figure 6 shows the percentages of the total number of misoperations for the three largest categories of misoperation cause codes by voltage class. Misoperations due to incorrect setting/logic/design errors occurred more often at the 115kV, 138kV, and 230kV levels , with communication failures occurring more often at the 138kV voltage level. The data is not normalized. Figure 6 : 2013 - 2014 misoperations by voltage class 0.00% 1.00% 2.00% 3.00% 4.00% 5.00% 6.00% 7.00% 8.00% 100 kV 100 kV 115 kV 120 kV 138 kV 161 kV 230 kV 345 kV 500 kV 735 kV 765 kV Communication failures Relay failures/malfunctions Incorrect setting/logic/design errors NERC | Analysis of System Protection Misoperations | December 2015 8 Chapter 2 – Misoperations Data by Regional Entity The reported mis operation data aggregated by the REs is provided in Figure 7 . As before, the analysis is focused on the three largest misoperation cause codes (communication failure s, relay failures/malfunctions , and i ncorrect sett ing/logic/design errors) . Misoperations are presented as a percent of total operations in each Region . Misoperations caused by incorrect setting/logic/design errors were the largest contributor to the misop eration rate in five of the seven Regions . Information

11 for WECC is not provided in this graph
for WECC is not provided in this graph because WECC does not report the total number of operations. This further supports the idea that setting/logic/design controls for microprocessor relays should be focused on . Figure 7 : Misoperations rate by Regional Entity The following sections provide protection system misoperation analysis for each NERC Regional Entity. No individual reporting entity within any R egion is identified in this report. 1.1% 1.7% 0.8% 1.9% 1.2% 3.2% 0.8% 2.5% 3.5% 1.8% 2.6% 2.2% 2.9% 3.3% 3.4% 2.1% 1.2% 2.4% 1.9% 2.0% 1.6% 0% 1% 2% 3% 4% FRCC MRO NPCC RF SERC SPP TRE Communication failures Incorrect setting/logic/design errors Relay failures/malfunctions Chapter 2 – Misoperations Data by Regional Entity NERC | Analysis of System Protection Misoperations | November 2015 9 FRCC Misoperation Analysis FRCC had a statistically significant decrease in its misoperation rate for misoperations caused by c ommunication failures and a nonsignificant increase in its misoperation rate for the other two causes. For the t op three causes combined, FRCC had a decrease in its misoperation rate from 7.6% in 2013 t o 6.7% in 2014, which was not statistically significant. Figure 8 : FRCC misoperations r ate MRO Misoperation Analysis MRO did not have a statistically significant cha nge in its misoperation rate for any of the top three causes. For the t op three causes combined, MRO had a decrease in its misoperation rate from 7.6% in 2013 to 6.8% in 2014, which was not statistically significant. Figure 9 : MRO misoperations rate 1.8% 3.3% 2.5% 7.6% 0.5% 3.6% 2.6% 6.7% 0.0% 1.0% 2.0% 3.0% 4.0% 5.0% 6.0% 7.0% 8.0% Communication failures Relay failures/malfunctions Incorrect setting/logic/design errors Top 3 combined FRCC 2013 2014 1.6% 2.5% 3.6% 7.6% 1.8% 1.8% 3.3% 6.8% 0.0% 1.0% 2.0% 3.0% 4.0%

12 5.0% 6.0% 7.0% 8.0% Communication failu
5.0% 6.0% 7.0% 8.0% Communication failures Relay failures/malfunctions Incorrect setting/logic/design errors Top 3 combined MRO 2013 2014 Chapter 2 – Misoperations Data by Regional Entity NERC | Analysis of System Protection Misoperations | November 2015 10 NPCC Misoperation Analysis NPCC had a statistically significant increase in its misoperation rate from 0.9% to 1.6% for misoperations caused by r elay failures/malfunctions and a nonsignificant decrease in misoperation cause for the other two causes in the top three. For the top three causes combined, NPCC had an increase in its misoperation rate from 3.7% in 2013 to 3.9% in 2014, which was not statistically significant. Figure 10 : NPCC misoperations rate NPCC has developed a set of sub - cause codes for the top two cause codes assigned to misoperations, incorrect setting/logic/design errors and relay failures/malfunctions. These sub - cause codes will allow for better analysis of the microprocessor relay misop eration data and help to tackle the large percentage of microprocessor relay misoperations , as shown in Figure 4 of the report. NPCC has also provided a regional perspective on NERC lessons learned on protection system misoperations and developed its own l essons learned from review of regional misoperations , which are then fed into further refinement of the NPCC protection design criteria. NPCC requires a comprehensive set of protection design criteria (NPCC Directory No. 4) be applied to facilities on whi ch faults or disturbances can have significant adverse impact such as:  I nstability  U nacceptable system dynamic response , an oscillatory response to a contingency that is not demonstrated to be clearly positively damped within 30 seconds of the initiating event  U nacceptable equipment tripping  V oltage levels in violation of applicable

13 emergency limits  L oadings on
emergency limits  L oadings on transmission facilities in violation of applicable emergency limits The NPCC protection design criteria ensure that no single point of failure can disable the composite protection system for these facilitie s. New or modified protection designs for these facilities are also reviewed by the NPCC Task Force on System Protection for conformity with the criteria, which include commissioning testing, before they are placed in service. 0.8% 0.9% 2.0% 3.7% 0.7% 1.6% 1.6% 3.9% 0.0% 0.5% 1.0% 1.5% 2.0% 2.5% 3.0% 3.5% 4.0% 4.5% Communication failures Relay failures/malfunctions Incorrect setting/logic/design errors Top 3 combined NPCC 2013 2014 Chapter 2 – Misoperations Data by Regional Entity NERC | Analysis of System Protection Misoperations | November 2015 11 RF Misoperation Analysis RF did not have a statistically significant change in its misoperation rate for any of the top three cause code s. For the t op three causes combined, RF had an increase in its misoperation rate f rom 6.6% in 2013 to 7.3 % in 2014, which was not statistically significant. Figure 1 1 : RF misoperations rate In order to mitigate future protection system misoperations for these three top causes , RF conducted some outreach efforts to r egistered e ntities in 2015 , which included providing some education regarding technical aspects of misoperations . RF conducted a training session for communication technicians, field personnel, and relay engineers , and t he technical topics included power line carrier equipment and issues, protection work kits, and human performance aspects. RF also had a vendor provide training on polarization for microprocessor relays to its Protection Subcommittee. In addition, RF also conducted an internal controls evaluation (ICE) on one entity related only to misoperations.

14 In 2016, RF plans to conduct a short
In 2016, RF plans to conduct a short - circuit value comparison between TOs to verify the calculation of fault values in short - circuit models and to implement a peer review process for misoperation data . RF also plans to incorporate field personnel into its Protection Subcommittee membership. All of these efforts are intended to aid entities in their efforts to reduce protection system misoperations. 1.9% 2.2% 2.5% 6.6% 2.0% 2.5% 2.8% 7.3% 0.0% 1.0% 2.0% 3.0% 4.0% 5.0% 6.0% 7.0% 8.0% Communication failures Relay failures/malfunctions Incorrect setting/logic/design errors Top 3 combined RF 2013 2014 Chapter 2 – Misoperations Data by Regional Entity NERC | Analysis of System Protection Misoperations | November 2015 12 SERC Misoperation Analysis SERC did not have a statistically significant change in its misoperation rate for any of the top three cause code s. For the t op three causes combined, SERC had a decrease in its misoperation rate from 5.3% in 2013 to 5. 2% in 2014, which was not statistically significant. Figure 1 2 : SERC misoperations rate SPP RE Misoperation Analysis SPP RE had a statistically significant decrease, as noted by the green arrow, in its misoperation rate for misoperations caused by c ommunication failures from 3.9% to 2.4% and nonsignificant changes in its misoperation rate for the other two causes. For the t op three causes combined, SPP RE had a decrease in its misoperation rate from 8.7% in 2013 to 7.4% in 2014, which was not statistically significant. Figure 1 3 : SPP RE misoperations rate 1.3% 1.9% 2.1% 5.3% 1.1% 1.9% 2.2% 5.2% 0.0% 1.0% 2.0% 3.0% 4.0% 5.0% 6.0% Communication failures Relay failures/malfunctions Incorrect setting/logic/design errors Top 3 combined SERC 2013 2014 3.9% 2.1% 2.7% 8.7% 2.4% 1.8% 3.1% 7.4% 0.0% 1.0% 2.0% 3.0% 4.0% 5.0% 6.0% 7.0% 8.0% 9.0% 10.0% Comm

15 unication failures Relay failures/malfun
unication failures Relay failures/malfunctions Incorrect setting/logic/design errors Top 3 combined SPP 2013 2014 Chapter 2 – Misoperations Data by Regional Entity NERC | Analysis of System Protection Misoperations | November 2015 13 Texas RE Misoperation Analysis Texas RE did not have a statistically significant change in its misoperation rate for any of the top three cause code s. For the t op three causes combined, Texas RE had an increase in its misoperation rate from 5.7% in 2013 to 5. 8% in 2014, which was not statistically significant. Figure 1 4 : Texas RE misoperations rate WECC Misoperation Analysis The WECC Region does not collect total operation data, therefore its misoperation rate cannot be calculated. WECC reported a total of 306 and 321 misoperations for 2013 and 2014 respectively. WECC has assigned staff that are responsible for monitoring the m isoperation submittals to ensure the information is accurate and detailed before submitti ng to NERC. WECC has a s taff liaison for the Relay Work Group (RWG) who reviews all misoperations reports in closed session meetings to protect confidentiality of the information submitted by WECC e ntities . As part of their review, the RWG develops general observations from the d ata by class as well as document specific conclusions and recommendations. Additionally, the RWG has a small subgroup that reviews event reports associated with protection system operations , and from these reviews, they develop an annual report with conclu sions and recommendations. 1.0% 1.6% 3.2% 5.7% 0.7% 1.6% 3.4% 5.8% 0.0% 1.0% 2.0% 3.0% 4.0% 5.0% 6.0% 7.0% Communication failures Relay failures/malfunctions Incorrect setting/logic/design errors Top 3 combined Texas RE 2013 2014 NERC | Analysis of System Protection Misoperations | December 2015 14 Chapter 3 – Recommended Actions

16 The 2014 State of Reliability report n
The 2014 State of Reliability report noted that communication failures, relay failures/malfunctions, and incorrect setting/logic/design errors were the top three causes of relay misoperations. After evaluating the data, incorrect setting/logic/design errors is clearly a priority area for NERC to concentrate its efforts, followed by communication errors and relay failures on electromechanical relays. Below are specific suggestions and quantifiable efforts that address the specific areas to reduce relay misoperation failu re rates . The go al is to reduce misoperations due to these three causes by 25% by yearend 2017 . That would equate to reducing annual misoperations by approximately 325, reducing the overall misoperation rate from 1 0% to 8% . Incorrect setting/log ic/design errors The NERC Protection System Misoperations Task Force issued a report in 2013 6 which identified that m isoperations due to incorrect setting/logic/design errors can be reduced by: 1) peer reviews, 2) increased training , 3) more extensive fau lt studies , 4) standard templates for setting standard schemes using complex relays , and 5) periodic review of existing settings when system topography is changed . Peer review consists of verifying that the relay settings meet the specifications of the r elay and control application. When new relays are installed or major changes are made on existing relay schemes, a peer review by a person that has equal or greater experience should be performed to verify that the relay settings meet the specifications of the relay and control application. Increased training will also reduce the calculation and application errors that lead to relay misoperations. The IEEE Power System Relaying Subcommittee ( IEEE PSRC ) published a working - group report to provide additional technical guidance for quality control of protective relay settings

17 . 7 Events Analysis has discovered t
. 7 Events Analysis has discovered that i ncorrect ground instantaneous overcurrent settings on the 115 - 230kV systems are a leading cause of relay misoperations that lead to a NERC - qualified event. NERC is in the process of working with relay vendors and industry participants to create a white paper with some suggestions for both commissioning and testing to uncover limitations in current applications. Communication failures The design of a protection system involves balancing both dependability and security. Dependability relates to the degree that a relay or relay system will operate correctly , as in causing trips when desired. Security is the degree that a relay or relay system will not operate incorrectly , as in causing a false trip. Recent discussions with engineers from Schweitzer Engineering Laboratories (SEL) has revealed that the design of power line carriers that use directional comparison blocking has caused relays to trip at inap propriate times due to holes in the communication channel . 8 Studies from SEL have shown that a directional comparison unblocking scheme provides better security , reduc ing misoperations. This analysis agrees with the work of the Protection System Misopera tions Task Force . Relay failures/malfunctions There are known problems with drift in electromechanical relays, which can be effectively addressed by the following actions:  Reduce maintenance intervals on electromechanical relays with known issues (e.g. , KD relays) .  Replace these electromechanical relays with microprocessor - based relays . 6 http://www.nerc.com/comm/PC/Protection System Misoperations Task Force PSMTF 2/PSMTF_Report.pdf . 7 “Processes, Issues, Trends and Quality Control of Relay Settings,” Working Group C3 of Power System Relaying Committee of IEE

18 E Power Engineering Society, March 2007
E Power Engineering Society, March 2007. 8 Investigation and Analysis into the Misoperation due to Carrier Holes, John J. Meinardi, Florida Power & Light Co., and Miriam P. Sanders, PE – AMETEK Power Instruments, Copyright 2008. Chapter 3 – Recommended Actions NERC | Analysis of System Protection Misoperations | November 2015 15 Additionally, some microprocessor - based relays are nearing their projected end - of - life and are experiencing increased failures. Actively engaging manufactures in propose d solutions will be essential in the foreseeable future. Overall activities NERC is continuing activity on several projects to address protection system misoperations. The Reliability Issues Steering Committee (RISC) has identified system protection issues as one of the top - priority risks to reliability. NERC has focused its Reliability Standards efforts in this area with the completion of the relay loadability standards and the revised relay misoperation standard. NERC continues its efforts to develo p a relay coordination standard . NERC Event Analysis continues to examine system events to identify those that are impacted by protection system misoperations to determine if action is needed to address trends and common modes of misoperations. While the Protection System Misoperations Task Force spent considerable effort developing a report on their investigation, the results have not been actively communicated to industry. This vital information addresses many additional components of relay misoperations . In addition, NERC has historically published regional misoperations rates with no discussion of comparisons or solutions. Since the Regions have industry experts in committees that regularly discuss relay operations and can implement recommendations, NER C should engage those regional committees in developing potential actions to reduce misop