PAVIRO  EOL module cable PAVIRO  EOL module cable

PAVIRO EOL module cable - PowerPoint Presentation

luanne-stotts
luanne-stotts . @luanne-stotts
Follow
376 views
Uploaded On 2018-03-20

PAVIRO EOL module cable - PPT Presentation

capacitance check V17 This information can be used as capacitance check to see if EOLs work correct Explanation Each loudspeaker cable has a certain capacitance The longer the cable the higher the capacitance ID: 658420

capacitance cable total check cable capacitance check total length loudspeaker eol connected lines module area green router rights calculate

Share:

Link:

Embed:

Download Presentation from below link

Download Presentation The PPT/PDF document "PAVIRO EOL module cable" is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

Slide1

PAVIRO

EOL module cable

capacitance

check V1.7Slide2

This information can be used as capacitance check to see if EOL’s work correct.

Explanation:

Each loudspeaker cable has a certain capacitance. The longer the cable, the higher the capacitance.

1-n topology systems face parallel loudspeaker cables increasing the total capacitance. To ensure correct operation of the EOL module it is important that the total capacitance is below the maximum C

g

of the EOL module.Below checks result in a clear indication with respect to correct operation using EOL’s in combination with the used cable and cable lengths.Information needed of used cableCable capacitance Cg (nF/km) (= capacitance to shield, ground or return wire, depending the application)Cable length per loudspeaker line (meters)Check 1 (Controller)Calculate the total cable length of connected loudspeaker lines (max 12 lines).Check if the intersection point in the graph between the mutual cable capacitance and total calculated length is in the green area.Check 2A (for each Router)Calculate per router the total cable length of connected loudspeaker lines connected to the first 12 outputs (1-12).Check if the intersection point in the graph between the mutual cable capacitance and total calculated length is into the green area.Check 2B (for each Router)Calculate per router the total cable length of connected loudspeaker lines connected to second 12 outputs (13-24).Check if the intersection point in the graph between the mutual cable capacitance and total calculated length is in the green area.Check 3 (for each Amplifier)Calculate per amplifier channel the total cable length connected to loudspeaker lines (max 24 lines).Check if the intersection point in the graph between the mutual cable capacitance and total calculated length is in the green area.For correct operation of the EOL all above checks needs to be within the green safe area!For 1200nF usage, max. 29 modules can be used and even or odd addressing is required. If more than 29 modules are required, 400nF should be taken in account

PAVIRO - EOL module (PVA-1WEOL) cable capacitance check

Security Systems | ST-CO/MKP1.2 | 25/11/2016