Commercial50Hz RDC Inverter  Service Manual20102011 Commercial50Hz RDC Inverter  Service Manual20102011

Commercial50Hz RDC Inverter Service Manual20102011 - PDF document

vivian
vivian . @vivian
Follow
342 views
Uploaded On 2021-06-16

Commercial50Hz RDC Inverter Service Manual20102011 - PPT Presentation

HOKKAIDO DCInverter Commercial 2010Contents Contentsi Part 1 General Information 1Part 2 Indoor Units 6Part 3 Outdoor UnitsPart 4 InstallationPart 5 Control The specifications designs and informat ID: 843438

indoor outdoor dcinverter commercial outdoor indoor commercial dcinverter temp type unit check hokkaido pipe refrigerant air 2010 cdb pressure

Share:

Link:

Embed:

Download Presentation from below link

Download Pdf The PPT/PDF document "Commercial50Hz RDC Inverter Service Man..." is the property of its rightful owner. Permission is granted to download and print the materials on this web site for personal, non-commercial use only, and to display it on your personal computer provided you do not modify the materials and that you retain all copyright notices contained in the materials. By downloading content from our website, you accept the terms of this agreement.


Presentation Transcript

1 Commercial50Hz RDC Inverter Service Man
Commercial50Hz RDC Inverter Service Manual20102011 HOKKAIDO DCInverter Commercial 2010Contents Contentsi Part 1 General Information. 1Part 2 Indoor Units 6Part 3 Outdoor UnitsPart 4 InstallationPart 5 Control The specifications, designs, and information in this book are subject to change without notice for product improvement. HOKKAIDO DCInverter Commercial 2010eneral Information eneralInformation 1 Part 1 General Information1. Model Names of Indoor/Outdoor Units 22. External Appearance 32.1 Indoor Units 32.2 Outdoor Units 4. Features 5 Model Names of Indoor/Outdoor UnitsHOKKAIDO DCInverter Commercial 2010 2 General Information 1.Model Names of Indoor/Outdoor Units1.1 Indoor Units410A(capacity in Kw) Type Function 3.5 5.3 7.1 10 14 17 New Four - way cassette Co oling and heating Four - way cassette Cooling and heating Duct Cooling and heating Ceiling & floor Cooling and heating Console Cooling and heating 1.2 Outdoor UnitsModel of outdoor unit and corresponding indoor unit Universal Outdoor unit Model Compressor type Compressor Brand Matched indoor units HCKI 351 XRRotary DC InverterGMCC HTFI 352 XR HUCI 352 XRHSFI 351 XR HFII 351 XR HCKI 532 XRScroll DC InverterShenyang SANYO HTFI 532 XR HUCI 531 XRHSFI 531 XR HFII 531 XR HCKI 712 XRRotary DC InverterHITACHI HUCI 711 XR HSFI 711 XRHTBI 711 XR HCSI 1083 XRRotary DC InverterMITSUBISHI HUCI 1081 XRHSFI 1081 XRHTBI 1081 XR HCSI 1413 XRRotary DC InverterMITSUBISHI HUCI 1411 XR HSFI 1411 XR H TBI 1411 XR HCSI 1762 XRScroll DC InverterMITSUBISHIHUCI 1761 XRHSFI 1761 XR HOKKAIDO DCInverter Commercial 2010External Appearance General Information3 2.External Appearance2.1 Indoor Units Duct Ceiling & Floor Four - w ay Cassette Compact Four - way cassette Console External AppearanceHOKKAIDO DCInverter Commercial 2010 4 General Information 2.2 Outdoor UnitsI 351 XR HCKI 532 XR HCKI 712 HCSI 1083 XR HCSI 1413 XR – HCSI 1762 XR HOKKAIDO DCInverter Commercial 2010Features General Information5 3.Features .1 Universal outdoor unit designIndoor unit with the same capacity can match with the same outdoor unit..2 High efficiency and energy savinThanks to the DC inverter technology and optimized piping system, the EER and COP of whole series can easily reach A-class. .3 Low noise and low starting current.Thanks to the DC inverter technology, the system can work with low noise, and verysmall starting current..4 Intelligent refrigerant adjustment technology.Throttle part is made up of capillary and electronic expansion valve (EXV). The outdoor unit can output the most accurate capacity in any condition..5 Working in cooling mode under (except 3,5kW). Outdoor unit builtin with low ambient kit, it can control the outdoor unit’s fan an

2 d cooling can be performed throughout th
d cooling can be performed throughout the year for computer rooms, banquet halls,etc. Wideoperation range covers outdoor temperatures as low as for cooling(except 3,5kW). Indoor & outdoor unit’s power supplyis separate. All indoor unitshavenetwork controlfunction. .8 All indoor unitshave Autorestart function. Indoor UnitsHOKKAIDO DCInverter Commercial 2010 6 Indoor Units Part 2 Indoor Units New Fourway Cassette Type (Compact) 7way Cassette Type17Duct Type34Ceiling & Floor Type51Console Type72 HOKKAIDO DCInverter Commercial 2010New Fourway Cassette Type New Fourway Cassette7 New -way Cassette Type (Compact)1. Features 82. Specifications 93.Dimensions104. Service Space105. Wiring Diagrams6. Air Velocity and Temperature Distributions127. Electric Characteristics138. Sound Levels139. Accessories. 1410. The Specification of Power1411. Field Wiring15 FeaturesHOKKAIDO DCInverter Commercial 2010 8 New Fourway Cassette (Compact) 1.Features(1)Low operation noiseStreamline plate ensures quietnessCreates natural and comfortable environment(2)Efficient coolingEqual, fast and widerange cooling (3)The adoption of the most advanced 3- Dimensional Screw fanReduces the air resistance passing throughmoothes the air flowMakes air speed distribution to the heat exchange uniform(4) Improvement for easy installation and maintenance Little space is required for installation into a shallow ceilingBecause of the compactness and weight reduction of the main unit and panel, all models can be installed without a hoist(5) 360Air Flow Panel0 air outlet makes equal,fast ad wide range cooling(6) Inside Ebox designThe Ebox is simply and safely build inside tge indoor unit, of witch ceiling side is 600mm*600mm. It is convenient to install and maintain. Checking the control part is easy, you only need to open the air return grille. HOKKAIDO DCInverter Commercial 2010Specifications New Fourway Cassette (Compact)9 2.SpecificationsModelHTFI 352 XRHTFI 532 XR Power supply V - ph - Hz 220~240 - 1 - 50 220~240 - 1 - 50 CoolingCapacitykw .5.30 InputW Current A 5.0 8.2 .37.23 HeatingCapacitykw .00.05 Input W 1 075 1 630 Current A 5.8 8.2 COP.72.71 Indoor fan motorModel YDK15YDK37 Qty1 1 InputW 47.1/31.1/26.980/46/32 Capacitor1.5 /450V2 /400450V Speed(Hi/Mi/Lo) r/min780/540/4301000/710/570 Indoor coilNumber of rows1 2 Tube pitch(a)×row pitch(b)21×13.3721×13.37 Fin spacing1.31.3 Fin type (code)Hydrophilic aluminumHydrophilic aluminum Tube outside dia. and type φ7Inner grooved copper tubeφ7Inner grooved copper tube Coil length × height × width 1380×210×13.371370×210×26.74 Number of circuits2 4 Indoor air flow (Hi/Mi/Lo) 683/530/510800/710/560 Indoor noise level (sound pressure)dB(A)42/41/3842/41/38 Indoor unitDimension (W×H×D)(body)570×260×570570×260×570 Packing (W×H×D)(body) 655×290×655655×290×655 Dimension (W×H×D)(panel)647×50×647647×50×647 Pac

3 king (W×H×D)(panel)705×113×705705×1
king (W×H×D)(panel)705×113×705705×113×705 Net/Gross weight(body) kg 16/1918/21 Net/Gross weight(panel) kg 3/53/5 Refrigerant typeR410AR410A Design pressure MPa4.2/1.54.2/1.5 Refrigerant pipingLiquid side/ Gas side φ6.4/φ12.7φ6.4/φ12.7 Drainage water pipe diameterODφ25ODφ25 ControllerR05/BGE (standard)R05/BGE (standard) Operation temperature Notes: Nominal coolingcapacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal)Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal)Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. DimensionsHOKKAIDO DCInverter Commercial 2010 New Fourway Cassette (Compact) 3.Dimensions4.Service Space HOKKAIDO DCInverter Commercial 2010Wiring Diagrams New Fourway Cassette (Compact) 5.Wiring DiagramsHTFI 352 XRHTFI 532 Air Velocity and Temperature DistributionsHOKKAIDO DCInverter Commercial 2010 New Fourway Cassette (Compact) 6.Air Velocity and Temperature Distributions Airflow velocity Temperature HOKKAIDO DCInverter Commercial 2010Electric Characteristics New Fourway Cassette (Compact) 7.Electric CharacteristicsModelIndoor Units Power Supply MFAMin.Max.MFA HTFI 352 XR HTFI 532 XR Remark: MFA: Max. Fuse Amps. (A)8.Sound Levels 1.0m FOUR-WAY CASSETTE TYPE Microphone Model Noise level dB(A) H M L HTFI 352 XR HTFI 532 XR Accessories HOKKAIDO DCInverter Commercial 2010 New Fourway Cassette (Compact) 9.Accessories NameShapeQuantity . Drain joint(Be provided in outdoor unit.) 1 . Remote controller 1 . Remote controller holder 1 . Mounting screw(ST2.9×10-C-H) 2 . Alkaline dry batteries (AM4) 2 . Owner's manual 1 . Installation manual 1 10.The Specification of Power HOKKAIDO DCInverter Commercial 2010Field Wiring New Fourway Cassette (Compact) 11.eld Wiring HTFI 352 XRHTFI 532 XR Field WiringHOKKAIDO DCInverter Commercial 2010 New Fourway Cassette (Compact) HTFI 352 XRHTFI 532 XR HOKKAIDO DCInverter Commercial 2010Fourway Cassette Type Fourway Cassette Type -way Cassette Type 1. Features182. Specifications213. Dimensions244. Service Space255. Wiring Diagrams266. Air Velocity and Temperature Distributions277. Electric Characteristics288. Sound Levels289. Accessories. 2910. The Specification of Power3111. Field Wiring32 FeaturesHOKKAIDO DCInverter Commercial 2010 Fourway Cassette Type 1.Features(1)Low operation noiseStreamline plate ensures quietnessCreates natural and comfortable environment(2)Efficient coolingEqual, fast and wide range cooling (3)Excellent performance. The optimal evaporator & sufficient airflow v

4 olume guarantees the excellent capacity(
olume guarantees the excellent capacity(4)The adoption of the most advanced 3- Dimensional Screw fanReduces theair resistance passing throughSmoothes theair flowMakes air speed distribution totheheat exchange uniform(5)Fresh air makes life healthier and more comfortable.(6)Drainage pump can take up the condenser water to750mm. (7)Ultra thin machine body to easy installation and maintenance.18K~24K:230mm, 36~48K:300mm. HOKKAIDO DCInverter Commercial 2010Features Fourway Cassette Type (8) Swing angle of louverAdd one more swing motor, one motor driving two louvers. Controlling the interspace of each part, minimizing the angle loss.The swing angle of the first louver are 40~42 degrees and the second louver are 37~38 degrees. New evaporator and inner configuration designed can acquire high heatexchanger effect.(10)More strengthening rib design around the panel, preventing the distortion for the panel.(11)New outlet frame design to make the phenomena of coagulation great improvement: prevent the condensing water from damaging the air guide strip.(12)Adding rib on the panel of fan outlet, which can avoid the air outlet direct flow to people.(13)4 speeds available, optional super high fan speed design suitable for the large building over 3m high.(14)Adding digital tube displaying on the display board. LED can display the Error Code to make the malfunction checking easier.(15)Reserve spaces for air sideoutlet, it is available to connect duct pipe hence ir supplying from the four sides to nearby small room.. FeaturesHOKKAIDO DCInverter Commercial 2010 Fourway Cassette Type ) The connecting pipe and drop height is higher.Max. pipe length up to 50mrefer to , and Max. drop height up to 30mrefer to . 7) Optimal design, smaller Control Box, Space saving and convenient for wiring, Using fire resistance galvanized steelfor Ebox material.Metal box make the control part more stable and prevent damaging.(18) 360air flow panel : 360air flow delivery ensures uniform airflow distribution. 60K is standard, the others are optional. HOKKAIDO DCInverter Commercial 2010Specifications Fourway Cassette Type 2.SpecificationsIndoor Unit Model HTBI 711 XR Power supply V-220~240-1- Outdoor UnitModelHCKI 712 XR Power supply V-220~240-1- CoolingCapacitykw .10 Inputw currentA 13.29.784.26 .26 HeatingCapacitykw .80 Inputw currentA 12.239.134.56 COP.73 Indoor fan motor Model YDK80 Qty 1 Input W 120/100/90 Capacitor 3.5uF/450V Speed(Hi/Mi/Lo) r/min 670/550/400 Indoor coilNumber of rows2 Tube pitch(a)×row pitch(b) mm 21 x13.37 Fin spacing1.5 Fin type (code) Hydrophilic aluminum Tube outside dia. and type mm Ф7 Inner grooved copper tube Coil length × height × width 1990x168x26.74 Number of circuits 8 Indoor air flow(Hi/Med/Lo) m 3 /h 1327/1114/871 Indoor noise level (Hi/Med /Lo) dB(A) 42/4/39 Indoor unit Dimension (W×H×D)(body) mm 840x230x840

5 Packing (W×H×D)(body) mm 900x250
Packing (W×H×D)(body) mm 900x250x900 Dimension (W×H×D)(panel) mm 950x55x950 Packing (W×H×D)(panel) 1035x90x1035 Net/Gross weight(body) kg 24/30 Net/Gross weight(panel) kg 6/9 Refrigerant type R410A Design pressure MPa 4.2/1.5 Refrigerant piping Liquid side/ Gas side mm φ9.5/φ15.9 Drainage water pipe diameter mm ODφ32 Controller R05/BGE (standard) Operation temperature Notes:Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref.piping: 7.5m (horizontal)Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. SpecificationsHOKKAIDO DCInverter Commercial 2010 Fourway Cassette Type Indoor Unit Model HTBI 1081 XR Power supply V-220~240-1- Outdoor Unit Model HCSI 1083 XR Power supply V--3- CoolingCapacitykw 0.80 Inputw currentA 7.76.04.1 .24 HeatingCapacitykw 1.85 Inputw currentA 6.54.83.2 COP.73 Indoor fan motorModelYDK90 Qty 1 Input W 143/116/100 Capacitor 3.5uF/450V Speed(Hi/Mi/Lo)r/min770/640/550 Indoor coilNumber of rows2 Tube pitch(a)×row pitch(b) mm 21x13.37 Fin spacing mm 1.5 Fin type (code) Hydrophilic aluminum Tube outside dia. and type mm Inner grooved copper tube Coil length × height × width mm 1990x252x26.74 Number of circuits 12 Indoor air flow(Hi/Med/Lo)1545/1354/1187 Indoor noise level (Hi/Med/Lo) dB(A) 44/42/41 Indoor unitDimension (W×H×D)(body) mm 840×300×840 Packing (W×H×D)(body) mm 900×320×900 Dimension (W×H×D)(panel) mm 950x55x950 Packing (W×H×D)(panel) mm 1035x90x1035 Net/Gross weight(body) kg 30/36 Net/Gross weight(panel) kg 6/9 Refrigerant type R410A Design pressureMPa4.2/1.5 Refrigerant piping Liquid side/ Gas side mm φ9.5/φ15.9 Drainage water pipe diameter mm ODφ32 Controller R05/BGE (standard) Operation temperature Notes:Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref.piping: 7.5m (horizontal)Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. HOKKAIDO DCInverter Commercial 2010Specifications Fourway Cassette Type Indoor Unit Model HTBI 1411 XR Power supply V-220~240-1- Outdoor Unit Model HCSI 1413 XR Power supply V--3- CoolingCapacitykw 4.10 Inputw currentA 9.06.94.0 EER 3 .26 HeatingCapacitykw 5.40 Inputw currentA 9.06.73.7 COP 3 .71 Indoor fan motor ModelYDK90 Qty

6 1 Input W 143/116/100 Ca pacito
1 Input W 143/116/100 Ca pacitor 3.5uF/450V Speed(Hi/Mi/Lo)r/min770/640/550 Indoor coilNumber of rows2 Tube pitch(a)×row pitch(b) 21x13.37 Fin spacing1.5 Fin type (code) Hydrophilic aluminum Tube outside dia. and type Ф7 Inner grooved copper tube Co il length × height × width mm 1990x252x26.74 Number of circuits Indoor air flow(Hi/Med/Lo) m 3 /h 1545/1354/1187 Indoor noise level (Hi/Med/Lo) dB(A) 44/42/41 Indoor unit Dimension (W×H×D)(body) mm 840×300×840 Packing (W×H×D)(body) mm 900×320×900 Dimension (W×H×D)(panel) mm 950x55x950 Packing (W×H×D)(panel) mm 1035x90x1035 Net/Gross weight(body) kg 30/36 Net/Gross weight(panel) kg 6/9 Refrigerant type R410A Design pressure MPa 4.2/1.5 Refrigerant piping Liquid side/ Gas side mm φ9.5/φ15.9 Drainage water pipe diameterODφ32 ControllerR05/BGE (standard) Operation temperature Notes:Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref.piping: 7.5m (horizontal)Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. DimensionsHOKKAIDO DCInverter Commercial 2010 Fourway Cassette Type 3.DimensionsUnit: mmMODEL(Btu/h)A B C H 2400015.9Ф9.5 3600015.9Ф9.5 4800015.9Ф9.5 HOKKAIDO DCInverter Commercial 2010Service Space Fourway Cassette Type 4.Service SpaceFor 48k Wiring DiagramsHOKKAIDO DCInverter Commercial 2010 Fourway Cassette Type 5.Wiring DiagramsHTBI 711 XRHTBI 1081 XRHTBI 1411 XR HOKKAIDO DCInverter Commercial 2010Air Velocity and Temperature Distributions Fourway Cassette Type 6.Air Velocity and Temperature Distributions Airflow velocity Electronicexpansion valve Oil separator Compressor Low pressureswitch Oil return CapillaryHigh pressure switchLow pressure liquid accumulator Evaporator CapillaryOutdoor unitIndoor unit 4-way valve Condenser Discharge temp. sensor Filter Filter Condenser temp. sensor T3 T4 Ambient temp. sensorFilter Filter T2 Evaporator temp. sensor Room temp. sensor Electric CharacteristicsHOKKAIDO DCInverter Commercial 2010 Fourway Cassette Type 7.Electric CharacteristicsModelIndoor Unit Power Supply VoltageMinMaxMFA HTBI 711 XR240 HTBI 1081 XR 240 HTBI 1411 XR 240 Remark: MFA: Max. Fuse Amps. (A) 8.Sound LevelsModelNoise level dB(A) H M L HTBI 711 XR41 HTBI 1081 XR HTBI 1411 XR HOKKAIDO DCInverter Commercial 2010Accessories Fourway Cassette Type 9.Accessories INSTALLATION FITTINGSNameShapeQuantity Installation paper board 1 Tubing & FittingsSoundproof / insulation sheath 2 Connecting pipe group1 Drainpipe FittingsOutl

7 et pipe sheath 1 Outlet pipe clasp
et pipe sheath 1 Outlet pipe clasp 1 Drain joint 1 Seal ring 1 Remote controller & Its FrameRemote controller & Its Frame 1 Remote controller holder 1 Mounting screw(ST2.9×10-C- 2 Alkaline dry batteries (AM4) 2 OthersOwner's manual1 Installation manual1 Installation accessory(The product you have might not be provided the following accessoriesExpansible hook 4 Installation hook 4 Orifice 1 Accessories HOKKAIDO DCInverter Commercial 2010 Fourway Cassette Type MCC60HRDN1Installation Fittings Name Shape Quantity Expansible hook 4 Installation hook 4 Installation paper board 1 Bolt M6 4 Tubing Fittings5. Soundproof / insulation sheath 2 Drainpipe Fitti6. Outlet pipe 1 7. Outlet pipe sheath 1 8. Outlet pipe clasp 1 9. Tighteningband 20 Remote controller Its Frame10. Remote controller 1 11. Remote controller holder 1 1 2 . Mounting screw(ST2.9 -C- 2 13. Remote controllermanual 1 14. Alkaline dry batteries (AM4) 2 Others. Owner's manual 1 . Installation manual 1 . Net work winding1 Optional fittingsHook for fourway air supply panel 1 HOKKAIDO DCInverter Commercial 2010The Specification of Power Fourway Cassette Type 10.The Specification of Power Field WiringHOKKAIDO DCInverter Commercial 2010 Fourway Cassette Type 11.Field Wiri Wiring chart HOKKAIDO DCInverter Commercial 2010Field Wiring Fourway Cassette Type Duct TypeHOKKAIDO DCInverter Commercial 2010 Duct Type Duct Type1. Features352. Specifications363. Dimensions394. Service Space405. Wiring Diagrams416. Static Pressure427. Electric Characteristics448. Sound Levels459. Accessories. 4610. The Specification of Power4711. Field Wiring48 HOKKAIDO DCInverter Commercial 2010Features Duct Type 1.Features● New structure design. uiltdrainage pump Two air intake ways: from below or rear (standard). Wire controller is standard. Three speeds indoor unit.Fresh air inlet hole is reserved. SpecificationsHOKKAIDO DCInverter Commercial 2010 Duct Type 2.SpecificationsIndoor Unit Model HUCI 351 XRHUCI 531 XRHUCI 711 XR Po wer supply V - ph - Hz 220~240-1-220~240-1-220~240-1- Outdoor UnitModelHCKI 351 XRHCKI 532 XRHCKI 712 XR Power supply V - ph - Hz 220~240-1-220~240-1-220~240-1- CoolingCapacitykw 3 .5 5 .3 7 .10 Inputw 1 050 1 620 2 180 Rated currentA 6.54.92.210.47.43.513.710.04.6 EER 3 .33 3 .27 3.2 6 HeatingCapacitykw 4 .00 5 .9 7 .8 Inputw 1 065 1 590 2 090 Rated currentA 6.4 - 4.9 - 2.1 10.7 - 7.5 - 3.6 13.9 - 9.6 - 4.8 COP 3 .76 3 .71 3 .73 Indoor fan motor Model YSK25YSK68YSK74 Qty 1 1 1 Input W 107/65/52107/65/52163/93/75 Capacitor 2μF /450V3.5μF /450V3.5μF /450V Speed(Hi/Mi/ Lo) r/min1150/800/7001150/800/7001000/750/680 Indoor coilNumber of rows2 3 4 Tube pitch(a)×row pitch(b) 21×13.3721×13.3721×13.37 Fin spacing1.51.51.5 Fin

8 type (code) Hydrophilic aluminum
type (code) Hydrophilic aluminum Hydrophilic aluminum Hydrophilic aluminum Tube outside dia. and type φ7 Inner grooved copper tubeφ7 Inner grooved copper tubeφ7 Inner grooved copper tube Coil length × height × width 735×252×26.74735×252×40.11735×252×53.48 Number of circuits 3 4 6 Indoor air flow(Hi/Med/Lo) m 3 /h 800/610/5201170/770/6501400/1100/1000 Indoor external static pressure (Hi) Pa 40 70 70 Indoor noise level (Hi/Med/Lo)dB(A)37/30/2644/36/3345/43/41 Indoor unit Dimension (W×H×D) 920x210x635920x210x635920x270x635 Packing (W×H×D) 1135x290x6551135x290x6551135x350x655 N et/Gross weight kg 25/3026/3130/35 Refrigerant typeR410AR410AR410A Design pressure MPa4.2/1.54.2/1.54.2/1.5 Refrigerant piping Liquid side/ Gas sideφ6./φ12.7φ6./φ12.7φ9.5/φ15.9 Drainage water pipe diameter ODφ25ODφ25ODφ25 Controller KJR10B/DP(T)-E KJR10B/DP(T)-E KJR10B/DP(T)-E Operation temperature Notes: Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal)Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. HOKKAIDO DCInverter Commercial 2010Specifications Duct Type Indoor Unit Model HUCI 1081 XR Power supply V - ph - Hz 220~240-1- Outdoor Unit Model HCSI 1083 XR Power supply V - ph - Hz 380~415-3- CoolingCapacitykw 0.80 Inputw 3 320 Rated currentA 7.0 - 5.2 - 2.3 .25 HeatingCapacitykw 1 1.85 Inputw 3 160 Rated currentA 7.8 - 5.3 - 2.6 COP.75 Indoor fan motorModelYSK140 Qty 1 Input W 291/168/138 Capacitor 10μF /450V Speed(Hi/Mi/Lo)r/min1070/790/710 Indoor coilNumber of rows4 Tube pitch(a)×row pitch(b) 21×13.37 Fin spacing1.5 Fin type (code) Hydrophilic aluminum Tube outside dia. and type φ7 Inner grooved copper tube Coil leng th × height × width 955×336×53.48 Number of circuits 8 Indoor air flow(Hi/Med/Lo) m 3 /h 2270/1890/1650 Indoor external static pressure (Hi) Indoor noise level (Hi/Med/Lo) dB(A)46/44/42 Indoor unit Dimension (W×H×D) 1140x270x775 Packing (W×H×D) 1355x350x795 Net/Gross weight kg 43/50 Refrigerant type R410A Design pressure MPa4.2/1.5 Refrigerant piping Liquid side/ Gas sideφ9.5/φ15.9 Drainage water pipe diameter ODφ25 Controller KJR10B/DP(T)-E Operation temperature Notes: Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal)Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)Actual noise level may d

9 iffer, depending on the room structure,
iffer, depending on the room structure, etc, since these noise values are from an anechoic room. SpecificationsHOKKAIDO DCInverter Commercial 2010 Duct Type Indoor Unit Model HUCI 1411 XRHUCI 1761 XR Power supply V - ph - Hz 220~240-1-220~240-1- Outdoor Unit Model HCSI 1413 XRHCSI 1762 XR Power supply V - ph - Hz 380~415-3-380~415-3- CoolingCapacitykw 4.107.60 Inputw Rated currentA 8.97.03.010.08.04.1 .25 .28 HeatingCapacitykw 5.408.50 Inputw Rated currentA 9.26.73.110.67.83.5 COP.72.73 Indoor fan motorModelYSK170YSK180 Qty 1 1 Input W 356/201/152355/223/173 Capacitor 10μF /450V10μF /450V Speed(Hi/Mi/Lo)r/min1070/750/6501080/830/710 Indoor coilNumber of rows4 4 Tube pitch(a)×row pitch(b) 21×13.3721×13.37 Fin spacing1.51.5 Fin type (code) Hydrophilic aluminumHydrophilic aluminum Tube outside dia. and typeφ7 Inner grooved copper tubeφ7 Inner grooved copper tube Coil length × height × width 955×336×53.481030×378×53.48 Number of circuits8 8 Indoor air flow(Hi/Med/Lo) 3010/2410/19403150/2510/1990 Indoor external static pr essure (Hi) Pa 100 100 Indoor noise level (Hi/Med/Lo) dB(A)47/45/43 47/45/43 Indoor unit Dimension (W×H×D) 1200x300x8651200x300x865 Packing (W×H×D) 1385x373x9201385x373x920 Net/Gross weight kg 50/5950/59 Refrigerant type R410AR410A Design pressureMPa4.2/1.54.2/1.5 Refrigerant piping Liquid side/ Gas sideφ9.5/φ15.9φ9.5/φ15.9 Drainage water pipe diameter ODφ25ODφ25 Controller KJR10B/DP(T)-E KJR10B/DP(T)-E Operation temperature Notes: Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal);Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. HOKKAIDO DCInverter Commercial 2010Dimensions Duct Type 3.DimensionsCapacity (KBtu) Outline d imension (mm) A ir outlet o pening size A ir return opening size Size of outline dimension mounted p lug A B C D E F G H I K L M 12/18 24 920 270 635 570 65 713 35 179 815 260 20 960 350 30/36 48/60 Service SpaceHOKKAIDO DCInverter Commercial 2010 Duct Type 4.Service SpaceEnsure enough space required for installation and maintenance.All the indoor units reservethe hole to joint thefresh air pipe. The hole size as following: HOKKAIDO DCInverter Commercial 2010Wiring Diagrams Duct Type 5.Wiring DiagramsHUCI 351 XRHUCI 531 XRHUCI 1081 XRHUCI 1411 XRHUCI 1761 XR CN1CN13CN2CN4CN5CN7CN6CN17CN11D MBROWNMAIN BOARDWHITEXS1XP1BLACKENC2INDOOR POWERDISPLAY BOARDTRCN10REDT2BCONNECTORSXS1-4XP1-4T2PUMP MOTORTRANSFORMERFMWATER LEVEL SWITCHCODEFAN MOTORTITLET1T2BT2WHITEBLACKROOM TEMP.T1MIDDLE PIPE TEMP.OUTER PIPE TEMP.Y/GN

10 OTE:PLEASE USE SHIELDER WIRE FOR COMM.BU
OTE:PLEASE USE SHIELDER WIRE FOR COMM.BUS WIRE, 202070390385 BLACKH/P2CH/P3HIGH FANSUPER HIGH FAN14000W10500W9000W7100WENC15600W5300W CN9 TO OUTDOORCOMM.BUSTO CCMCOMM.BUS S2 S1 S1S2 CN1 XYEPQALARM BLACKBLACK33CNBLUE ENC2 SW1 ENC1 S3 16000WXS4SW1 WHITESWITCHof the different units, respectively.(FOR INDOOR UNIT ADDRESS)'0~F' of the ENC2 and 'ON/OFF'of the Sw1 mean the addresses NUMBERSWITCH(FOR POWER)POWERSWITCHof the different net units, respectively.(FOR CCM UNIT ADDRESS)'0~F' of the S2 and 'ON/OFF'of the S1 mean the addresses FUNCTION OF SWITCHON/OFFY/G REMOTECONTROLERROROUTPUTCN2CN4 CN3CN5 TO WIRE CONTROLLER Static PressureHOKKAIDO DCInverter Commercial 2010 Duct Type 6.Static PressureHUCI 351 XR HUCI 531 XR 800700400300Low speed Air volume(m/h)External static pressure (Pa) High speedMid speed500600900 Super high speed 1200Mid speedHigh speed External static pressure (Pa)Air volume(m/h)11001000900800700600 Low speed200300400500 Super high speed HUCI 711 XR 15001200Mid speedHigh speed External static pressure (Pa)Air volume(m/h)11001000900800Pa Low speed13001400 Super high speed HOKKAIDO DCInverter Commercial 2010Static Pressure Duct Type HUCI 1081 XR HUCI 1411 XR 2400220016001400Low speed 1020304050607080901100Air volume(m/h)External static pressure (Pa) High speedMid speed120018002000 Super high speed 3100280019001600Low speed 1000Air volume(m /h)External static pressure (Pa) High speedMid speed130022002500 Super high speed HUCI 1761 XR Mid speedHigh speed External static pressure (Pa)Air volume(m Low speed16001900 Super high speed Electric CharacteristicsHOKKAIDO DCInverter Commercial 2010 Duct Type 7. Electric CharacteristicsModelIndoor UnitPower Supply VoltageMin.Max.MFA HUCI 351 XR HUCI 531 XR HUCI 711 XR HUCI 1081 XR HUCI 1411 XR HUCI 1761 XR Remark: MFA: Max. Fuse Amps. (A) HOKKAIDO DCInverter Commercial 2010Sound Levels Duct Type 8.Sound Levels SuctionDischargeMicrophone 1.4mConcealed Duct Type DuctDuct ModelNoise level dB(A) H M L HUCI 351 XR37 HUCI 531 XR36 33 HUCI 711 XR41 HUCI 1081 XR HUCI 1411 XR43 HUCI 1761 XR43 Accessories HOKKAIDO DCInverter Commercial 2010 Duct Type 9.AccessoriesTubing & FittingsNameShapeQuantity Soundproof / insulation sheath 2 Binding tape 1 Seal sponge 1 Drainpipe Fittings(for cooling & heating)Drain joint 1 Seal ring1 Remote controller Its FrameRemote controller1 Frame 1 Mounting screw(ST2.9 10-C- 2 Alkaline dry batteries (AM4) 2 Remote controllermanual1 Wired controller & Its FrameWired controller1 OthersOwners manual1 Installation manual1 EMS & Its fittingMagnetic ring (twist the electric wires L and N around it to five circles) 1 HOKKAIDO DCInverter Commercial 2010The S

11 pecification of Power Duct Type 10.The S
pecification of Power Duct Type 10.The Specification of Power Field WiringHOKKAIDO DCInverter Commercial 2010 Duct Type 11.Field Wiring HOKKAIDO DCInverter Commercial 2010Field Wiring Duct Type Airconditioner link-circuit. Field WiringHOKKAIDO DCInverter Commercial 2010 Duct Type HOKKAIDO DCInverter Commercial 2010Ceiling & Floor Type Ceiling & Floor Type Ceiling & Floor Type1. Features522. Specifications533. Dimensions584. Service Space605. Wiring Diagrams616. Air Velocity and Temperature Distributions637. Electric Characteristics658. Sound Levels669. Accessories. 6710. The Specification of Power6811. Field Wiring69 FeaturesHOKKAIDO DCInverter Commercial 2010 Ceiling & Floor Type 1.Features1.1.New design, more modern and elegant appearance.1.2.Convenient installationThe ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrowIt is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting. 1.3.Two direction auto swing (vertical & horizontal) and wide angle air flow, Air flow directional control minimizes the air resistance and produces wilder air flow to vertical direction.e range of horizontal air discharge is widened which secures wider air flow distribution to provide more comfortable air circulation no matter where the unit is set up1.4.Three level fan speed, more humanism design, meets different airsupply requirement. 1.5.Water proof by utilizing the absorbing plastic film on water collector1.6.Easy operation. Autorestart function, remote control and optional wire control method.1.7. Low noise level plus compact sizeShape of the blades has been improvedto prevent noise caused by turbulence. HOKKAIDO DCInverter Commercial 2010Specifications Ceiling & Floor Type 2.SpecificationsIndoor Unit Model HSFI 351 XRHSFI 531 XRHSFI 711 XR Power supply V - ph - Hz 220~240-1-220~240-1-220~240-1- Outdoor UnitModelHCKI 351 XRHCKI 532 XRHCKI 712 XR Power supp ly V - ph - Hz 220~240-1-220~240-1-220~240-1- CoolingCapacitykw .30.10 Inputw 1 050 1620 2180 currentA 5.94.671.6812.37.092.4713.29.94.26 EER 3 .33 .27.26 HeatingCapacitykw .00.90.80 Inputw 1 065 1590 2090 currentA 6.41 - 5.05 - 1.89 11.076.913.1312.239.224.56 COP 3 .76 .71.73 Indoor fan motor Model YSK25YSK55YSK55 Qty 1 1 1 Input W 33.4/31.1/29.5125/105/85125/105/85 Capacitor 1.5uF/450V2.5uF/450V2.5uF/450V Speed(Hi/Mi/Lo) r/min 756/666/5921310/1190/10401310/1190/1040 Indoor coilNumber of rows3 3 3 Tube pitch(a)×row pitch(b) mm 25.4×22 25.4 x 2225.4 x 22 Fin spacing mm 1.71.71.7 Fin type (code) Hydrophilic aluminium Hydrophilic aluminum Hydrophilic aluminum Tube outside dia. and type mm Ф9.53 Inner grooved copper tubeФ9.53 Inner grooved copper tubeФ9.53 Inner grooved coppertube Coil length × height × width

12 mm 804x254x66804x254x66804x254x66 Numb
mm 804x254x66804x254x66804x254x66 Number of circuits 3 3 3 Indoor air flow(Hi/Med/Lo)584/518/463800/600/5001000/900/700 Indoor noise level (Hi/Med/Lo) dB(A) /3/3343/41/3845/43/40 Indoor unit Dimensi on (W×H×D) mm 990x203x660990 x203 x660990 x203 x660 Packing (W×H×D) mm 1089x296 x7441089 x296 x7441089 x296 x744 Net/Gross weightkg 27/3329/3529/35 Refrigerant type R410AR410AR410A Design pressure MPa 4.2/1.54.2/1.54.2/1.5 Refrigerant pi ping Liquid side/ Gas side mm φ6./φ12.7φ6./φ12.7φ9.5/φ15.9 Drainage water pipe diameter mm ODφ25ODφ25ODφ25 Controller R05/BGE (standard)R05/BGE (standard)R05/BGE (standard) Operation temperature Notes:Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal)Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal)Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. SpecificationsHOKKAIDO DCInverter Commercial 2010 Ceiling & Floor Type Indoor Unit Model HSFI 1081 XR Power supply V - ph - Hz 220~240-1- Outdoor Unit Model HCSI 1083 XR Power supply V - ph - Hz -3- CoolingCapacitykw 0.80 Inputw 3 320 currentA 7.534.723.30 EER 3.25 HeatingCapacitykw 1.85 Inputw 3 160 currentA 5.984.471.49 COP 3.75 Indoor fan motorModelYSK80 Qty 1 Input W 143/122/110 Capacitor 3.5uF/450V Speed(Hi/Mi/Lo)r/min1310/1210/1115 Indoor coilNumber of rows3 Tube pitch(a)×row pitch(b) 25.4 x 22 Fin spacing1.7 Fin type (code) Hydrophilic aluminum Tube outside dia. and typeФ9.53 Inner grooved copper tube Coil length × height × width mm 1094 x 254 x 66 Number of circuits5 Indoor air flow(Hi/Med/Lo) m 3 /h 1400/1200/1000 Indoor noise level (Hi/Med/Lo) dB(A) 45/43/40 Indoor unit Dimension (W×H×D) mm 80 x 203 x 660 Packing (W×H×D) mm 1379 x 296 x 744 Net/Gross weight kg 37/42 Refrigerant type R410A Design pressure MPa 4.2/1.5 Refrigerant piping Liquid side/ Gas side mm Ф9.5/Ф15.9 Drainage water pipe diameter mm ODφ25 Controller R05/BGE (standard) Operation temperature Notes:1. Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal)2. Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal)3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. HOKKAIDO DCInverter Commercial 2010Specifications Ceiling & Floor Ty Indoor Unit Model HSFI 1411 XRHSFI 1761 XR Power supply V - ph - Hz 220~

13 240-1-220~240-1- Outdoor Unit Model HC
240-1-220~240-1- Outdoor Unit Model HCSI 1413 XRHCSI 1762 XR Power supply V - ph - Hz -3--3- CoolingCapacitykw 4.107.60 Inputw 5 360 currentA 8.56.273.6011.57.204.3 .25 3 .28 HeatingCapacitykw 5.408.50 Inputw 4 960 currentA 8.486.192.089.637.062.37 COP.72 3 .73 Indoor fan motorModelYSK59-4 YSK59-4 Qty 2 2 Input W 102/98/96102/98/96 Capacitor 2.5uF/450V2.5uF/450V Speed(Hi/Mi/Lo)r/min1230/1130/10701230/1130/1070 Indoor coilNumber of rows3 3 Tube pitch(a)×row pitch(b) 25.4 x 2225.4 x 22 Fin spacing1.71.7 Fin type (code) Hydrophilic aluminumHydrophilic aluminum Tube outside dia. and typeФ9.53 Inner grooved copper tubeФ9.53 Inner grooved copper tube Coil length × height × width mm 1360 x 254 x 661360 x 254 x 66 Number of circuits5 5 Indoor air flow(Hi/Med/Lo) m 3 /h 2000/1800/16002000/1800/1600 Indoor noise level (Hi/Med/Lo) dB(A) 47/46/4447/46/44 Indoor unit Dimension (W×H×D) mm 1670 x 240 x 6801670 x 240 x 680 Packing (W×H×D) mm 1764 x 329 x 7601764 x 329 x 760 Net/Gro ss weight kg 52/5952/59 Refrigerant type R410AR410A Design pressure MPa 4.2/1.54.2/1.5 Refrigerant piping Liquid side/ Gas side mm Ф9.5/Ф15.9Ф9.5/Ф15.9 Drainage water pipe diameter mm ODφ25ODφ25 Controller R05/BGE (standard)R05/BGE (standard) Operation temperature Notes:Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal)Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal)Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. DimensionsHOKKAIDO DCInverter Commercial 2010 Ceiling & Floor Type 3.Dimensions a. Wall mounting installation b. Ceiling installation HOKKAIDO DCInverter Commercial 2010Dimensions Ceiling & Floor Type Capacity(Btu/h) A B C D E F G H 24000Btu/h 36000Btu/h1195 60000Btu/h Service SpaceHOKKAIDO DCInverter Commercial 2010 Ceiling & Floor Type 4.Service Space HOKKAIDO DCInverter Commercial 2010Wiring Diagrams Ceiling & Floor Type 5.Wiring DiagramsHSFI 351 XR Wiring DiagramsHOKKAIDO DCInverter Commercial 2010 Ceiling & Floor Type HSFI 531 XR HSFI 711 XR HSFI 1081 XR HSFI 1411 XR HSFI 1761 XR HOKKAIDO DCInverter Commercial 2010Air Velocity and Temperature Distributions Ceiling & Floor Type 6.Air Velocity and Temperature Distributions Discharge angle ° (CEILING) Airflow velocity Electronicexpansion valve Oil separator Compressor Low pressureswitch Oil return CapillaryHigh pressure switchLow pressure liquid accumulator Evaporator CapillaryOutdoor unitIndoor unit 4-way valve Condenser Discharge temp. sensor Filter Filter Condenser temp. sensor T3 T4 Ambient temp. sensorFilter Filter T2 Evaporator temp. sens

14 or Room temp. sensor Air Velocity and
or Room temp. sensor Air Velocity and Temperature DistributionsHOKKAIDO DCInverter Commercial 2010 Ceiling & Floor Type Discharge angle ° (FLOOR) Airflow velocity Temperature HOKKAIDO DCInverter Commercial 2010Electric Characteristics Ceiling & Floor Type 7.Electric CharacteristicsModel Indoor Unit Power Supply Hz Voltage Min Max MFA HSFI 351 XR 50 220~240 198 254 20 HSFI 531 XR 50 220~240 198 254 15 HSFI 711 XR 50 220~240 198 254 15 HSFI 1081 XR 50 220~240 198 254 15 HSFI 1411 XR 50 220~240 198 254 15 HSFI 1761 XR 50 220~240 198 254 15 emark: MFA: Max. Fuse Amps. (A) Sound LevelsHOKKAIDO DCInverter Commercial 2010 Ceiling & Floor Type 8.Sound Levels CeilingFloor ModelNoise level dB(A) H M L HSFI 351 XR37 HSFI 531 XR HSFI 711 XR HSFI 1081 XR HSFI 1411 XR HSFI 1761 XR HOKKAIDO DCInverter Commercial 2010Accessories Ceiling & Floor Type 9.Accessories .1 For 12kBtu/hInstallation fittingsNameShapeQuantity 1.Hook 2 2.Hanging arm 2 Remote controller & Its holder3. Remote controller 1 4. Remote controller holder 1 5. Mounting screw(ST2.9×10-C- 2 6. Alkaline dry batteries (AM 2 Others7. Owner's manual 1 8. Installation manual 1 9. Remote controller manual 1 The Specification of PowerHOKKAIDO DCInverter Commercial 2010 Ceiling & Floor Type 10.The Specification of Power HOKKAIDO DCInverter Commercial 2010Field Wiring Ceiling & Floor Type 11.Field Wiring Field WiringHOKKAIDO DCInverter Commercial 2010 Ceiling & Floor Type HOKKAIDO DCInverter Commercial 2010Field Wiring Ceiling & Floor Type onsoleTypeHOKKAIDO DCverter Commercial 2010 onsoleType onsoleType1. Features 732. Specifications743. Dimensions754. Service Space765. Wiring Diagrams776. Air Velocity and Temperature Distributions787. Electric Characteristics798. Sound Levels809. Accessories. 8110. The Specification of Power8211. Field Wiring83 HOKKAIDO DCInverter Commercial 2010Features Console Type 1.Features1.1. Consumes up to 30% less energy than noninverter unitsDC inverter compressorindoor fan motor adopts DC motor2. Achieves set temperature more quicklyair supplying from top and bottom or from top onlyair inlet from four directions3. Compact unitbody, space savingthis unit body is very thin and harmonious with room. It is beautiful, elegant and space saving.lightweight and compact.4. Flexible installation.can be used for floor standing or lower wall applicationsas a floor standing floor model, it can be semi or fully recessed without loss of capacity. 5. High efficiency filterbuilt in Formaldehyde nemesis filteractivecarbon and biological antivirus filter is optional.6. Comfort flexible air blow: vertical auto swing and wide angle louvers ensure that warm air reaches the furthest corners of the room and increase the air flow coverageLow noise operation, lowest to 23DbLow

15 starting power and precise room tempera
starting power and precise room temperature adjustment7. Powerful mode can be selected for rapid cooling or heating.8. Easy cleaning grille and maintenance9. Indoor unit adopts DC motor, it has five level fan speed meet different requirements. SpecificationsHOKKAIDO DCInverter Commercial 2010 onsoleType 2.SpecificationsIndoor Unit Model HFII 351 XRHFII 531 XR Power supply V - ph - Hz 220~240-1-220~240-1- Outdoor UnitModelHCKI 351 XRHCKI 532 XR Power supply V - ph - Hz 220~240-1-220~240-1- CoolingCapacitykw .50.30 Inputw 1 075 1 610 currentA 6.84.32.09.727.082.26 EER 3.2 6 3 .29 HeatingCapacitykw .00.90 Inputw 1 078 1 590 currentA 6.69 - 5.21 - 1.95 9.57.052.39 COP 3. 7 1 3 .71 Indoor fan motor Model RD - 280 - 20 - 8A RD - 280 - 20 - 8A Qty 1 1 Input W 18 28 Capacitor / / Speed(Hi/Mi/Lo) r/min 680/610/560/460/420 890/ 840/780/680/530 Indoor coilNumber of rows2 2 Tube pitch(a)×row pitch(b) mm 21x13.37 21x13.37 Fin spacing mm 1.3 1.3 Fin type (code) Hydrophilic aluminum Hydrophilic aluminum Tube outside dia. and type mm Ф7 Inner grooved copper tube Ф7 Inner grooved copper tube Coil length × height × width mm 512x378x26.74 512x378x26.74 Number of circuits 2 2 Indoor air flow(Hi/Med/Lo)550/(490)/460/380/350740/(700)/640/560/440 Indoor noise level (Hi/Med/Lo)dB(A)38/(35)/33/31/2844/(41)/39/37/34 Indoor unit Dimension (W×H×D) mm 700x600x210 700x600x210 Packing (W×H×D) mm 810x710x305 810x710x305 Net/Gross weightkg 15/2015/20 Refrigerant typeR410AR410A Design pressure MPa 4.2/1.54.2/1.5 Refrigerant piping Liquid side/ Gas sideφ6.4/φ12.7φ6.4/φ12.7 Drainage water pipe diameter mm ODφ16ODφ16 Controller R51D/E (standard)R51D/E (standard) Operation temperature Notes: 1.Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB;Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. HOKKAIDO DCInverter Commercial 2010Dimensions Console Type 3.DimensionsHFII 351 XRHFII 531 XR Service SpaceHOKKAIDO DCInverter Commercial 2010 onsoleType 4.Service Space HOKKAIDO DCInverter Commercial 2010Wiring Diagrams Console Type 5.Wiring DiagramsHFII 351 XRHFII 531 XR MAIN CONTROL BOARD LN ROOMPIPEWHITEBLACK CN7 Y/G COMM CN20 CN11 CN5CN1CN2CN14 CN15 CN101 SWITCH BOARD CN10 DISPLAY BOARDCN201 CN202 CN16 FAN TO WIRE CONTROLLER XS1-XS5XP1-XP5CN1-20RT2 RT1XT1FAN6-WAY TERMINALROOM TEMPERATUREPIPE TEMPERATURECONNECTORSCONNECTORSP.C BOARD SOCKETSWIRING DIAGRAMINDOOR UNITCODEPART NAMEINDOOR DC FAN MOTORUPPER OUTLET SWING MOTORXT1 CN13CN6 M1 M2 RT1RT2 JP1JUMPERLOWER OUTLET SWING MOTORTO OUTDOOR UNITFUNCTION OF

16 SWITCHES SWITCH BOARD TEMP.COMPENSATION6
SWITCHES SWITCH BOARD TEMP.COMPENSATION6℃4℃2℃0℃ TEMP. SW102 (FACTORY SETTING) FANMO/MUSW103 RESERVED THE SECOND STRONGEST LEVEL OF AIR FLOW RATE(FACTORY SETTING)(EFFECTIVE IN POWERFUL MODE)THE STRONGEST LEVEL OF AIR FLOW RATE NET MODULETO CCM Air Velocity and Temperature DistributionsHOKKAIDO DCInverter Commercial 2010 onsoleType 6.Air Velocity and Temperature DistributionsDischarge angle 60 Airflow velocity Temperature HOKKAIDO DCInverter Commercial 2010ElectricCharacteristics Console Type 7.Electric CharacteristicsModel Indoor Unit Power Supply Hz Voltage Min Max MFA HFII 351 XR 220~240V HFII 531 XR 220~240V Remark: MFA: Max. Fuse Amps. (A) Sound LevelsHOKKAIDO DCInverter Commercial 2010 onsoleType 8.Sound Levels ModelNoise level dB(A) HighestHigherH M L HFII 351 XR38 35 3 3 31 28 HFII 531 XR 3 9 3 7 34 HOKKAIDO DCInverter Commercial 2010Accessories Console Type 9.AccessoriesHFII 351 XRHFII 531 XR Name Shape Quantity Installation fittings Hook 2 Remote controller & Its Frame Remote controller 1 Frame 1 Mounting screw(ST2.9×10-C- 2 Alkaline dry batteries (AM4) 2 Others Installation manual / 1 Owner's manual / 1 The Specification of PowerHOKKAIDO DCInverter Commercial 2010 onsoleType 10.The Specification of Power HOKKAIDO DCInverter Commercial 2010Field Wiring Console Type 11.Field Wiring Field WiringHOKKAIDO DCInverter Commercial 2010 onsoleType Outdoor Units HOKKAIDO DCInverter Commercial 2010 Outdoor Units Part 3Outdoor Units 1. Specification872. Dimensions923. Service Space934. Piping Diagrams945. Wiring Diagrams956. Electric Characteristics997. Operation Limits108. Sound Levels1019. Troubleshooting102 HOKKAIDO DCInverter Commercial 2010Specification Outdoor Unit 1.SpecificationOutdoor Model name HCKI 351 XRHCKI 532 XR Power supply 220~240V1 Ph50Hz220~240V1 Ph50Hz Max. input consumptionW Max. currentA 7.013.1 CompressorModel DA108X1C - 20FZ3 C-6RVN93H0V Type Rotary DC InverterScroll DC Inverter Brand GMCC Shenyang SANYO CapacityBtu/h10918.419277.8 InputW 855 1470 Rated current(RLA)A 5.38.96 Refrigerant oil ESTER OIL VG74 480ml FV 50S, 350 Outdoor fanmotorModel YDK24YDK53 Qty 1 1 InputW 67/48 129/86 Capacitor / 3uF/450V Speedr/min800/550770/560 Outdoor coilNumber of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4×22 22×19.05 Fin spacing 1.4 1.4 Fin type (code) Hy drophilic aluminum Hydrophilic aluminum Tube outside dia.and typeФ9.53 Inner grooved copper tubeФ97.94 Inner gro

17 oved copper tube Coil length x height x
oved copper tube Coil length x height x width mm 654×558.8×44 778×660×38.1 Number of circuits 2 2 Outdoor air flow(Hi/Low) 2500/1600 2570/2300 Sound level(sound pressure)(Hi/Low)dB(A)48/4451/46 Outdoor unitDimension(W x D x 761×593×279 842×695×324 Packing (W x D x 887×655×355 965x752x399 Net/Gross weightkg 39.5/42.5 59/63 RefrigerantType R410AR410A Charged volumeg Throttle type CapillaryElectronic expansion valve & Capillary Design pressure(Hi/Low)MPa4.2/1.54.2/1.5 Refrigerant pipingLiquid side/ Gas sideФ6.4/Ф12.7Ф6.4/Ф12.7 Max. refrigerant pipe length m Max. difference in levelm 5 Ambient temp (Outdoor)Cooling5~43;Heating5~24Cooling15~43;Heating15~24 Notes: 1.Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB;Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. Specification HOKKAIDO DCInverter Commercial 2010 Outdoor Units OutdoorModel nameHCKI 712 XR Power supply220~240V1 Ph50Hz Max. input consumptionW Max. currentA 15.48 CompressorModel ATL165SDC9AU Type Rotary DC Inverter Brand HITACHI CapacityBtu/h InputW Rated current(RLA)A 10.4 Refrigerant oil68HESH,880 Outdoor fan motorModel YDK53 Qty 1 InputW 141.5/92 Capacitor3uF/450V Speed r/min815/550 Outdoor coilNumber of rows 2 Tube pitch(a)x row pitch(b)25.4 x 22 Fin spacing1.5 Fin type (code) Hydrophilic aluminum Tube outside dia.and typeФ9.53 Inner grooved copper tube Coil length x height x width758x813x44 Number of circuits 2 Outdoor air flow(Hi/Low)3200/2850 Sound level(sound pressure)(Hi/Low)dB(A)53/48 Outdoor unitDimension(W x D x 895×862×313 Packing (W x D x 1043×915×395 Net/Gross weightkg 73/76 RefrigerantType R410A Charged volumeg Throttle type Electronic expansion valve & Capillary Design pressure(Hi/Low)MPa4.2/1.5 Refrigerant pipingLiquid side/ Gas sideФ9.5/Ф15.9 Max. refrigerant pipe lengthm Max. difference in levelm Ambient temp (Outdoor)Cooling15~43; Heating15~24 Notes: 1.Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB;Nominal heating capacities are based on the following conditions:Indoortemp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. HOKKAIDO DCInverter Commercial 2010Specification Outdoor Units OutdoorModel nameHCSI 1083 XR Power supply38

18 0V~3 Ph50Hz Max. input consumptionW Max
0V~3 Ph50Hz Max. input consumptionW Max. currentA CompressorModel TNB306FPNM Type Rotary DC Inverter Brand MITSUBISHI ELECTRIC CapacityBtu/h InputW Rated current(RLA)A 9.3 Refrigerant oilFV50S, 870 Outdoor fan motorModel YDK250 Qty 1 InputW 307/194 Capacitor10uF±5% 450V Speedr/min740/530 Outdoor coilNumber of rows 2 Tube pitch(a)x row pitch(b)25.4×22 Fin spacing1.7 Fin type (code) Hydrophilic aluminum Tube outside dia.and typeФ9.53 Inner grooved copper tube Coil length x height x width876×914.4×44 Number of circuits 4 Outdoor air flow(Hi/Low)5000/4800 Sound level(sound pressure)(Hi/Low)dB(A)55/50 Outdoor unitDimension(W x D x 990×966×354 Packing (W x D x 1120×1100×435 Net/Gross weightkg 87/95 RefrigerantType R410A Charged volumeg Throttle type Electronic expansion valve & Capillary Design pressure(Hi/Low)MPa4.2/1.5 Refrigerant pipingLiquid side/ Gas sideФ9.5/Ф15.9 Max. refrigerant pipe lengthm Max. difference in level m Ambient temp (Outdoor)Cooling15~43Heating15~24 Notes: 1.Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB;Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. Specification HOKKAIDO DCInverter Commercial 2010 Outdoor Units OutdoorModel nameHCSI 1413 XR Power supply380V~3 Ph50Hz Max. input consumptionW Max. currentA CompressorModel TNB306FPNM Type Rotary DC Inverter Brand MITSUBISHI ELECTRIC CapacityBtu/h InputW Rated current(RLA)A 9.3 Refrigerant oilFV50S, 870 Outdoor fan motorModel YDK100 Qty 2 InputW 185/120 Capacitor3.5uF/450V Speedr/min860/610 Outdoor coilNumber of rows 2 Tube pitch(a)x row pitch(b)25.4×22 Fin spacing1.7 Fin type (code) Hydrophilic aluminum Tube outside dia.and typeФ9.53Inner grooved copper tube Coil length x height x width887×1220×44 Number of circuits 8 Outdoor air flow(Hi/Low)6000/5800 Sound level(sound pressure)(Hi/Low)dB(A)59/54 Outdoor unitDimension(W x D x 940×1245×360 Packing (W x D x 1058×1380×438 Net/Gross weightkg 99/107 RefrigerantType R410A Charged volumeg Throttle type Electronic expansion valve & Capillary Design pressure(Hi/Low)MPa4.2/1.5 Refrigerant pipingLiquid side/ Gas sideФ9.5/Ф15.9 Max. refrigerant pipe lengthm Max. difference in levelm Ambient temp (Outdoor)Cooling15~43Heating15~24 Notes: 1.Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB;Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7Â

19 °CDB, 6°CWB; Actual noise level may dif
°CDB, 6°CWB; Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. HOKKAIDO DCInverter Commercial 2010Specification Outdoor Units OutdoorModel nameHCSI 1762 XR Power supply380~415V3 Ph50Hz ax. input consumptionW Max. currentA CompressorModel ANB42FBEMT Type Scroll DC Inverter Brand MITSUBISHI CapacityBtu/h InputW Rated current(RLA)A 15.2 Refrigerant oilMEL 56, 1700 Outdoor fan motorModel YDK100 Qty 2 InputW 185/120 Capacitor3.5uF/450V Speedr/min860/610 Outdoor coilNumber of rows 3 Tube pitch(a)x row pitch(b)25.4× 22 Fin spacing1.5 Fin type (code) Hydrophilic aluminum Tube outside dia.and typeФ9.53 inner grooved copper tube Coil length x height x width87×1220×66 Number of circuits 8 Outdoor air flow(Hi/Low)6000/5800 Sound level(sound pressure)(Hi/Low)dB(A)59/54 Outdoor unitDimension(W x D x 940×1245×360 Packing (W x D x 1058×1380×438 Net/Gross weightkg 124/130 RefrigerantType R410A Charged volumeg Throttle type Electronic expansion valve & Capillary Design pressure(Hi/Low)MPa4.2/1.5 Refrigerant pipingLiquid side/ Gas sideФ9.5/Ф15.9 Max. refrigerant pipe lengthm Max. difference in levelm 25 Ambient temp (Outdoor)Cooling15~43Heating15~24 Notes: 1.Nominal cooling capacities are based on the following conditions:Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB;Nominal heating capacities are based on the following conditions:Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. Dimensions HOKKAIDO DCInverter Commercial 2010 Outdoor Units 2.Dimensions Unit MODEL A B C D E F H HCKI 351 XR 761 530 290 315 270 279 593 HCKI 532 XR 842 560 335 360 312 324 695 HCKI 712 XR 895 862 313 355 302 80 862 HCSI 1083 XR 990 624 366 396 340 354 966 HCSI 1413 XR 940 600 376 400 340 360 1245 HCSI 1762 XR 940 600 376 400 340 360 1245 HOKKAIDO DCInverter Commercial 2010Service Space Outdoor Units 3.Service Space Piping Diagrams HOKKAIDO DCInverter Commercial 2010 Outdoor Units 4.Piping DiagramsHCKI 351 XR CompressorOutdoor unit 4-way valve Condenser Indoor unit Capillary ass'y Evaporator HCKI 532 XR HCKI 712 XR T1 Room temp. sensor T2 Evaporator temp. sensorAmbient temp. sensor T

20 3 Condenser temp. sensor FilterFilter Di
3 Condenser temp. sensor FilterFilter Discharge temp. sensorCompressorElectronic expansion valve Evaporator Capillary Indoor unit 4-way valveHigh pressure switch Outdoor unit Condenser Low pressure switchLow pressure liquid accumulator HCSI 1083 XR HCSI 1413 XR HCSI 1762 XR Electronicexpansion valve Oil separator Compressor Low pressureswitch Oil return CapillaryHigh pressure switchLow pressure liquid accumulator Evaporator CapillaryOutdoor unitIndoor unit 4-way valve Condenser Discharge temp. sensor Filter Filter Condenser temp. sensor T3 T4 Ambient temp. sensorFilter Filter T2 Evaporator temp. sensor Room temp. sensor HOKKAIDO DCInverter Commercial 2010Wiring Diagrams Outdoor Units 5.Wiring DiagramsHCKI 351 XR Wiring Diagrams HOKKAIDO DCInverter Commercial 2010 Outdoor Units HCKI 532 XRHCKI 712 XR HOKKAIDO DCInverter Commercial 2010Wiring Diagrams Outdoor Units HCSI 1083 XRHCSI 1413 XR Wiring Diagrams HOKKAIDO DCInverter Commercial 2010 Outdoor Units HCSI 1762 XR HOKKAIDO DCInverter Commercial 2010Electric Characteristics Outdoor Units 6.Electric CharacteristicsModelOutdoor UnitPower Supply VoltageMin.Max.MFA HCKI 351 XR HCKI 532 XR 50 220-240 198 254 30 HCKI 712 XR HCSI 1083 XR HCSI 1413 XR HCSI 1762 XR Remark: MFA: Max. Fuse Amps. (A) Operation Limits HOKKAIDO DCInverter Commercial 2010 Outdoor Units 7.Operation LimitsAll models except HCKI 351 XR combinations HOKKAIDO DCInverter Commercial 2010Sound Levels Outdoor Units 8.Sound LevelsModelNoise level dB(A) H/L HCKI 351 XR48/44 HCKI 532 XR 51/46 HCKI 712 XR53/48 HCSI 1083 XR55/50 HCSI 141359/54 HCSI 1762 XR59/54 Troubleshooting HOKKAIDO DCInverter Commercial 2010 Outdoor Units 9.Troubleshooting9.1 Indoor unit malfunction.1.1 Display boardCompact 4way cassetteCeiling & Floor Normal 4way cassetteDuct HOKKAIDO DCInverter Commercial 2010Troubleshooting Outdoor Units

21 .1.2 Troubleshoot
.1.2 Troubleshootingor Normal 4way cassetteFor compact 4waycassette(12K) Troubleshooting HOKKAIDO DCInverter Commercial 2010 Outdoor Units For compact 4waycassette(18K)&ceiling & floor &High static duct unitFor Duct type HOKKAIDO DCInverter Commercial 2010Troubleshooting Outdoor Units Troubleshooting HOKKAIDO DCInverter Commercial 2010 Outdoor Units 1. Operation lamp flashes Operation lamp flashes at 5Hz Judge 1: Indoor temp. sensor is abnormal Check whether the resistance of the evaporator temp. sensor is correct according to Annex 1 Judge 2: Room temp. sensor is abnormal Replace evaporator temp. sensor No Yes Check whether the resistance of the room temp. sensor is correct according to Annex 1 Replace room temp. sensor No Replace indoor PCB Yes HOKKAIDO DCInverter Commercial 2010Troubleshooting Outdoor Units 2. Timer lamp flashes3. Alarm lampslowflash Timer lamp flashes at 5Hz Judge: Indoor/outdoor unit communication is abnormal Refer to the outdoor unit LED display E2 malfunc tion in the following part Indoor alarm lamps flash at 1Hz Judge 1: Condenser temp. sensor is abnormal Check whether the resistance of the condenser temp. sensor is correct according to Annex 1 Judge 2: Outdoor unit is abnormal Refer to the outdoor unit LED display E4malfunctionin the following part Replace condenser temp. sensor No Yes Condenser temp. sensor or outdoor unit is malfunction Troubleshooting HOKKAIDO DCInverter Commercial 2010 Outdoor Units 4. Alarm lamp quickflash5. Defrost lamp flashes Alarm lamp flashes at 5Hz Judge: Water level switch is abnormal. Select the cooling mode to make water pump work for a few minutes, then check whether the system can run normally Replace indoor PCB Trouble is solved Yes No Check whether the water drain pipe is blocked No olve to make the water can flow fluently Yes Check whether the water pump can work normally Replace water pump No Yes Defrost lamp flashes Judge: Mode conflict s malfunction Turn the indoor unit to heating mode or turn off the u HOKKAIDO DCInverter Commercial 2010Troubleshooting Outdoor Units .2 Outdoor unit malfunctionDisplayMalfunction

22 or Protection EEPROM malfunction Commun
or Protection EEPROM malfunction Communication malfunction between indoorIC and outdoor Communication malfunction in outdoor IC and DSP alfunctionof outdoor temperature sensor oltage protectionof compressor PFC module protection (Only for 30K, 36K & 48K with 1 phase) Top temperature protection of compressor High pressure protection Low pressure protection urrent protectionof compressor ischarge temperature protectionof compressor igh temperature protectionof condenser Moduleprotection 1. E0 malfunction display EEPROM alfunction Judge: Check whether the EEPROM is inserted well Yes No Insert the EEPROM well Replace outdoor main board Troubleshooting HOKKAIDO DCInverter Commercial 2010 110 Outdoor Units 2. E2 malfunction 2 display Communication malfunction between indoorIC and outdoor udge 3: Check whether the signal wiring betweenthe indooroutdoor unitsis wrong polarity? Connect the signal wiring correctly Yes No udge 4: Check whether the signal wiring betweenthe indooroutdoor unitsis broken? Yes Replace the broken wiring No udge 2: Check whether the signal wiring is shield cable or whether the shield cable is earthed Yes Adopt the shield cable/ let shield cable earthed No Indoor or outdoor main board is broken. Replace the main board until the malfunction disappear udge 1: Check whether the indoor unit power is on Turn on the indoor unit power No Yes HOKKAIDO DCInverter Commercial 2010Troubleshooting Outdoor Units 3. E3 malfunction(For 18K & 24K & 30K) Check whether the indicator lights LED1on the main board is flashing Check whether the connecting wiring between the IPM module and the CN4 on the main board is broken off Check whether the connecting wiring betweenthe IPM module positive pole and the CN12 on the power board is brokenoff Use the multimeter to measure whether the voltage between the CN12 and the CN13 on the power board is between +277V~345V Check whether the connecting wiring between the IPM module negative pole and the CN13 on the power board is brokenoff 3 display Communication malfunction in outdoor IC and DSP Replace the outdoor main board Yes Insert the connecting wiring well over again Yes No No Replace outdoor main board Yes No Insert the connecting wiring well over again Yes No No Replace the IPM module Yes Replace thepower board No Insert the connecting wiring well over again Yes D isconnect the connecting wiring between the IPM module and the CN4 on the main board, use the multimeterto measure the voltagebetween the IPM module CN1s 3 and 4 pillar, check whether it is 5V, (the third pillar on the main bo

23 ard labels +5V) Troubleshooting
ard labels +5V) Troubleshooting HOKKAIDO DCInverter Commercial 2010 112 Outdoor Units 4. E3 malfunction(For 36K & 48K & 60K) 3 display Communication malfunction in outdoor IC and DSP Check whether the indicator lights LED1 or LED2 on the main control board are flashing Replace PCB Yes Install the ICU3 chip of the PCB over again, check whether the system can run normally Trouble is solved Yes No Check whether the output of the transformer to CN4 socket is well No Replace PCB Yes No Replace the transformer HOKKAIDO DCInverter Commercial 2010Troubleshooting Outdoor Units 113 5. E4 malfunction 4 display Check whether the wiring of the outdoor ambient temperature sensor ( T4 ) is broken off Replace PCB J udge 1 : Outdoor condenser temp. s ensor ( T3) is malfunction Check whether the wiring of the condenser te mp. s ensor is broken off Connect the wiring well Yes No Check whether the resistance of condenser temp. s ensor is wrong refer to the Annex 1 Yes Replace condenser temp. s ensor No J udge 2 : Outdoor a mbient temp. s ensor ( T4) is malfunction Connect the wiring well Yes No Check whether the resistance of outdoor ambient temperature sensor ) is wrong refer to the Annex 1 Yes Replace outdoor ambient temperature sensor ) No Troubleshooting HOKKAIDO DCInverter Commercial 2010 114 Outdoor Units 6. E5 malfunction7. E6malfunction(Only for 30K, 36K & 48K with 1 phase) 5 display oltage protectionof compressor Check the voltage of outdoor unit power supply, whether the voltage between L(1) and N is about 172 No Replace the power board , then check whether the system can run normally Check the power supply Yes Replace outdoor main board Yes Trouble is solved No E6 display PFC module protection Check whether the connecting line between main board and the PFC module is connected tightly No Connect it tightly, check normal or not Yes Check whether the vol tage between P and N of IPM module is 380 No Yes Replace the outdoor main board No Replace the PFC module HOKKAIDO DCInverter Commercial 2010Troubleshooting Outdoor Units 115 8. P1malfunction P1 display High pressure protection J udge 1 : Whether the wiring between the high pressure switch and main control board is connected well or correctly udge 2: Whether the high pressure switch isbroken Yes No Conn

24 ect it well Method: Short connect the hi
ect it well Method: Short connect the high pressure switch socket , check whether the system can run normally Yes Replace high pressure switch No Check whether the refrigerant system is ok Replace outdoor main board No J udge 3: Check whether the outdoor ambient temperature is too high Yes Stop the unit No J udge 4: Check whether the outdoor unit is bad ventilation Yes Make the outdoor unit ventilate well No J udge 5: Check whether the h e at exchanger is dirty Yes Clean the h eat exchanger No J udge 6: Check whether the refrigerant pipe is blocked Yes Let th e refrigerant out, then use the high pressure nitrogenor refrigerantto blow pipe, vacuumize charge the refrigerant again Troubleshooting HOKKAIDO DCInverter Commercial 2010 116 Outdoor Units 9. P2malfunction P2 display pressure protection J udge 1 : The wiring between the low pressure switch and main control board is connected well or correctly udge 2: Whether the low pressure switch is broken Connect it well Method: Short connect the low pressure switch socket , check whether the system can run normally Check whether the refrigerant system is ok Yes No J udge 3: Check whether the outdoor ambient temperature is too low Yes Stop the unit No J ud ge 4: The refrigerant of the system is leakage Yes Method: Connect the pressure gauge to the gauge joint of the system, check whether the pressure is lower than 0.14MPa Leak hunting: C harge nitrogen or refrigerant to the system, if the leakage is serious, there will be distinct gas leakage “cici” sound; if thleakage is slight, use the suds(mixture of water and abluent is also if it can make bubble) orelectronic leak detector. J udge 5: The refrigerant pipe is blocked Yes Let the refrigerant out, then use the high pressure nitrogenor refrigerantto blow pipe, vacuumize charge the refrigerant again No Replace outdoor main board No No Yes Replace low pressure switch HOKKAIDO DCInverter Commercial 2010Troubleshooting Outdoor Units 117 10. P3malfunction P3 display Current protection of compressor J udge 1: Check whether the input current of the power supply wire is more than 20A (For 36K & 48K with 1 phase, it is 30A) Check whether the refrigerant system is ok Yes J udge 2: Check whether the outdoor ambient temperature is too high Yes Stop the unit Replace outdoor main board No No J udge 3: Check whether the outdoor unit is bad ventilation Yes Make the outdoor unit ventilate well No J udge 4: Check whether the h eat exchanger is dirty

25 Yes Clean the h eat exchanger No
Yes Clean the h eat exchanger No J udge 5: The refrigerant pipe is blocked Yes Let the refrigerant out, then use the high pressure nitrogenor refrigerantto blow pipe, vacuumize charge the refrigerant again Troubleshooting HOKKAIDO DCInverter Commercial 2010 118 Outdoor Units 11. P4malfunctionWhenompressor discharge temperature is higherthan 15°C, the unit will stop, and unit runs again when ompressor discharge temperature islowerthan 90°C. P4 display scharge temperature protectionof compressor Check whether the c ompressor discharge temp. is more than 115 ° C ? No Check whether the wiring connection is right between compressor discharge temp. sensor and PCB according to wiring diagrams Yes Method: Check whether the resistance of c ompressor discharge temp. sensor is right refer to the Annex 2 No Correct the wiring connection Yes Replace outdoor main board Judge: The discharge temp. sensor is broken No R eplace the c ompressor discharge temp. sensor Check whether the refrigerant is leak Stop leaking and add refrigerant Yes Yes HOKKAIDO DCInverter Commercial 2010Troubleshooting Outdoor Units 119 12. P5malfunctionWhen ondenser high temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52°C. Clean the h eat exchanger P5 display igh temperature protectionof condenser Check whether the condenser temperature is more than 65 °C No Check whether the resistance of condenser temp. sensor is correct refer to the Annex 1 Yes Replace outdoor main board No R eplace the temperature sensor Yes Judge1: The outdoor temp. is too high Replace outdoor main board No J udge 2: Check whether the h eat exchanger is dirty No J udge 3: The refrigerant pipe is blocked Clean the h eat exchanger Yes Yes Let the refrigerant out, then use the high pressure nitrogenor refrigerantto blow pipe, cuumize charge the refrigerant again Yes Stop the unit No Troubleshooting HOKKAIDO DCInverter Commercial 2010 Outdoor Units 13. P6malfunction(For single phase units) P6 display Module protection Check whether the voltage range of P - N on IPMmodule is normal? DC277356V for 18K/24K/30KBtu/h; DC277410V for 36K/48KBtu/h No Check whether the input power supply is correct? 220240V, 1N, 50Hz No Regulate it to correct , then check whether the system can work normally? Yes Check whether the power supply line is connected correctly and tightl

26 y No Connect it correctly and tightly
y No Connect it correctly and tightly, check ok or not? No Yes Check whether the lines in E-part boxare connected tightly No Connect it tightly, check ok or not? No Yes Check whether the single - phase bridge is normal? Use the multimeterto measure the resistance between each two terminals, check whether there is the condition that value of resistance is 0 Yes Replace the singlephase bridge No No Check whether the connecting line of every reactor is normal?If the line is broken, the resistance of the two ports is No Replace the connecting line Yes Check whether the connecting line between main board and the IPM module is connected tightly Yes Check whether the connecting line of the compressor is connected correctly or tightly Yes Replace the IPM module, check whether the system can work normally? No Replace the main board, check whether the system can work normally? Yes Trouble is solved No Rep lace the compressor, check whether the system can work normally? Connect it tightly, check ok or not? No No Yes Trouble is solved No No Yes Trouble is solved Yes Check whether the fuse on the power board is normal? No Replace with the same model fuse Yes Replace the power board Connect it well, check ok or not? HOKKAIDO DCInverter Commercial 2010Troubleshooting Outdoor Units 14. P6malfunction(For three phases units) P6 display Module protection Check whether the voltage range of P - N on IPM module is normal? DC 350 No Check whether the input power supply is correct? 380415V, 3N, 50Hz No Regulate it to correct , then check whether the system can work normally? Yes Check whether the power supply line is connected correctly and tightly No Connect it correctly and tightly, check ok or not? No Yes Check whether the lines in E-part boxare connected tightly No Conne ct it tightly, check ok or not? No Yes Check whether the t hree phase bridge is normal? No Replace the t hree phase bridge No Yes Check whether the 3300µF /400V lectrolytic capacitoris normal? No Replace th is e lectrolytic capacitor Yes Check whether the connecting line between main board and the IPM module is connected tightly Yes Check whether the connecting line of the compressor is connected tightly Yes Replace the IPM module, check whether the system can work normally? No Replace the main board, chec k whether the system can work normally? Yes Trouble is solved No Replace the compressor , check whether the system can work normally? Yes Trouble is solved Connect it tightly, check ok or not? No Connect it tightly, check ok or not? No Yes Trouble is solved Troubleshooting HOKKAIDO DCInverter Commercial 2010

27
Outdoor Units AppendixIndoor Temp. and Pipe Temp. Sensor Resistance Value Table ( K Ohm K Ohm K Ohm K Ohm 115.26612.64312.357740.62973 108.14612.05612.272490.61148 101.51711.50002.190730.59386 96.342310.97312.112410.57683 89.586510.47362.037320.56038 84.219010.0001.965320.54448 79.31109.550741.896270.52912 74.53609.124451.830030.51426 70.16988.719831.766470.49989 66.08988.335661.705470.48600 62.27567.970781.646910.47256 -9 58.70797.624111.590680.45957 -8 56.36947.294641.536680.44699 -7 52.24386.981421.484810.43482 -6 49.31616.683551.434980.42304 -5 46.57256.400211.387030.41164 -4 44.00006.130591.341050.40060 -3 41.58785.873591.290780.38991 -2 39.82395.629611.254230.37956 -1 37.19885.396891.213300.36954 0 35.20245.175191.173930.35982 1 33.32694.963921.136040.35042 2 31.56354.762531.099580.3413 3 29.90584.570501.064480.33246 4 28.34594.387361.030690.32390 5 26.87784.212630.998150.31559 6 25.49544.045890.966810.30754 7 24.19323.886730.936620.29974 8 22.56623.734760.907530.29216 9 21.80943.589620.879500.28482 20.71843.450970.852480.27770 19.68913.318470.826430.27078 18.71773.19183.801320.26408 17.80053.070750.777090.25757 16.93412.958960.753730.25125 16.11562.844210.731190.24512 15.34182.738230.709440.23916 14.61812.636820.688440.23338 13.91802.539730.668180.22776 13.26312.446770.648620.22231 InstallationHOKKAIDO DCInverter Commercial 2010 Installation Part 4Installation 1.Precaution on Installation1252.Vacuum Dry and Leakage Checking1263.Additional Refrigerant Charge1284.Water Drainage1295.Insulation Work1326.Wiring1337.Test Operation134 HOKKAIDO DCInverter Commercial 2010Precaution on Installation Installation 1.Precaution on Installation1).Measure the necessarylength of the connecting pipe, and make it by the following way.Connect the indoor unit at first, then the outdoor unit.Bend the tubing in properway. Do not harm them.Specially Notice the pipe length/height/dimension of each capacity.Maximum pipe length Model Max. Length Max. Elevation 12,000Btu/h 1 0 m 5 m 18,000Btu/h ~24,000Btu/h 25 m 1 2 m 36 ,000Btu/h 30 m 2 0m 48 ,000Btu/h ~60,000Btu/h 5 0m 2 5m Piping sizes Model Liquid(mm) Gas( mm) 12,000Btu/h~18,000Btu/h 6. 4 12.7 24,000Btu/h ~ 6 0 ,000Btu/h 9.515.9 CAUTIONSDaub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds With hands before fasten the flare nuts. Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.Pipe gaugeTightening torqueFlare dimension AMin (mm) MaxFlare shape Φ6.4 4.27.2N.m (1 44 1 76 kgf.cm) 8.38.7 Φ9.5 32.739.9N.m ( 333 407 kgf.cm) 12.012.4 Φ12.749.560.3N.mkgf.cm)15.415.8 Φ15.9 61.8 7 5.4 N.m 0 kgf.cm) 18.619.1 Φ19.197.2118.6N.mkgf.cm)22.923.3 The stop value of the outdoor unit should be closed absolutely (as original state). Every time you

28 connect it, first loosen the nuts at the
connect it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before connection.Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Thenfasten the nuts at the repairpoints.Locate The PipeDrill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover.Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by condensation.Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing.Connect the pipes. Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in fluent flow.Be sure of no leakage by checking it with leak detector or soap water.Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage. Vacuum Dry and Leakage CheckingHOKKAIDO DCInverter Commercial 2010 Installation 2.Vacuum Dry and Leakage CheckingVacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out of the pipe to make the pipe dry. Under one atmospheric pressure, the boiling point of water(steam temperature) is 100. Use vacuum pump to make the pressure in the pipe near vacuum state, the boiling point of water falls relatively. When it falls under outdoor temperature, the moisture in the pipe will be vaporized. Necessary vacuum degree Vacuum dry procedureThere are two methods of vacuum dry due to different construction environment: common vacuum dry, special vacuum dry.Common vacuum dry procedure Vacuum dry (for the first time)connect the allpurpose detector to the inlet of liquid pipe and gas pipe, and run the vacuum pump more than two hours (the vacuum pump should be below 755mmHg)If the pump can’t achieve below 755mmHg after pumping 2 hours, moisture or leakage point will still exist in the pipe. At this time, it should be pumped 1 hour more.If the pump can’t achieve 755mmHg after pumping 3 hours, please check if there are some leakage points.Vacuum placement test: place 1 hour when it achieves 755mmHg, pass if the vacuum watch shows no rising. If it rises, it shows there’s moisture or leakage point.Vacuuming from liquid pipe and gas pipe at the same time.Sketch map of common vacuum dry procedure. HOKKAIDO DCInverter Commercial 2010Vacuum Dry and Leakage Checking Installation . Special vacuum dry procedure This vacuum dry method is used in the following conditions:There’s

29 moisture when flushing the refrigerant
moisture when flushing the refrigerant pipe.Rainwater may enter into the pipe.Vacuum dry for the first time ······ 2h pumpingVacuum destroy for the second time ······ Fill nitrogen to 0.5Kgf/cmBecause nitrogen is for drying gas, it has vacuum drying effect during vacuum destroy. But if the moisture is too much, this method can’t dry thoroughly. So, please pay more attention to prevent water entering forming condensation water. . Vacuum dry for the second time······1h pumpingDeterminant: Pass if achieving below 755mmHg. If 755mmHg can’t be achieved in 2h, repeat procedure . Vacuum placing test ······ 1h. Sketch map of special vacuum dry procedure Additional Refrigerant ChargeHOKKAIDO DCInverter Commercial 2010 Installation 3.AdditionalRefrigerant harge Caution Refrigerant cannot be charged until field wiring has been completed.Refrigerant may only be charged after performing the leak test and the vacuum pumping.c) When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer.Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant is charged.Refrigerant containers shall be opened slowly. f)Always use protective gloves and protect your eyes whencharging refrigerant.The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the diameter and the lenth of the liquid side pipe of the outdoor unit/indoor unit. R(g) D(mm) L(m) φ6.4Φ9.5Φ12.7 Less than 5m (Oneway)— — — Added Refrigerant When Over 5m(One - way) g/m×(Lg/m×(L-5) g/m×(L Remark:R (g): Additional refrigerant to be chargedL (m): The length of the refrigerant pipe(oneway)D (mm): Liquid ide iping iameter HOKKAIDO DCInverter Commercial 2010Water Drainage Installation 4.Water rainage4.1Gradient and Supporting 1).Keep the drainpipe sloping downwards at a gradient of at least 1/0. Keep the drainpipe as short as possible and eliminate the air bubble. 2).The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/0 and prevent bending. Refer to the following table for the specification of the prop stand. Diameter Distance between the prop stands Hard PVC pipe 25~40mm 1 .5 ~ 2 m 3).Precautions The diameter of drainpipe should meet the drainage requirement at least. the drainpipe should be heatinsulated to prevent atomization. Drainpipe should be installed before installing indoor unit. After powering on, there is somewater in waterreceiver plate. Please check if the drain pump can operate correctly. All connection should be firm. Wipe color on PVC pipe to note connection. Climbing, horizontal and bending conditions are prohibited.The dimension of drainpipe can’t less than the connecting dimensio

30 n of indoor drainpipe. Heatinsulation sh
n of indoor drainpipe. Heatinsulation should be done well to prevent condensation.Indoor units with different drainage type can’t share one convergent drainpipe.4.2Drainpipe Trap 1).If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap.2).Every indoor unit needs one drainpipe trap.3).A plug should be designed to do cleaning. Plug 4.3Upwards drainage(drain pump)For Fourway cassette(compact) Water DrainageHOKKAIDO DCInverter Commercial 2010 Installation For Fourway cassette4.4Convergent drainage1).The number of indoor units should be as small as possible to prevent the traverse main pipe overlong.2).Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system.3).Selecting the diameterNumber of connecting indoor unitsCalculate drainage volumeSelect the diameterCalculate allowed volume =Total cooling capacity of indoor units(HP)×2 (l/ hr) 集中水管 Allowed volume ( lean 1/ 5 0) (l/ hr) I.D. (mm) Thick H ard PVC 14 25 3.0 Hard PVC 88 3.5 Hard PVC 88334 40 4.0 Hard PVC 175 334 50 4.5 Hard PVC 334 80 6.0 4.5Drainage test1).Drainage without drain pump After finishing drainpipe installation, pour some water into the water receiver plate to check if the water flows smoothly.2).Drainage with drain pump Poke the Water Level Switch, remove the cover, use water pipe to pour 2000ml water into the water receipt plate through the water inlet. Turn on the power to Cooling operation. Check the pump’s operation and switch on the Water Level Switch. Check the pump’s sound and look into the transparent hard pipe in the outlet at the same time to check if the water can discharge normally. HOKKAIDO DCInverter Commercial 2010Water Drainage Installation Stop the air conditioner running, turn off the power, and put back the cover.Stop the air conditioner. After 3 minutes, check if it has abnormity. If the collocation of drainpipes is illogical, the water will flow back overfull, which will cause the alarm lamp flashes, even overflow from the water receipt plate.Keep on pouring water until it gives an alarm signal for high water level, check if the pump drains water at once. If the water level can’t fall below the alarmed water level after 3 minutes, the air conditioner will stop. Turn off the power and drain the remained water, and then turn on the air conditioner.Note:the drain stuff in the main water receipt plate is for maintenance. Stuff up the drain stuff to prevent water leakage. Insulation WorkHOKKAIDO DCInverter Commercial 2010 Installation 5.Insulation ork 5.1Insulation material and thickness1).Insulation materialInsulation material should adopt the material which is able to endure the pipe’s temperature: no less than 70 in the highpressure side, no less than 120 in the lowpressure side(For the cooling type machine, no requirements at the low

31 pressure side.)ample: Heat pump typeHeat
pressure side.)ample: Heat pump typeHeatresistant Polyethylene foam (withstand above 120Cooling only typePolyethylene foam (withstand above 100) 2).Thickness choice for insulation materialInsulation material thickness is as follows: Pipe diameter (m m) Adiabatic material thickness Refrigerant pipeΦ6.4Φ25.410mm Φ28.6Φ38.115mm Drainage pipe Inner diameterΦ20Φ326mm 5.2 Refrigerant pipe insulation1).Work Procedure Before laying the pipes, the nonjointing parts and nonconnection parts should be heat insulated. When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat insulated2).Insulation for nonjointing parts and nonconnection partswrongright Gas pipe and liquid pipe shouldnot be put together to insulateInsulate the gas pipe(cooling only)Insulate the gas pipe andliquid pipe HOKKAIDO DCInverter Commercial 2010nsulation ork Installation For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with, at the sametime, at two ends of the pipe, remain some length not to be insulated, in order to be welded and check the leakage after laying the pipes.3).Insulate for the jointing area, expanding area and the flange area Insulate for the jointing area, expanding area and the flange area should be done after checking leakage of the pipes Make sure there’s no clearance in the joining part of the accessorial insulation material and local preparative insulation material. 5.3Drainage pipe insulationThe connection part should be insulated, or else water will be condensing at the noninsulation part.5.4NoteThe jointing area, expanding area and the flange area should be heat insulated after passing the pressure teThe gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually.Use the attached heatinsulation material to insulate the pipe connections (pipes’ tiein ,expand nut ) of the indoor unit.6. WiringPlease refer to the Wiring Diagram. Test OperationHOKKAIDO DCInverter Commercial 2010 Installation 7.Test peration (1) The test operation must be carried out after the entire installation has been completed.(2) Please confirm the following points before the test operation. The indoor unit and outdoor unit are installed properly.Tubing and wiring are correctly completed.The refrigerant pipe system is leakagechecked.The drainage is unimpeded.The ground wiring is connected correctly.The length of the tubing and the added stow capacity of the refrigerant have been recorded.The power voltage fits the rated voltage of the air conditioner.There is no obstacle at the outlet and inlet of the outdoor and indoor units.The gasside and liquidside stop values are both opened.The air conditioner is preheated by turning on the power.(3) According to the user's requirement, install the remote controller when the remote controller's s

32 ignal can reach the indoor unit smoothly
ignal can reach the indoor unit smoothly.(4) Test operationSet the air conditioner under the mode of "COOLING" with theremote controller, and check the following points.Indoor unitWhether the switch on the remote controller works well.Whether the buttons on the remote controller works well.Whether the air flow louver moves normally.Whether the room temperature is adjusted well.Whether the indicator lights normally.Whether the temporary buttons works well.Whether the drainage is normal.Whether there is vibration or abnormal noise during operation.Outdoor unitWhether there is vibration or abnormal noise during operation.Whether the generated wind, noise, or condensed of by the air conditioner have influenced yourneighborhood.Whether any of the refrigerant is leaked. HOKKAIDO DCInverter Commercial 2010Control Control Part 5Control 1. Wireless Remote Controller136 Wireless Remote ControllerHOKKAIDO DCInverter Commercial 2010 Control 1.Wireless Remote Controller1.1 R11HG/EAfter Sliding the cover, the button and function are as follows: I/O ButtonTemperature Button Each time you push button, a mode is selected in a sequencethat goes from AUTO,COOL, DRY, HEAT (cooling only type without), FAN ONLY andback to AUTO.the Push the button to start operation, push thebutton again to stopoperation.This button is usedfor selecting fan speed.Each time you pushthe button, a fan speedisselectedinasequencethat goes from AUTO,LOW, MED(Some modelswithout, HIGH, and back toAUTO. Mode select button Fan button This button is used forsetting the current timeand OFF time.Adjust forwardsAdjust backwordsPush this button to cancel ON timer and OFF timer.When you push the RESET button, all current settingsare cancelled and get intothe condition of beginning.In the clock, the colon in"0:00" will flash, the modedisplays"AUTO",fanspeed displays "AUTO", thetemperature displays "24". Push ON-TIME timerbutton to set the ON timer.Push OFF-TIME timerbutton to set the OFF timer. Auto louver buttonPush this button to swinglouver. Push the buttonagain to stop.Push this button to confirmON and OFF timer settings.Confirmation buttonClock buttonPush this button to settime.When you push the LOCKbutton, all current settings are locked in and the remotecontroller does not acceptany operation except that ofthe LOCK button. Use the lock mode when you want toprevent setting from beingchanged accidentally or playfully. Push the LOCK button again when you want to cancel the LOCK mode. FANTimer buttonRESET buttonLock button HOKKAIDO DCInverter Commercial 2010Wireless Remote Controller Control 2 R05BGEThe R05E wireless remote controlleris for Fway cassette type and the eiling& floor type. Mode setting ON/OFF Horiz swing Time setting Air direction setting Vert. swing Time OFF Time ON Adjust Fan speed setting Adjust 13 Cool/heatLockReset Confirm button Economic operation TIME ONTIME OFFCLOCKSWINGAIR DIRECTIONECOSWINGMODE FAN SPE

33 ED 1.3 General Function for wireless rem
ED 1.3 General Function for wireless remote controller: Model and SpecificationModelR05/BGE Rated voltage3.0V(2pieces of LR03 7batteries) Min voltage for sending signal of CPU2.4V Effective receiving distance8m~11m Operation condition5~60 Wireless Remote ControllerHOKKAIDO DCInverter Commercial 2010 Control Buttons andfunctions1. MODE: Once pressing, running mode will be selected inthe following sequence: AUTODRFANNOTE: No heating mode for cool only type unit. 2. FAN SPEED:Fan speed will be selected in following sequence once pressing this button:AUTO W D HIG3. Adjust : Decrease the set temp. Keeping pressing will decrease the temp with 1per 0.5s.4. Adjust: Increase the set temp. Keeping pressing will increase the temp with 1 per 0.5s.5. ON/OFF: For turning on or turning off the air conditioner.6. AIR DIRECTION: Activate swing function of air deflector. Once pressing, air deflector will turn 6°. For normal operation and better cooling and heating effect, deflector will not turn to the degree which is the state of deflector when the unit is turned off.( Only available when remote controller is used with corresponding unit.)7. HORIZ SWING:Activate or turn off horizontal swing function. (Only available when remote controller is used with corresponding unit, i.e. Ceiling & floor type)8. VERT SWING:Activate or turn off vertical swing function.(Only available when remote controller is used with corresponding unit.)9. CLOCK:Display the current time. (12:00 is displayed when resetting or electrifying for the first time.)Press CLOCK for 5s, icon indicating hour will flash with 0.5s. Pressit again; icon indicating minute will flash with 0.5s. and are used to adjust the figure. Setting or modification is effective only by pressing OK button to make confirmation.10. TIME ON:Fortime ON setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjusting the figure to 0.00 will cancel time ON setting.11. TIME OFF:For time OFF setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjust the figure to 0.00 will cancel time ON setting.12. RESET(inner located): Press this button with a needle of 1mm to cancel the current setting and reset remote controller.13. LOCK(inner located): Press this button with a needle of 1mm to lock or unlock the current setting.14. : Used to confirm the time setting and modification.15. OL/HEAT(inner located): Press this button with a needle of 1mm to shift mode between COOL only and COOL&HEAT. During setting, background light will be lightened. Factory default mode is COOL &HEAT.16. ECO: Activate or turn off economic operation mode. Itis suggested to turn on this function when sleeping. (Only available when remote controller is used with corresponding un