Available Alarms Alarm Definitions
Life safety (ie. Smoke Detection, High CO2)
Critical Lockout (High Pressure, etc)
Urgent “Trip” (1st and 2nd alarms of HPS, LPS, etc)
Normal message
Alarm Information Provided:
Timestamp, Alarm Name, Critical (Y/N), Lockout (Y/N)
Generally, “three strikes you’re out”<br>
07
Communications - BACnet Our controller is BTL Certified which guarantees interoperability with all major BAS frontends and devices. BACnet IP BACnet MS/TP<br>
08
Communications - BACnet BACnet Point Properties
AO - Analog Output
BO - Binary Output
AI - Analog Inputs
BI - Binary Inputs
AV – Analog Value
BV – Binary Value
Present Value
Relinquish Default Value
Priority Array
Point Address (Object ID)<br>
09
Communications - BACnet<br>
10
Control Methodologies (PID Feedback) Proportional
Integral
Derivative Sensor Setpoint How FAR away from setpoint? How LONG has it been away? How FAST is it trending toward or away?<br>
11
Control Methodologies (PID Feedback) Enabled Setpoint Sensor Control Signal PROCESS PID<br>
12
Control Methodologies (PID Feedback)<br>
13
Control Methodologies, Hot Gas Reheat Valve example<br>
14
Control Methodologies, Hot Gas Reheat Valve example Enabled Setpoint Sensor Control Signal<br>
15
Example of Control Modes<br>
16
Enabling TechnologiesOPTICORE LS-1628u 32-bit ARM core, Linux kernel
16GB Flash memory, 512MB RAM
Universal Inputs and Outputs Performance / Hardware Communication Features: 3 Configurable Communication Ports
Gig-E: Gigabit Ethernet Port for BACnet/IP or Modbus/TCP, also allows addressing via DHCP
Port S1: Rotary configurable EIA-485 Port for BACnet MS/TP or Modbus
Port S2: Firmware configurable EIA-485 Port for BACnet MS/TP or Modbus
6 Dedicated Communication Ports
Service Port: 10/100 Ethernet port for technician access and touchscreen connection
Rnet: ALC proprietary Sensor Network. Can be used for touchscreen connection
I/O Bus Port: for I/O point expansion via screw terminal for remote mounting
I/O Bus Edge Connector: for I/O point expansion (includes power)
Act Net: Network of communicating valves and actuator
Comm Expansion Edge Connector Port: for comm expansion<br>
18
Enabling TechnologiesOptiCore Equipment Touch 3 (EQT3) Fanless cooling system and ultra-low power consumption
Front IP65 water and dust proof
Access to most data points in the controller
Support for graphics and animations
Schedule Interface – view and edit BACnet schedules
Alarm Viewing – view the controls alarm history buffer
Customize for any application
NEW! Can access Service Port Page for communications setup<br>
19
OPTICORE EQT3 Displays<br>
20
OPTICORE EQT3 Displays Sample Screenshots<br>
21
OPTICORE EQT3 Displays Sample Screenshots<br>
22
OPTICORE EQT3 Displays Sample Screenshots<br>
23
Displays EQ-10,EQ-7,EQ-2<br>
24
Enabling Technologies:ZS Sensors Provide flexibility for multiple building applications
Low-profile, neutral color scheme
Efficient options for multiple sensors in one case
Units are daisy chainable, can control on average or min/max
Discreet service port for laptops to access the LS-1628u
Mounts on a standard 2 inch by 4-inch electrical box
Combinations can include zone temperature and/or relative humidity, CO2, VOC
Multiple models offer a choice of options, including a large easy-to-read display, local setpoint adjustment, local override, and fan control<br>
27
Sequences of Operation Addison’s Sequence of Operation is generated dynamically based on equipment code string
Standard set of control methods are written (enabled) to the control program at the end of the production line
Custom ‘special’ Sequences can be generated by Addison Controls Engineering, at cost<br>
29
Project ODO (Operational Digital Optimization) A comprehensive re-write of Addison's control logic to be more adaptable and dynamic. Leon Folts
Carlin Walser<br>
30
Need for new program Current program is conglomeration of several authors and fractured revision control.<br>
31
Need for new program Logic files used for "standard" units<br>
32
Project ODO Main Features Inclusion of High Outside Air logic
I/O assignable at runtime (Dynamic I/O), via EQT
Secondary ‘Nanny’ program for operational mode mutual exclusion and feature selection
4 compressor control logic, (2 circuit tandem), standard
Improved ECW control, besting competitor algorithms
Desiccant wheel control
A2L Alarming
FrostShield™ control, derived from over a year of remote data
Unit configuration/control methods changeable in field<br>
33
Goal: Standardized I/O locations<br>
34
Goal: Standardized I/O locations<br>
35
Goal: Standardized I/O locations<br>
36
Goal: Standardized I/O locations BINARY OUT ANALOG IN BINARY IN ANALOG OUT AUX OUT AUX IN<br>
37
Goal: Standardized I/O locations BINARY OUT ANALOG IN BINARY IN ANALOG OUT AUX OUT AUX IN New Standard Inputs
Clogged Filter BI
Condensate Overflow BI
Liquid Line Temp AI
Suction Line Pressure AI
Suction Line Temp AI<br>
38
Goal: Flexible Control Options<br>
39
Goal: Flexible Control Options The Nanny Program™<br>
40
Goal: Flexible Control Options The Nanny Program™<br>
41
Goal: Less Specials (80/20) Current State All Orders 60% SPECIAL PROGRAMMING 40% STANDARD PROGRAMMING<br>
42
Goal: Less Specials (80/20) Current State All Orders 20% SPECIAL PROGRAMMING 80% STANDARD PROGRAMMING<br>
43
Goal: T-Stat compatible Units will be able to be ordered to be compatible with Thermostats
-2 Heat, 2 Cool, Dehum, Fan, Dehum
-W1, W2, Y1, Y2, D T-stat will need to be ordered up front and may be difficult to switch to/from in the field. T-stat will require isolating relays to be added to our unit T-stat control would basically reset setpoints for Supply Air based on call.<br>
44
Equipment Control Supported Compressors
Single/Circuit
Tandem/Circuit
Single/2 Circuit
Tandem/2 Circuit
Condenser Fan control (Head Pressure Control)
Air source (includes Shared Condenser Section)
Heat Pump (optimized for FrostShield)
Water Source (Normal or Reverse)
Supply Fan control
On/Off
Constant Air Volume (CFM)
Zone Pressure (ZN-DPT)
Duct Pressure (SF-DPT)
SZVAV (ZN-T)
Outdoor Air Damper control
2 Position, Open/Closed (Occupancy based)
Modulating
Minimum Position, Zone Pressure
Economizer by OAT
Economizer by OAE (Single Enthalpy)
Economizer by OAT/RAT Reset
Economizer by OAE/RAE (Dual Enthalpy)
Demand Control Ventilation (CO2)
Exhaust Fan
On/Off
Constant Volume (CFM)
Zone/Building Pressure (ZN-DPT)
Exhaust Fan Pressure (EF-DPT)
Track Supply Fan
Track Outdoor Damper
Energy Recovery
ECW On/Off
ECW Modulating (VFD)
Plate Heat Exchanger, OA & BP
Plate Heat Exchange, Face & BP (future)
Desiccant wheel
Subcool Coil
Switchable
Modulating
Hot Gas Reheat
Lead Circuit
2 Circuit
Modulating
Heating control
Electrical
Gas
Water
Steam
Tstat and WSHP On/Off Valve<br>
45
TODO (as of 4/10/24) Update IOM documentation
Fully create Touchscreen
Create Sequence Selection software (currently under development)
Tech Service training<br>
46
TODO (as of 4/10/24) 2024 2025 June: Touchscreen August: Sequence Selection Software Oct: IOM Updated, Rep Letters, etc. Dec: Tech Service training/curriculum 1Q: H-E-B,
full production<br>