G.E. UPS  Productline   Uninterruptible Power Supplies | 1 Phase G.E. UPS  Productline   Uninterruptible Power Supplies | 1 Phase

G.E. UPS Productline Uninterruptible Power Supplies | 1 Phase - PowerPoint Presentation

tatyana-admore
tatyana-admore . @tatyana-admore
Follow
343 views
Uploaded On 2019-11-04

G.E. UPS Productline Uninterruptible Power Supplies | 1 Phase - PPT Presentation

GE UPS Productline Uninterruptible Power Supplies 1 Phase Delivering reliable power in a compact footprint LP11 LP31T LP31 Series Application Medium data networks telecom equipment local site protection ID: 763236

ups power input efficiency power ups efficiency input tle high series amp cost output operating improved mode load conversion

Share:

Link:

Embed:

Download Presentation from below link

Download Presentation The PPT/PDF document "G.E. UPS Productline Uninterruptible ..." is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

G.E. UPS Productline

Uninterruptible Power Supplies | 1 Phase Delivering reliable power in a compact footprint LP11 / LP31T / LP31 Series Application Medium data networks, telecom equipment, local site protection Double conversion, high efficiency (up to 97%) and redundant parallel capable, with galvanic isolation and GE’s battery management for load security. Line Interactive topology, automatic voltage regulation, step-wave output with internal hot swappable batteries. IT & Match Series Application Point-of-sale (POS), ISDN switches PCs, routers, & small IT servers Application Healthcare & marine, wind turbine, controls, all IT & high speed processing VH Series GT Series Double conversion, parallel-ready technology with modular battery and power components for easy expansion and retrofit. Application Telecom equipment, server racks, small to medium data networks Double conversion technology, hardened design, peak load handling, and wide temperature operating range. RatingOutputCert.600 VA – 2 kVA120 VacUL500 VA – 3 kVA230 VacCE RatingOutputCert.1 – 2kVA120 VacUL3kVA120/208 VacUL5 - 10kVA120/208/240 VacUL6 & 10kVA220/230/240 VacCE RatingOutputCert.5-10 kVA120/208/240 VacUL & CE3-10 kVA220/230/240 VacCE5-20 kVA220/230/240 VacCE Rating Output Cert. 2 kVA 208/220/230/240 Vac UL 700 VA-3 kVA 208/220/230/240 Vac CE

Uninterruptible Power Supplies | 3 Phase Clean, reliable and energy efficient power The high efficiency SG series provides fast step/transient load response while eliminating single points of failure. SG Series Application Enterprise class data networks, large data centers, healthcare equipment The LP33 series is a transformer-less design reducing install footprint and installation time. LP33 Series Application Large data networks, telecom equipment The SitePro model is a robust, double conversion UPS that provides true on-line operation and galvanic isolation. SitePro ApplicationManufacturing & process controlhealthcare equipment, data centers Leading the industry through innovation Redundant Parallel Architecture (RPA)Increasing reliability by eliminating single points of failure. Paralleling multiple UPS’ for true redundancy without adding complexity. ECO ModePower supplied from mains via UPS bypass circuit. Immediate transfer to inverter power during disturbance. Energy efficiency of up to 98.5%. PurePulse ®Delivers pure clean waveform from the mains, reducing sizing of upfront equipment and eliminating additional input filters.RatingOutputCert.10 - 750 kVA480 VacUL60 - 500 kVA 400 VacCERatingOutputCert.10 - 100 kVA208 VacUL10 - 120 kVA380/400/415 VacCERatingOutputCert.10 - 40 kVA380/400/415 Vac CE

TLE Series Platform 225 – 1500 kW GE Critical Power

TLE Series platform Introducing TLE Series UPS What is it? TLE Series is a new high power transformer less 3 phase UPS platform with best in class multi-mode efficiency (eBoost and double conversion), and modular scalable from 200 kW up to 1500 kW for global UPS markets (CE and UL). Why is it important? This TLE platform establishes GE technology leadership in mid/high power UPS applications with industry leading differentiation in efficiency, output power capacity and footprint. Differentiated Value Proposition Best in class multi-mode efficiency 96.5% Double Conversion mode (VFI)99.0% eBoost mode (VFD) Highest output power (up to 1.5 MW) High reliability:Improved serviceability and lower MTTRStandard building blocks 250 kwInherent redundancy inside UPS moduleHigh power density and small foot printExcellent input , output performance

Creating Value – Low TCO

Creating Value – Low TCO Ultra high Efficiency 1

Double conversion Efficiency – 96.5% High Efficiency at all loads Reduced customer operation costs and cost saving in air conditioning design High efficiency performances High efficiency at full and partial loads for real benefit in operating conditions Energy cost saving Reduced cost of customer equipment operation at all loads Air conditioning cost savingReducing size and cost of air condition systemReducing consumption and related operating cost GE Sets the Bar for highest UPS Operating Efficiency

High Efficiency – eBoost mode eBoost high efficiency (up to 99%) fast transfer to inverter <2ms "GE's eBoost feature expands a classic mode On-Line Double Conversion UPS System to a multi-mode UPS capable of maximizing operating efficiency commensurate with the stability of utility voltage and frequencyeBoost can be operated in RPA mode, up to 6 UPS modules in parallel, with all units operating and switching as one through redundant communication bus

High Efficiency – Low TCO High efficiency up to 96.5% Considerable life cycle cost savings Reduction in UPS operating cost Reduction in cooling cost 5 MW IT load - TLE series life cycle savings of $1.5 MM while operating in VFI mode Assumptions: Power cost = $ 0.10 /kw-hr Operating hours/year = 8760Cooling factor = 0.35Configuration = S+S operating at 50% load 93%96.5%99%

High Efficiency – Low TCO High efficiency up to 96.5% Considerable life cycle cost savings Reduction in UPS operating cost Reduction in cooling cost Assumptions: Power cost = $ 0.10 /kw-hr Operating hours/year = 8760 Cooling factor = 0.35Configuration = 500 kW UPS @ 50% load TLE Series UPS annual savingsCompared to 92% efficiency UPS > $ 14,980 94% efficiency UPS > $ 8,140 95% efficiency UPS > $ 4,830

Creating Value – Low TCO Excellent Performance 2

UPS input performances Total Current Harmonic Distortion – THDi <5% UPS input power factor: 0.99 Constant behavior at all loads Negligible harmonics contents at full and partial loadsProgrammable Soft Start Feature Benefit on input mains Saving in the sizing of upfront equipment e.g. GenSet, cablings, circuit breakers, … No disturbances to nearby equipment Saving cost due to additional filtersBest in class input performance

High input performance means saving: GenSet size ( From 2 X Load kVA to 1.3 X Load kVA) - Stable & longer life due to absence of harmonics Circuit breaker size Cabling section/size Investment & space Improved life for nearby equipments No reactive power – saves on power compensation Input performances benefit

Power capability – Unity power factor (kVA = kW) Designed to supply real power for Unity power factor data centers load Suitable for modern power supply application with unit or capacitive power factor (e.g. new servers generation), crest factor up to 3:1 UPS output power capability 11% more kW power compared to UPS with PF=0.9No output voltage distortion with linear and non-linear loads Voltage distortion - linear loads: THDv < 2-3% - non-linear loads: THDv < 5%

UPS Input-Output Performance Module size optimization/ Electrical infrastructure utilization 4000 A Input Bus 6 x TLE 500 kW 4 x TLE 750 kW 3 x TLE 1000 kW 2 x 1500 KW 3 MW Power 3000 A Input Bus 4 x TLE 500 kW3 x TLE 750 kW2 X 1000 kW 2.25 / 2 MW Power2000 A Input Bus 3 x TLE 500 kW2 x TLE 750 kW1 x 1500 kW 1.5MW Power11% more kW power compared to UPS with PF=0.9Competitors units with 0.9 power factor provides less output power from same input bus size

Creating Value – Low TCO Improved Diagnostic High Reliability 3

New FLEX DSP board: the black-box Waveform capture, diagnostic and trend analysisSimultaneous acquisition of 32 channels Sampling frequency up to 10kHzSmart trigger capability with up to 16 indipendent trigger sources to record only specific events with pre/post trigger data acquisitionBuffer depth of 1000 samples per channel: each event is recorded for 100ms @ s.f. 10kHz 8 buffers to record up to 8 events without losing older events – can be extended with external USB mass storage devices WAVEFORMS Inverter voltages Bypass voltages Input mains voltages Output voltages: Output current Phases:Input capacitors “Cin” voltages:Inverter primary current: Input current: IDC current: Battery current: Bypass current:UDCCommunication status RPAAuxiliary statusSSM statusFuses statusPhase error slave master.

Creating Value – Low TCO Ease of Installation Improved Serviceability4

Reduced footprint Compact design saving space in installation - 225-250 kW: (w x d x h) 44.4 x 33.9 x 75.1 inch -400-500 kW: 66.9 x 33.9 x 75.1 inch Standard Top-bottom cable entry Easier to handleHigh power densitySavings in installation space Compact design 1907 / 75.1” 1100 / 43.3”TLE Series 250 kW

Improved serviceability Improving Mean Time to Repair & Installation Front access construction/design Draw out construction for fans & power modules Common 250 kW power block & common components Faster power block MTTR Easy access to customer connections Easy access to connectivity Improved diagnostic capabilityiUPS Guard – Remote monitoringStandard back feed protectionInternal Option - Q2 (TLE 250-500) External Option – Q2 (TLE 750 -1500)

Installation flexibility – RPA Cable Saver 1A 2 A 3 A 1B 2 B 3 B Bypass input to UPS Output from UPS Competitors – 1A=2A=3A and 1B=2B=3B or max 10% difference TLE Series with inductor = allows variation up to 20-25% (depends on UPS rating & cable section

Menu driven touch screen 7” display Critical measurement of input, output and battery included with mimic diagram Quick operational status Different access level for user and service Different mimic diagram based on configurationMultilanguage communication interface Advanced User Interface Metering Alarm Set up CommandRPA System

Advanced User Interface Menu driven touch screen display

Advanced User Interface Menu driven touch screen display Separate screen for RPA system with status and measurements Metering screen by tabs Home button inside each screen Improved alarm and events screen Easy to use set up screen

Creating Value – Low TCO Summary 5

Differentiated TLE Series UPS 96.5% THDi 3-5%, Input pf 0.99 Output pf -1

TLE Series UPS Differentiating : Best in class double conversion efficiency - up to 96.5%Ultra high efficiency in eBoost mode of operation - up to 99%Static bypass inductor Compact foot print provides very high power densityExcellent input, output performanceImproved diagnostic capability with black box Ease of installation and Improved serviceability

3-Level topology High Efficiency at all loads Reduced customer operation costs and cost saving in air conditioning design High efficiency performances The TLE Series UPS uses a three level technology with an Advanced Neutral Point Clamped topology implemented with true Reverse Blocking IGBT. These result in reduced switching and filter losses with respect to a standard two level technology

Improved diagnostic, High Reliability Improving Mean Time to Repair Wave form capture capability Fan failure detection Improving Reliability & Diagnostic AC Capacitor health monitoringComponent life time counters Dedicated supply path for bypass logic Redundant Isolated power supply Robust RPA communication No total OFF button to avoid human error Heat sink & input, output filter coils temperature monitoring

Double conversion (VFI) technology Automatic bypass for overloads, short circuit and UPS disturbances conditions Manual bypass Q2 (optional) for UPS maintenance operations without load interruption (225-500 kW internal option) Standard common mainsNumber of battery blocks – 40-42 - back feed protection K6 standard UPS configuration Optional – TLE Series 225-500 kW TLE Series 225-500 kW

Supplemental Cabinetry VRLA Battery Cabinet Systems Flywheel DC Energy Storage480/480V External Maintenance Bypass 480/208V External Maintenance Bypass (250kw max)Optional Equipment 480/415VAC Input Isolation Xfmr600VAC Input Isolation Xfmr Remote Alarm Status PanelDual InputRPA Card for parallel operation eBoost Software for multi-mode operation Installation flexibility - Product options ISM (intelligent Synchronization module) – not supported

Remote monitoring – TLE Series iUPSGuard – Remote monitoring Improved response time 24 x7 monitoring & alarm notification of UPS Improved pre dispatch diagnostic & first time fixRegular status reports Highly secure communication

Customer ConnectivityEasy integration with Building Management System (BMS) Customer interface UPS supervision capability 1x RS232 Serial Communication Port 6 programmable potential free alarm contacts: - D plug - Terminals blocks1x Emergency Power OFF contact1x Gen-ON Input contact1x Control Input contact Additional interface:SNMP Interface Card (10/100Mbps auto-select)MODBUS Interface (RS232 or RS485)iUPSGuard (free license during warranty)- SNMP card required for iUPSGuard

Configurable up to 6 units in parallel Future expansion Safe and reliable power supply Redundant Communication Bus Redundant Parallel Architecture Easy to install and maintain Easy system upgrade/downgrade Maintenance operation withoutload interruptionRPA cable saver allows installation flexibilitySystem reliability improved by RPA